Zero and span are two independent calibration controls that define where a Pt100 transmitter starts and how its output changes across the selected range [S1].
The distinction applies to any 4–20 mA temperature transmitter: zero concerns the lower range value, while span concerns the slope toward the upper range value [S1].
Zero and Span in a Pt100 Measurement Loop
Zero error is the constant difference between the indicated and true temperature at the lower calibration point. If a transmitter assigned 0 °C reads -1.2 °C at 0 °C, its zero error is -1.2 °C, which is corrected as an additive offset [S1].
Span error is a gain error in the input-to-output relationship. If the transmitter is correct at 0 °C but reads 99.0 °C at 100 °C, the span error is -1.0% of reading, and the induced error increases with input magnitude [S1].
For a linearized transmitter configured from 0 to 500 °C, the output relation is Iout = 4 mA + 16 mA × (Tmeasured - TLRV) / (TURV - TLRV). Its nominal slope is therefore 0.032 mA/°C, while a -1% span error reduces that slope to 0.03168 mA/°C [S1].
The resulting error at 250 °C would be 2.5 °C and at 500 °C would reach 5.0 °C under that example. This is why the same span error has a much larger process impact at the top of the range [S1].
How Zero and Span Parameters Map to a Pt100
The zero parameter identifies the lower range value selected in the transmitter, not necessarily an electrical reading of 0 Ω. A transmitter configured for 0 to 400 °C maps 0 °C to 4 mA and 400 °C to 20 mA [S1].
The span parameter describes the difference between the upper and lower range values. In that 0 to 400 °C configuration, the span is 400 °C, even though the output current spans only 16 mA from 4 mA to 20 mA [S1].
Span should not be confused with the output-current interval. The 4–20 mA interval is the transmitter output range, whereas span is the numerical difference between TURV and TLRV in the selected engineering unit [S1].
These concepts also apply to RTD Pt100 temperature transmitters, where the sensor resistance is converted into a calibrated temperature signal before the transmitter applies its configured range and output mapping.
Correcting Zero and Span Errors

Zero adjustment corrects the transmitter output at the lower range value. It is an additive correction and addresses offset caused by factors such as reference-junction drift, input bias current, converter offset, or installation effects [S1].
Span adjustment corrects the slope between the lower and upper range values. It is a multiplicative correction intended to address gain drift associated with resistor aging, reference-voltage drift, or amplifier gain drift [S1].
The error model is Tindicated - Ttrue = εz + εs × Ttrue, where εz is zero error and εs is fractional span error. Checking the transmitter at a third point can reveal whether the remaining error behaves linearly or contains a non-linearity that needs a separate solution [S1].
Zero and Span Adjustment Methods
Typical analog instruments use electronic trim controls, potentiometers, or manufacturer-specific tools to alter the output at the lower and upper calibration points. The controls correct the transmitter, they do not replace a calibrated reference [S2].
Digital transmitters may provide trim commands through their configuration interface, while the temperature transmitter architecture determines whether correction is applied through hardware trims, software parameters, or both [S1].
Installation can itself change the reading. Tightening when installing a pressure transducer or transmitter can affect its output reading [S4].
Pressure transducers and transmitters are factory calibrated to read a fixed output range, and the effects of tightening during installation can affect the output reading [S4].
Choosing the Correct Adjustment for the Job

When an installed pressure transmitter is calibrated, its zero and span offsets can be eliminated using system settings or adjustment features incorporated in the transmitter [S4].
Zero offset and span tolerance are the actual signal outputs at zero and full span, and offset tolerance is usually expressed as a percentage of full span [S4].
Do not use zero trimming to conceal a span problem. If the transmitter reads correctly at one endpoint but has a proportional error, modify the slope; if it has the same absolute offset across the range, modify the zero [S1].
This distinction is critical when matching Pt100 sensors to transmitters, because sensor tolerance, wiring resistance, configured range, and transmitter calibration contribute separately to the final indicated temperature.
Acceptance Checks and Traceability
Record the configured TLRV and TURV before adjustment, then measure the output at both endpoints and at least one intermediate point. For a 4–20 mA loop, the nominal endpoint outputs are 4 mA and 20 mA, with 12 mA representing the midpoint of the output interval [S1].
A properly calibrated analog temperature transmitter produces an output that is linear with respect to the measured temperature across its working range [S1].
Do not infer temperature accuracy from loop-current agreement alone. A transmitter can produce the expected 4, 12 and 20 mA values while the underlying Pt100, wiring or reference input introduces its own error. Each element in the measuring chain must be assessed separately [S1].
Calibration records should identify the instrument, range, reference method, as-found values, adjustment settings and as-left values. The reference material and measurement chain should remain traceable to the recognized temperature scale, with the field guide specifying NIST ITS-90 for this purpose [S1].
Limits, Failures, and Common Misconceptions

Zero is not synonymous with 0 °C. A transmitter configured from -50 to 150 °C still uses 4 mA at -50 °C and 20 mA at 150 °C, so changing its lower range value changes what the zero setting means [S1].
Span is not an independent additive offset. Applying a span error as a fixed temperature correction causes the correction to be wrong at every point except the endpoint, because a gain error grows in proportion to the measured value [S1].
Field adjustment also has limits. Components age, environmental stress and electrical noise can produce drift, while an unsuitable reference or an unstable loop can make a valid transmitter appear defective. Replaceable instrumentation may be preferable when adjustment hardware is unavailable or the drift exceeds the transmitter’s tolerance [S2].
For any calibration, the most traceable next node is a three-point check against a reference: verify the lower range value, apply the upper-range span correction, then verify zero again at the lower range value.