ANSI Z358.1-2014 requires an eyewash to deliver at least 0.4 US gallons per minute, approximately 1.5 L/min, for 15 minutes.
The requirement applies to plumbed eyewash and self-contained, gravity-fed portable units, with both eyes flushed simultaneously by a controlled, low-velocity stream [S2][S4].
0.4 GPM for 15 Minutes
The core performance requirement is 0.4 gpm, equivalent to approximately 1.5 L/min, sustained for 15 minutes [S4][S5]. Multiplying the minimum flow by the required duration gives a nominal flushing volume of 6 US gallons, or about 22.7 L, per station [S4].
This is a minimum performance target, not a recommendation to select a slightly larger number. The supply system, valve, nozzles, fluid, and operating conditions must all allow the station to maintain the required flow for the full 15-minute flushing period [S2].
OSHA 29 CFR 1910.151(c) requires suitable quick-drenching or flushing facilities where employees may encounter injurious corrosive materials, but it does not specify a numerical flow rate. ANSI Z358.1 is detailed guidance for assessing whether those facilities are suitable [S1].
Eyewash, Eye/Face Wash, and Shower
The main equipment options differ by the body area served, required flow, and purpose. ANSI Z358.1-2014 lists minimum flows of 0.4 gpm for an eyewash, 3.0 gpm, or 11.4 L/min, for an eye/face wash, and 20 gpm, or 75.7 L/min, for an emergency shower [S2][S3].
An eyewash is appropriate when the exposure risk is confined to the eyes. An eye/face wash is the higher-flow option where the face also requires flushing, while a shower serves body exposures involving larger affected areas [S3][S8].
Pressure Does Not Replace Flow Testing
A pressure reading alone does not prove that an eyewash meets the flow requirement. The available research identifies 30 psi as a design or operating reference for the listed eyewash arrangements, but also warns that inadequate supply pressure can reduce actual flow and impair spray pattern or coverage [S4][S5].
For a plumbed station, the most defensible acceptance method is to measure flow at the eyewash outlets, confirm that both eyes are flushed simultaneously, and verify that the station sustains at least 0.4 gpm for 15 minutes [S2][S4]. Testing the plumbing pressure alone cannot establish the delivered flow, especially when a supply is shared with other equipment [S5].
Self-contained units present a different failure mode. They depend on their stored fluid, valve, nozzle, and condition, and the fluid must be replaced after use. A unit can look complete yet fail because the reservoir does not contain enough usable solution or the flushing hardware is obstructed [S3][S4].
Installation Criteria That Affect Performance
The flushing pattern must be positioned 33 to 53 inches, or 83.8 to 134.6 cm, above the floor and at least 6 inches, or 15.3 cm, from the wall or nearest obstruction [S2][S4]. This geometry matters because a numerically correct flow can still miss the eyes if the spray is misdirected.
The station should be on the same level as the hazard, with an unobstructed travel path, and within 10 seconds of the hazard, described as approximately 55 feet at a normal walking pace [S2][S4]. Highly visible identification and adequate lighting are also part of the installation checklist [S2].
Delivered water should be tepid, defined in the research as 60 to 100 °F, or 16 to 38 °C [S2][S6]. The temperature range supports use throughout the 15-minute flushing period, rather than causing a worker to leave the station early because the water is too cold or too hot [S3][S5].
Valve and Weekly Operation Checks
The eyewash valve must be hands-free, activate in 1 second or less, and remain open until manually closed [S2][S4]. This requirement supports continuous operation during an emergency and prevents a worker from having to hold the actuator while keeping both eyes open under the flushing stream.
Operating the station at least weekly helps verify that flushing fluid is available, the valve operates, and the outlets are not blocked [S2][S4]. Annual compliance inspection is listed in the ANSI Z358.1-2014 survey, while annual flow-rate testing is also called for in guidance on fully compliant stations [S2][S3].
Outlet covers protect the spray heads from airborne contamination and must be removable by the flushing flow [S2][S4]. Covers are not a substitute for cleaning or inspection, since a damaged cover, blocked nozzle, or contaminated solution can affect whether the station works as intended.
Compliance, Maintenance, and Failure Modes
Common failure modes include flow below 0.4 gpm, flow that stops before 15 minutes, a spray pattern outside the 33 to 53 inch mounting range, nozzles positioned too close to an obstruction, and activation that takes more than 1 second [S2][S4].
Annual testing, weekly activation, correct fluid replacement, and routine pipe or valve maintenance are the practical control points. A station should also be checked for freezing protection, sediment, contamination, missing parts, and nonfunctional components, particularly in corrosive-material handling areas [S3].
OSHA enforcement can be based on 29 CFR 1910.151(c) when suitable drenching or flushing facilities are absent. Because that rule does not prescribe a flow number, the employer must assess the exposure and select a configuration capable of providing suitable protection [S1]. ANSI Z358.1 supplies the detailed performance criteria used to make that assessment [S1].
For a new plumbed specification, write 0.4 gpm minimum, 15 minutes minimum, simultaneous flushing of both eyes, 33 to 53 inch outlet height, at least 6 inch obstruction clearance, hands-free operation, and 1 second maximum activation. For verification, record actual flow over the full 15-minute test rather than relying on static supply pressure, and confirm the station remains accessible within the 10-second travel criterion [S2][S4][S5].