A Pt100 temperature transmitter normally maps a programmed lower temperature to 4 mA and an upper temperature to 20 mA, with a 16 mA span representing the configured engineering range [S1][S2].
The range must match the Pt100 element, lead resistance, measurement accuracy, expected process temperatures, and downstream control or recording limits; the RTD Pt100 is not the transmitter’s adjustable output span.
Engineering Range Meaning and Output Mapping
The engineering range is the temperature interval assigned to the transmitter’s analog output. For a temperature-linear 4–20 mA transmitter, the lower range point is fixed at 4 mA and the upper range point at 20 mA, while both temperature endpoints can be assigned [S1].
A 4–20 mA transmitter outputs 4 mA at the low end of the temperature scale and 20 mA at the maximum temperature value [S4]. The output relationship is:
T = T_low + ((I - 4 mA) / 16 mA) × (T_high - T_low)
At 12 mA in that example, the calculated temperature is 25 °C. Incorrect endpoint entries therefore create a systematic scaling error even when the transmitter and sensor are operating correctly.
Some programmable models also support 0–10 VDC, 2–10 VDC, and 0–20 mA outputs, with output type selected by jumpers or a programming tool [S2]. The engineering principle remains the same: the configured temperature span must be mapped onto the selected output span.
Range Selection Criteria
Set the range from the actual process requirement, not from the full resistance capability of the sensor. , but one ABB TS 04 transmitter imposes a maximum programmed span of 1,050 K and a minimum span of 40 K [S1].
Use these criteria in sequence:
1. Confirm the normal process minimum and maximum, including expected excursions.
2. Keep both endpoints inside the intended operating envelope of the installed sensor.
3. Verify that the programmed span meets the transmitter’s minimum and maximum span limits.
4. Confirm the output type, such as 4–20 mA for a long-distance industrial loop.
5. Check the power supply, loop resistance, wiring arrangement, and downstream input range.
6. Record the lower and upper endpoints, output units, and alarm or fault settings in the commissioning record.
Narrowing the range to the fraction of the sensor signal actually used improves output resolution, but it does not improve the physical resolution of the Pt100 element [S2]. Sensor accuracy, element tolerance, lead effects, and transmitter error remain separate contributors to total measurement uncertainty.
Preset Ranges Versus Fine-Tuned Endpoints

Preset engineering ranges are suitable when a documented temperature band matches the process. The Vector SCC-T1-Tp1 offers eight DIP-switch presets: -40 to 60 °C, 0 to 50 °C, 0 to 100 °C, 0 to 200 °C, -60 to 200 °C, -40 to 150 °C, -20 to 80 °C, and -15 to 35 °C [S2].
Fine-tuned endpoints are preferable when the process has a nonstandard band, such as -30 to 45 °C for an outdoor installation.
The temperature transmitter configuration method is less important than the resulting endpoints. Verify the displayed or readback values rather than assuming a jumper position or saved configuration was applied.
2-Wire and 3-Wire Effects on Range Setup
Engineering-range configuration does not eliminate errors caused by the sensor and wiring. In a 2-wire connection, lead resistance adds directly to the measured Pt100 resistance, so an incorrect range can amplify the resulting temperature error [S1][S3].
A 3-wire arrangement compensates for equal cable resistances when all three conductors have identical resistance.
For a 2-wire input, the transmitter adds the cable resistance to the nominal Pt100 value when evaluating temperature. The sensor, extension leads, and transmitter should therefore be commissioned as one measuring chain, with the actual ohms contribution calculated from the installed cable length and conductor resistance.
Do not substitute a transmitter configured for a different sensor type or wiring topology. The core input requirements to verify are Pt100, 2-wire or 3-wire, the programmed engineering range, and the required output [S1].
Comparison of Common Pt100 Transmitter Ranges

The correct range depends on process coverage, available output resolution, and configuration convenience. A wide industrial band offers headroom but uses less of the 4–20 mA scale for a narrow process, while a narrow band increases output resolution without improving the underlying sensor accuracy. [S4]
Commissioning Checks and Failure Modes
The ABB TS 04 uses 4 mA and 20 mA as normal output limits and 22 mA as an error current. Error signaling covers sensor or cable break, sensor signal outside -200 to 850 °C, short circuit, or device error [S1]. Verify that the controller recognizes this fault state rather than treating it as a valid measurement.
For a 4–20 mA loop, 22 mA can be differentiated from 20 mA only when the receiver, wiring, power supply, and load support the extra current. A 250 Ω burden resistor gives 1.00 V at 4 mA and 5.00 V at 20 mA; a 165 Ω resistor produces 0.66 V to 3.30 V for a 3.3 V input [S4].
Other checks include confirming an 8–30 VDC supply for the TS 04, observing its 3.8 mA current consumption, and checking that the loop remains within the rated load [S1]. A transmitter display can show configured values, but the temperature recorder or PLC should also be checked against the as-installed configuration.
Common range-setting errors include swapping lower and upper endpoints, entering degrees Fahrenheit into a Celsius field, assuming an output-span change improves Pt100 accuracy, and failing to account for 2-wire lead resistance. The procedure for Pt100 transmitter zero and span configuration provides a practical framework for documenting those checks.
Standards, Traceability, and Sourcing

The Pt100 resistance scale is defined by DIN/IEC 60751, also identified as IEC 751 in the cited material. It specifies 100.00 Ω at 0 °C and a temperature coefficient of resistance of 0.00385 Ω/Ω/°C between 0 and 100 °C [S3].
IEC 60751 also defines common element tolerances. Class A is ±(0.15 + 0.002t) °C, while Class B is ±(0.3 + 0.005t) °C; at 0 °C, their resistance tolerances are ±0.06 Ω and ±0.12 Ω respectively [S3]. The selected transmitter range should remain within the temperature domain over which the sensor’s stated tolerance applies.
The ABB TS 04 input specification identifies the resistance thermometer as Pt100 under IEC 751, with a stated deviation of 0.15%. Its balancing uncertainty is below 0.15% or 0.15 K, whichever is greater, and linearity deviation is below 0.05% or 0.05 K [S1].
Do not treat these transmitter figures as a replacement for the Pt100 element tolerance. The measurement chain includes the sensor, leads, transmitter, loop receiver, and reference standard. During acceptance, record the transmitter model, serial number, sensor class, wiring arrangement, engineering endpoints, output type, supply voltage, and observed current at both endpoints.