Thermal overload relays protect motors by sensing excess current through bimetallic elements and opening a normally closed control contact that de-energizes the contactor coil.
This guide covers direct-mounted and separately mounted relays, heater selection, wiring, commissioning, troubleshooting, and replacement decisions for industrial motor circuits up to 600 V in the Eaton Type A range.
Thermal Relay Selection Criteria
Select the relay by motor full-load current, mounting arrangement, phase count, reset mode, and control-circuit voltage; the relay must be correctly paired with the motor and contactor rather than treated as a generic overload device. [S5]
Eaton Size 1 and Size 2 Type A thermal overload relays cover motor circuits not exceeding 600 V, with maximum current ratings of 26.2 A and 45.0 A respectively [S3]. Ambient-compensated versions use light-gray reset rods, while non-compensated versions use red reset rods, providing a visible installation check [S3].
The Entlec M 06 offers selectable hand or automatic reset, a blue button for stopping and hand reset, and a yellow mechanical indicator that appears after the relay has tripped [S5]. These ranges represent product options, not a substitute for checking the motor nameplate and the relay instruction leaflet.
Install the relay only after the motor nameplate current, contactor size, conductor size, control circuit, and required protection function have been matched.
Mounting Orientation and Thermal Environment
Install a Size 1 or Size 2 Type A overload relay on a vertical surface with the control terminals at the bottom [S3]. This orientation supports the intended operating conditions and removes an avoidable source of installation error.
Place the relay preferably in the same ambient as the motor and away from drafts [S3]. Ambient compensation matters because the relay responds to heat generated by motor current; a non-compensated design or an unsuitable installation environment can alter the effective protection margin. The Eaton Type A relay is available in ambient-compensated and non-ambient-compensated constructions, as indicated by light gray and red reset rods, respectively [S3].
For direct mounting, align the overload relay leg with the hole in the magnetic contactor and insert it in the direction shown by the arrow [S4]. The Entlec M 06 mounts directly beneath KL 2 and KL 4 contactors with screw terminals, while separate mounting uses an adapter block that snaps onto 35 mm DIN rail [S5].
Do not force a relay into a mismatched contactor. If the interface, terminal arrangement, or mounting hole does not match, use the designated separate mounting method or replace the assembly with compatible equipment.
Heater, Conductor, and Control Wiring

Select the heater elements in accordance with the motor current and the relay’s selection criteria, because the replaceable heater elements carry the motor current [S3].
Secure every wire with the correct terminal screw and use wire sizes appropriate to the applied voltage and flowing current [S3][S4]. For separate mounting, the contactor-to-relay power conductors must match the heater element rating and the motor circuit design. Incorrect wire size can prevent reliable operation or create a fire hazard.
Connect the normally closed control contact in series with the magnetic contactor coil [S3]. When the bimetallic elements trip, the heated strip bimetals deflect to open the normally closed contact and disconnect the overloaded motor [S3].
Keep control wiring and power wiring physically controlled during installation. The relay module commissioning procedure provides a useful framework for checking terminal condition, wiring continuity, and functional response before the motor is started.
Reset Mode, Indicators, and Test Function
Choose manual or automatic reset before energizing the control circuit; the Type A relay is normally supplied for hand reset and can be changed to auto reset by repositioning the reset plate and tightening the reset screw [S3].
Manual reset requires an operator to correct the overload cause and press the reset rod before the relay can restart the motor. Automatic reset closes the control circuit again after the relay cools and resets, so it must be used only where restarting after a fault is acceptable [S3].
The Entlec M 06 provides hand or automatic reset selection, a blue button for stopping and hand reset, and a yellow mechanical indicator that appears after the relay has tripped [S5].
Do not use an automatic-reset relay as a substitute for fault investigation. Repeated restarts can reapply full voltage to a motor that is overloaded, stalled, mechanically jammed, or incorrectly wired.
Commissioning Tests and Acceptance Criteria

Commission the relay with the motor circuit isolated and the control circuit energized only after all terminals have been checked; the acceptance test must demonstrate both the tripped state and the selected reset method. [S3]
Check the following conditions before starting the motor:
1. Confirm that the relay is vertical, securely mounted, free of damage, and installed in a suitable ambient. For Type A units, the control terminals must face downward [S3].
2. Verify all three heater elements against the motor nameplate and the approved heater selection table, then confirm that every conductor is correctly landed and tightened [S3].
3. Operate the manual test or trip function. The NC auxiliary contact must open, the contactor coil must de-energize, and any NO trip-indication contact must close [S3][S5].
4. Restore manual or automatic reset as designed. A manual-reset relay must remain open until the reset control is operated; an automatic-reset relay must reset only after its internal thermal element has cooled sufficiently [S3].
5. Observe the motor at no-load and at the expected process load. Record motor current against the relay setting and verify that the relay does not trip during normal operation.
For phase-failure-sensitive equipment, verify the specified phase-loss response with the approved test procedure rather than relying on visual observation alone. The M 06 documentation identifies phase-failure sensitivity under IEC 947 as a product feature [S5].
Failure Modes, Corrective Actions, and Limits
If the motor does not start after a trip, treat the relay as a symptom rather than resetting it repeatedly. The motor may be overloaded, stalled, phase-failed, or incorrectly wired, and the relay should not be replaced until those causes are checked. [S3]
For a relay that fails to trip during its test function, check that the reset mode is set to hand, the test mechanism is not locked by its cover, the auxiliary contacts are wired correctly, and the contactor coil circuit is continuous [S5]. If the relay was mounted incorrectly, damaged, or exposed to severe contamination, replace it rather than adjusting the calibration.
For nuisance tripping, verify the heater range, motor current, conductor sizing, ambient temperature, mounting position, and ventilation. Do not compensate for persistent nuisance trips by selecting a larger heater or bypassing the relay without an engineered motor-protection review.
ABB Type BL-1 installation material identifies a separate limitation: assembly and adjustment of the thermal unit require alignment fixtures, special tools, and test equipment to locate the position [S1]. Such setup tasks should be assigned to qualified personnel using the manufacturer-specific procedure, not improvised in the field.
Replace the relay when the device is damaged, the thermal mechanism has been operated outside its prescribed limits, calibration has been disturbed, required accessories are missing, or the relay has reached the end of its specified service life. A solid-state relay is not a drop-in substitute for a bimetallic thermal overload relay; its rated operation requires a heatsink or metal plate, and its derating curves govern permissible load [S6].
Installation Record and Service Traceability

A complete installation record should identify the relay model, serial number, heater range, motor full-load current, mounting orientation, reset mode, contactor model, backup fuse type, and test results, because these values determine whether a future fault is caused by the relay or by the protected circuit. [S3]
For example, the Entlec M 06 documentation specifies a 10.3 × 38 mm aM fuse for Type 2 short-circuit protection under the cited IEC 947-4 arrangement, with separate gL values and fuse-terminal provisions listed for each current range [S5]. Record the exact backup protection selected for the installed motor circuit rather than copying a generic fuse value.
Save the relay instruction leaflet, wiring diagram, approved heater selection, and commissioning results with the equipment maintenance file. The Eaton Type A leaflet is IL14568, while the Fuji manual covers the TK13, TK25, TK26, and TK26E thermal overload relays with long-time, quick, separate-mounting, and auto-reset variant codes [S3][S4].
Track two service signals for every installation: whether the relay trips during expected motor loading, and whether any mechanical trip indication remains after the cause is removed. Repeated unexplained trips, failed test operations, or damaged heaters require technical review before another motor start.