A pressure sensor can output 4-20 mA, 0-5 V, 0-10 V, millivolts, or digital data, so cable length, interference, controller compatibility and maintenance access determine the practical choice.
Conventional pressure transmitters usually provide current, voltage or digital output, while the 4-20 mA signal is the most common choice for industrial process transmission over longer cable runs [S2].
Analog output types and their practical boundaries
Millivolt output commonly follows a sensitivity such as 2 mV/V, which produces 20 mV full scale from 10 V excitation and 10 mV from 5 V excitation. Because the signal changes with excitation, millivolt sensors require a stable supply and are generally limited to short cable runs [S5].
Voltage outputs are normally 0-5 V or 0-10 V, and 0-5 V is described as one of the most widely used pressure-transducer outputs [S3][S5]. They work with unregulated supplies more readily than millivolt devices, but voltage signals can be affected by wire resistance, electrical interference and power-grid noise over extended routes [S2][S5].
Current output spans 4-20 mA and is less susceptible to interference, parasitic thermocouples, temperature drift and voltage drop from cable resistance. A 4-20 mA signal can remain reliable over runs of 1,000 ft or more, compared with the shorter reach generally associated with millivolt output [S2][S5].
Digital interfaces add configuration and diagnostic data
Digital pressure sensors can carry more than the process value, including configuration, location, logged information or alarm states. Their listed communication choices include I2C, SPI and UART, so the sensor protocol must match the receiving controller rather than merely the sensor [S5].
RS-485, RS-232 and Modbus are listed as digital transmitter interfaces, with Modbus requiring explicit support in the control system [S2]. I2C, also identified as IIC, is described as a common digital communication technique for sensors and transducers [S9].
HART is a different architecture: it superimposes digital communication on a conventional analog loop. A HART-equipped transmitter can retain a 4-20 mA process signal while carrying additional digital information, provided the receiving equipment and wiring support that combination [S2].
Fieldbus, RS-485 and other digital networks should not be confused with HART merely because all are labeled digital. Their physical layers, addressing and receiver requirements differ, so protocol compatibility must be checked at the controller, cable and transmitter levels [S2].
Output selection by distance, interference and equipment

The main decision is not simply analog versus digital. It is a four-part comparison covering signal type, usable distance, interference behavior and controller compatibility, with millivolt, voltage, current and digital links evaluated against the same installation constraints. [S2]
Millivolt output offers the lowest-cost path, but its output depends on excitation and requires amplification for longer runs [S5]. Voltage output, typically 0-5 V or 0-10 V, handles short-to-medium industrial links more cleanly and is broadly readable by control inputs [S3][S5].
For long process runs, 4-20 mA provides better rejection of interference and less sensitivity to cable resistance than voltage output [S2][S4]. Digital output is appropriate when configuration, diagnostics or additional sensor data are required, but it adds a protocol-compatibility requirement and usually a more demanding network arrangement [S2][S5].
The fitting depends on the receiving device. A 0-10 V output can be read directly with a voltmeter, while a 4-20 mA signal requires a suitable current input and loop wiring [S4]. HART should be selected when an existing 4-20 mA infrastructure must support digital communication; a native digital bus should be selected when the control architecture already uses that bus [S2].
Where each output family fits
Millivolt sensors are suitable for cost-sensitive laboratory, OEM and short-wire applications where the excitation source is regulated and the receiving amplifier is close to the sensor. A 2 mV/V device at 10 V excitation requires the receiver to distinguish a 20 mV full-scale signal, which is not a practical long-distance process-loop choice without buffering [S5].
Voltage output is common in HVAC, process-control and industrial machinery applications. Published examples include 0-5 V and 0-10 V pressure-transducer outputs, while offered 0.5-4.5 V devices provide a nonzero lower endpoint that can expose a broken wire or power failure [S1][S3].
Current output is suited to chemical production, food and beverage processing and other long-distance industrial installations where standardized 4-20 mA signals interface with alarms, recorders and controllers [S2][S3]. Digital output is better suited to smart sensors, laboratory equipment and factory systems that need configuration or diagnostic information beyond a single pressure value [S5].
Wireless interfaces also appear in the wider output taxonomy, but the reviewed material does not provide enough operating-band, range or battery-life data to support a protocol-specific selection. Wireless pressure sensing should therefore be treated as a separate engineering decision rather than assumed equivalent to wired I2C, RS-485 or HART [S1].
Installation constraints can disqualify an output

Voltage output is a poor choice for long cables exposed to severe electrical interference because grid disturbances can affect the measured signal. Current output is the stronger option in that environment because its loop behavior is less exposed to voltage-drop and interference effects [S2].
Millivolt output has two separate constraints: excitation-dependent scaling and short transmission distance. Unregulated excitation can change the full-scale output, while nearby equipment can inject noise into a low-level signal; stable excitation, short wiring and suitable amplification address those limitations [S5].
Digital systems have their own failure modes. Protocol mismatch prevents communication even if the physical output is present, and RS-485, RS-232 and Modbus wiring arrangements are not interchangeable. An HART transmitter also requires the correct load and a HART-capable communicator or controller for digital commissioning [S2].
Loop-powered current transmitters commonly use a two-wire architecture, while voltage and some digital devices require additional conductors. The identified 4-20 mA examples include a specified two-wire configuration, demonstrating why conductor count and supply method belong in the selection check rather than the output label alone [S1].
Specification records to capture before ordering
The output specification should state more than “4-20 mA” or “digital.” A traceable datasheet needs the pressure reference, minimum and maximum calibrated range, overpressure and burst limits, compensated temperature range, output span, power supply and wiring arrangement. [S5]
Concrete examples show why those fields matter. One 0.5-4.5 V device is specified for 0-200 bar relative pressure, 300 bar overpressure, 400 bar burst pressure, less than 0.5 ms response time and an operating range of -40°C to +150°C [S1].
Other examples list 4-20 mA output across gauge-pressure ranges from 100 mbar to 150 bar, absolute-pressure ranges from 250 mbar to 150 bar, and compensated temperature bands from 0°C to +50°C, -20°C to +80°C, or -40°C to +125°C [S1].
Selection records should also identify whether the output is a pressure sensor, transducer or transmitter and whether the receiver accepts the selected protocol. The pressure sensor and pressure transmitter categories overlap in practice, but transmitter specifications normally cover signal conditioning and standardized transmission output [S3].