Configure Fire Alarm Remote Annunciators by Design

Table of Contents
  1. Define the Remote Annunciator Function
  2. Match the Annunciator to the FACP
  3. Set Address and Communication Parameters
  4. Calculate Power and Wiring Capacity
  5. Program Labels and Validate Display Content
  6. Place the Unit for Reliable Human Use
  7. Audit Configuration and Commissioning Records
Configure Fire Alarm Remote Annunciators by Design

A compatible remote annunciator can display device-level text, independent point alarm, trouble, or supervisory zone information, and custom FACP labels [S1].

The annunciator is a remote status display, not the system controller, and its practical value depends on FACP compatibility, correct addressing, power supervision, readable labels, and placement that supports response operations [S1][S4][S5].

Define the Remote Annunciator Function

A remote annunciator duplicates selected fire alarm status information at a second location while the fire alarm control panel retains control of event decisions, outputs, programming, and system reset functions [S1][S5]. Detectors, manual stations, and sprinkler flow switches report to the FACP rather than directly to the display [S5].

The Honeywell 315-080 has a backlit LCD that mimics the FACP display and can show device type, independent point alarm, trouble, or supervisory zone information, including custom labels programmed into the FACP [S1].

This division of responsibility prevents a remote display from becoming an independent control point.

Match the Annunciator to the FACP

Compatibility must be established before field configuration because the 315-080 is designed for compatible FACPs and follows the FACP manual for system information and wiring [S1]. Remote annunciator options include alpha-numeric LCD displays, approved directory panels with individual lamps, and integrated graphic displays [S4].

The comparison below covers the three principal formats against information depth, response visibility, and configuration burden.

Graphic annunciator displays must be fabricated of a durable material and include a graphic diagram identifying the building address, north arrow, and the building floor plan outline of each general type [S4]. This level of detail is appropriate for larger or operationally complex premises, while a text LCD is generally more practical where responders primarily need readable floor, zone, device, and status labels.

Set Address and Communication Parameters

fire alarm control panel annunciator remote display configuration - Set Address and Communication Parameters
fire alarm control panel annunciator remote display configuration - Set Address and Communication Parameters

Refer to the FACP manual installation section for detailed system information and wiring [S1].

Calculate Power and Wiring Capacity

The 315-080 power input operates from 18.8 VDC to 38.2 VDC, with maximum current consumption of 39 mA in normal or standby operation, 46 mA under a fault condition, and 48 mA during an alarm [S1]. An AC-fail state with the backlight off draws 15 mA [S1]. These values should be used directly in branch-circuit and power-budget calculations.

The COMM-BUS terminals are rated at 5.5 VDC and 60 mA maximum [S1].

The device measures 6.875 in wide by 5.375 in high by 1.375 in deep, equivalent to 17.46 by 13.65 by 3.49 cm [S1]. The 315-080 plastic enclosure can be surface- or semi-flush-mounted in a single, double, or 4-inch square electrical box [S1].

Program Labels and Validate Display Content

fire alarm control panel annunciator remote display configuration - Program Labels and Validate Display Content
fire alarm control panel annunciator remote display configuration - Program Labels and Validate Display Content

The most useful remote display presents intelligible point identification rather than a generic alarm code. The 315-080 can present English-language device type, alarm, trouble, supervisory zone information, and custom labels programmed into the FACP [S1]. The 315-080 can display the FACP point status, including device type, independent point alarm, trouble, or supervisory zone, and custom labels programmed into the FACP [S1].

Directory-style displays should use readily identifiable plain-English designations for related floor, zone, and status conditions [S4]. Graphic annunciator displays must be fabricated of a durable material, and an approved directory-style panel may use individual lamps [S4].

Verification should cover at least four states: normal power, alarm, trouble, and supervisory. Each annunciator should also be checked for correct Station ID, custom point text, lamp-test operation, audible annunciation where fitted, and correct response to acknowledge, silence, and reset commands sent to the FACP [S1][S4][S5]. Remote annunciators may provide limited functional switches, but the FACP remains responsible for acting on those commands [S8].

Place the Unit for Reliable Human Use

Directory-style annunciation is required in buildings with more than one story above or below grade and in buildings with more than one zone per floor under the cited code section [S4]. Remote displays should be positioned where responders can identify them without passing through hazards or losing sight of the panel, and accessibility should support trained staff as well as emergency responders [S5][S6].

For a graphic panel, the orientation of each floor-plan diagram must remain consistent with the annunciator location [S4]. The display location itself must be marked on the graphic with “YOU ARE HERE,” while the plan also identifies the fire command center or fire alarm control equipment and the fire department connection [S4].

Local audible annunciation is normally expected for alarm, trouble, and supervisory conditions, although an exception applies when the required audible annunciation is provided by adjacent fire alarm control equipment [S4]. The silencing control must be accessible only to authorized personnel [S4]. Placement decisions therefore cover sightlines, approach routes, local sound coverage, operating authority, and consistency with approved building plans, not simply the availability of wall space.

Audit Configuration and Commissioning Records

fire alarm control panel annunciator remote display configuration - Audit Configuration and Commissioning Records
fire alarm control panel annunciator remote display configuration - Audit Configuration and Commissioning Records

A defensible commissioning file should reconcile every remote display with the FACP database and the approved shop drawing. For the 315-080, the record should include the unique Station ID, DIP-switch address, protocol selection, wiring route, measured voltage, and load calculation [S1].

Distance checks should record the FACP-to-last-device run, which cannot exceed 6,000 ft or 1,800 m, and the voltage drop across the power circuit, which cannot exceed 1.2 V [S1]. The record should also identify the wire size, supervision arrangement, enclosure mounting method, and authorized operator for local controls [S1][S4].

For addressable zoning decisions before the display is specified, the addressable and conventional fire alarm panel zoning comparison provides a useful framework for deciding how much point-level detail the annunciator needs to display. The practical rule is straightforward: specify the display around the information responders must act on, then confirm that the FACP, labels, bus settings, power budget, and site location all support that workflow.

Frequently asked questions

What power and wiring specifications apply to the Honeywell 315-080?

The 315-080 operates from 18.8 to 38.2 VDC and consumes a maximum of 39 mA in normal or standby operation, 46 mA under a fault condition, 48 mA during an alarm, and 15 mA during an AC failure with the backlight off [S1].

Which operating states and identifiers should be verified after programming a 315-080?

Verification should cover normal power, alarm, trouble, and supervisory states, along with the correct Station ID and custom point text.

8 sources
  1. 315-080 - Remote Fire Annunciator
  2. The Difference Between A Fire Alarm Annunciator And ... (Oct 18, 2023)
  3. Fire Alarm Remote Annunciators & Enclosures
  4. Remote Annunciator Panels
  5. What is Annunciator Panel?
  6. Fire Alarm Annunciator Panel Placement Guide (Jul 10, 2026)
  7. Best Practices for Working with Fire Alarm Control Panels (Jul 29, 2024)
  8. What Are Remote Annunciators in Fire Alarm Systems? (Aug 27, 2020)

Need to source matching manufacturers or get a quote?

SpecForge connects industrial buyers with verified manufacturers. Submit your requirement and we will route it to matched suppliers.

Submit RFQ now →
Ask SpecForge AI