Pt100 Head Transmitter Total Error at 100 °C

A Pt100 Class A element contributes ±0.35 °C at 100 °C, so the complete transmitter system error is the sensor tolerance plus input, output, ambient, installation, and lead-resistance effects [S3].

The usual head-transmitter arrangement uses a three- or four-wire Pt100 and converts 138.51 Ω at 100 °C into a 4–20 mA signal over a configured 0–100 °C span; the transmitter’s datasheet, wiring, calibration, and thermal conditions determine the remaining error [S1][S2][S3].

What total error should be specified?

The defensible specification is an error budget, not one headline percentage. For a Pt100 to IEC 60751, Class A is ±(0.15 + 0.002·|t|) °C and Class B is ±(0.3 + 0.005·|t|) °C. At 100 °C, those become ±0.35 °C and ±0.8 °C respectively [S3].

Add the transmitter’s specified input accuracy, analog output accuracy, and ambient-temperature effect. A head transmitter moves the resistance-to-temperature conversion from the PLC to the sensor head, but it does not eliminate sensor tolerance, lead effects, or calibration error. The temperature transmitter datasheet must therefore be reviewed for the exact sensor type, configured span, output mode, and ambient conditions.

For comparison, a head transmitter specified at ±1 °C accuracy for a 0–100 °C application does not automatically provide ±1 °C total accuracy. With a Class A Pt100, the simple worst-case addition would be ±1.35 °C, plus any separately specified wiring, installation, or environmental effects [S3][S4].

Pt100 error at 100 °C

IEC 60751 defines the Pt100 relation using a platinum temperature coefficient of 0.00385 Ω/Ω/°C over 0–100 °C. A nominal Pt100 measures 100 Ω at 0 °C and 138.51 Ω at 100 °C [S2][S4].

The Pt100 does not change by exactly 0.385 Ω for every degree: IEC 60751 uses α = 0.00385 Ω/Ω/°C as the mean temperature coefficient between 0 and 100 °C, and a 100 Ω Pt100 reaches 138.51 Ω at 100 °C [S2]. A transmitter using the correct Pt100 curve can linearise this relationship; treating the sensor as a fixed 0.385 Ω/°C line introduces growing error at higher temperatures.

The RTD Pt100 tolerance class is one of the few values that can be calculated directly at 100 °C. Class A gives ±0.35 °C, while Class B gives ±0.8 °C. The cited guide describes PT100 sensors as generally being used below about 500 °C [S2].

How much do wiring and installation add?

what total error does a Pt100 plus head transmitter give at 100 C? - How much do wiring and installation add?
what total error does a Pt100 plus head transmitter give at 100 C? - How much do wiring and installation add?

Copper resistance also changes by about 0.39% for each degree Celsius of cable temperature, so the error is not fixed under seasonal conditions [S2].

A three- or four-wire connection compensates for lead resistance, while a transmitter mounted in the connection head limits the resistance-measurement path and makes long cable runs less sensitive to lead effects [S2][S4]. For longer cable runs, the cited guide recommends a 4–20 mA head transmitter [S4].

Transmitter and loop contributions

At 100 °C on a correctly configured 0–100 °C, 4–20 mA head transmitter, the output should be 20 mA. The loop signal does not measure temperature directly: the PLC or receiver maps 4 mA to the lower range and 20 mA to the upper range, then scales the current to engineering units [S1].

Range mismatch can therefore create errors much larger than the Pt100 tolerance. One commissioning example documents a transmitter labeled and configured for a 0–100 °C span in which the Siemens input reported approximately 70 °C for a true 40 °C, an over-reading of about 27 °C [S1].

Configuration should be verified from the device interface rather than inferred from the label. The cited Siemens S7 procedure sets the lower and upper process-variable limits to 0 °C and 100 °C, then checks 4 mA and 20 mA trim only when primary calibration is required [S1].

Which installation gives the lowest error?

what total error does a Pt100 plus head transmitter give at 100 C? - Which installation gives the lowest error?
what total error does a Pt100 plus head transmitter give at 100 C? - Which installation gives the lowest error?

The lowest practical installation error normally combines a Class A Pt100, three- or four-wire connection, a head transmitter with stated input accuracy over the complete 0–100 °C span, and verified 4–20 mA scaling. This arrangement removes much of the copper resistance error while preserving a defined sensor tolerance and calibrated signal path [S2][S3][S4].

The head-transmitter option is therefore the stronger choice for long runs, while a direct RTD input can be acceptable where the input itself supports three- or four-wire compensation and the installation remains electrically suitable.

Construction should be compared against operating range and mechanical conditions. Thin-film elements are smaller, faster, cheaper, and more resistant to vibration, while wire-wound elements offer broader temperature coverage and are described as more stable at high temperature [S2]. For a 100 °C measurement, both can be viable if their specified limits, tolerance class, sheath material, and immersion construction match the service.

Calculation method for an error budget

For a worst-case estimate, add the absolute Pt100 tolerance at 100 °C, transmitter input accuracy, analog output accuracy, and applicable ambient or installation terms. A Class A Pt100 contributes 0.35 °C, and a transmitter specified at ±1 °C contributes 1.0 °C, producing 1.35 °C before other terms [S3][S4].

For statistical combination, root-sum-square treatment may be justified only when the manufacturer’s specifications define independent uncertainties and their test conditions. Do not combine ±0.35 °C sensor tolerance, transmitter accuracy, and output accuracy by root-sum-square unless the applicable datasheets support that treatment. Also distinguish the accuracy referenced to 25 °C from the additional temperature coefficient over hot outdoor installations [S3].

Verification should include resistance checks at known temperatures, inspection of the configured 0–100 °C span, a 4 mA and 20 mA check where required, and comparison against a calibrated reference at 100 °C. The differential-pressure transmitter encyclopedia is not part of this measurement chain, but the same discipline of checking zero, span, and full-scale output applies.

Use the final datasheets to close the budget: Pt100 tolerance class, connection method, transmitter input specification at 100 °C, output accuracy, ambient coefficient, and installation method. If those documents are unavailable, ±0.35 °C is the sensor contribution only, not the defensible total system error.

4 sources
  1. PT100 4-20mA Transmitter Scaling on Siemens S7: Troubleshooting (2026/09/24 19:35:11)
  2. PT100 sensors: the curve, 2-, 3- and 4-wire connections and the errors (2026/09/20 00:00:00)
  3. Temperature Transmitter Selection: Head vs Rail Mount, HART, Dual Sensors and Sensor Ma… (2026/11/02 00:00:00)
  4. PT100 to LOGO! 0BA8: Wiring, Scaling & Verification (2026/09/14 22:37:14)

Need to source matching manufacturers or get a quote?

SpecForge connects industrial buyers with verified manufacturers. Submit your requirement and we will route it to matched suppliers.

Submit RFQ now →
Ask SpecForge AI