Controller output capacity should be calculated from the installed device and its configured settings, because the LP7 is specified at 68 mA average [S6] while one Macurco HS configuration is specified at 186 mA [S4].
Typical alarm controllers provide relay contacts or 24 VDC transistor outputs for local horns, buzzers, fans, and strobes, while notification-appliance circuits commonly operate over a 16–33 VDC range [S1][S8].
What Determines Horn and Strobe Current Draw
Current draw is a circuit-design variable, not a single device label. The Macurco HS series operates from 16–33 VDC and specifies separate current values for four strobe candela settings, two volume levels, and multiple tone patterns [S4].
At 15 cd, listed current draw ranges from 0.083 A to 0.115 A across the published horn, pattern, and volume combinations. At 30 cd, it ranges from 0.080 A to 0.113 A, while 75 cd spans 0.117 A to 0.165 A and 110 cd spans 0.124 A to 0.186 A [S4].
The LP7 is a useful low-load comparison point because its specified average consumption is 68 mA across an 18–30 VDC operating range [S6]. This lower figure should not be transferred to a different model without checking that model's voltage range, flash output, and audible pattern.
Compare Three 24 VDC Notification Load Cases
For a direct current budget, the Pure Air LP7 provides 68 mA at 18–30 VDC [S6]. A Macurco HS at 15 cd consumes 83–115 mA depending on sound and pattern, with the upper value applying to the highest-load listed combination [S4].
That comparison shows why a controller should not be selected from the relay or transistor rating alone. Installers must add the calculated load of every simultaneous alarm device and retain margin for the selected flash intensity and audible pattern.
Controller Output Architecture and Circuit Requirements

The M-CONTROLLER II contains four removable relays and three 24 VDC transistor outputs for local alarms, fans, buzzers, strobes, and horns [S8].
Relay outputs control devices through their field contacts, while transistor outputs provide a switched 24 VDC source. The load on either output must remain within the controller's documented capacity, and relay contacts require suitable switching ratings for the device inrush and continuous current.
For a gas-detection architecture, the controller, notification appliance, wiring method, and alarm power source should be reviewed as one circuit. This is particularly important where horn-strobes are grouped for simultaneous notification.
Select by Voltage, Flash Output, and Audible Pattern
The documented operating voltage ranges include 16–33 VDC for the Macurco HS [S4] and 18–30 VDC for the LP7 [S6].
Flash output also changes the load. Macurco offers 15, 30, 75, and 110 cd settings, and the published maximum current rises from 115 mA at 15 cd to 186 mA at 110 cd for the high-load horn and pattern combinations [S4].
Audible output is another independent setting. The Macurco device provides continuous and Temporal 4 patterns with high and low volume, while its listed anechoic sound levels range from 82.2 dBA to 92.0 dBA across those configurations [S4]. Siemens offers high and low horn output with 12 configurable tone patterns and six candela settings: 15, 30, 75, 110, 135, and 185 cd [S2].
These options make a single headline current value inadequate for procurement. The enforceable specification should name the voltage, flash intensity, tone, volume, and number of devices operating together.
Match the Appliance to the Gas Alarm System

The Macurco HS is explicitly compatible with DVP-120 and DVP-120M control panels and Macurco 6 and 12 Series detectors, and it is rated for 32–120°F operation with 10–93% relative humidity [S4]. Its housing measures 5 1/2 by 4 3/4 by 2 inches, with flush or surface mounting on a double-gang box [S4].
The Honeywell SpectrAlert Advance family is described as usable indoors or outdoors in wet or dry applications, with weatherproofing rated to NEMA 4X and IP56, an operating range of −40°F to 151°F, and field-selectable candela settings including values from 15 through 185 cd [S1].
A gas alarm controller should therefore be specified around the actual notification circuit, while a fixed gas detector alarm path must lead to an output capable of operating the selected horn-strobe under its configured condition.
Budget for Installed Load and Failure Conditions
Controller sizing should use the published current for the configured condition, multiply it by the number of devices that can sound together, and then compare the result with the available output and power-supply capacity. For example, ten Macurco HS units at 110 cd can require up to 1.86 A when each is assigned a 186 mA combination [S4].
That arithmetic is a capacity check, not a complete design. A 24 VDC source supplying 1.86 A at 24 V would deliver 44.6 W before allowing for supply losses, control margin, and any other connected loads.
Field verification also needs to include the low-voltage condition. Honeywell specifies a 9–17.5 V operating range for 12 VDC-rated circuits with its synchronization module and 17–33 V for 24 VDC-rated circuits [S1]. The older L-Series data similarly lists 8.5–17.5 V and 16.5–33 V respectively [S3] (2017-05).
For an installed system, the trackable evidence is the controller configuration record, notification-appliance part number, voltage, candela setting, tone, volume, and measured worst-case circuit current. Those fields expose an undersized output before an alarm event turns the mismatch into a notification failure.