Under IEC 60751:2022, Pt100 tolerance is temperature-dependent: Class AA starts at ±0.10 °C, while Classes A, B, and C start at ±0.15, ±0.30, and ±0.60 °C at 0 °C [S2].
Select the grade from the required error at the actual process temperature, then verify element construction, operating range, wiring, and total measurement error before approval [S1][S2].
Tolerance equations and class comparison
The four IEC 60751:2022 classes use different temperature-error formulas: AA is ±(0.10 + 0.0017 × |t|) °C, A is ±(0.15 + 0.002 × |t|) °C, B is ±(0.30 + 0.005 × |t|) °C, and C is ±(0.60 + 0.01 × |t|) °C [S2].
Class B is normally sufficient for coarse alarms, heater protection, or trend displays, while the tolerance difference between Classes A and B is not a fixed number because it grows with temperature according to their respective formulas.
For example, a requirement better than ±0.5 °C points toward Class A or AA at the relevant temperature, while a trend display, coarse alarm, or heater-protection function can usually accept Class B if its full temperature-dependent error meets the process requirement [S2].
Valid ranges depend on element construction
Class A applies from −100 to +450 °C for wire-wound construction and −30 to +300 °C for thin-film construction [S2].
Class B extends to −196 to +600 °C for wire-wound elements and −50 to +500 °C for thin-film elements.
A drawing that requests “Class A to 600 °C” is incomplete at best. For a wire-wound element, Class A ends at +450 °C; for a thin-film element, it ends at +300 °C. Above either construction-specific limit, specify a class whose validity range covers the service temperature rather than extrapolating the Class A equation [S2].
Where each tolerance class fits

Class AA is appropriate when the specified error at 0 °C is ±0.10 °C and the complete measurement chain is correspondingly stringent. Its proportional term is 0.0017 × |t| °C, so it remains the tightest grade within its construction-specific range [S2].
Class A is the practical choice for precision process control, laboratories, calibration equipment, and critical product-temperature measurement. It requires better than ±0.5 °C performance in the cited selection guidance, but the full tolerance must be checked at the operating temperature, not at the ice point [S2].
Class B is normally sufficient and less costly for general industrial temperature measurement, including steam lines, food vessels, and many laboratory baths [S1][S2]. Class C is not an accuracy upgrade: it provides a wider usable range but permits substantially more error, including ±3.60 °C at 300 °C [S2].
The decision is not suitable for every class at every temperature.
Wiring and installed error can erase the grade advantage
A two-wire Pt100 includes lead resistance in the measurement. Three-wire wiring compensates for much of this error, while four-wire measurement offers the best accuracy, particularly over long cables, at greater installation complexity and cost [S1].
Keep measuring current low because self-heating can shift the indicated temperature. For commissioning, disconnect the sensor from the control circuit, verify the meter and ambient conditions, and check cable resistance, terminals, and connection stability [S1].
The Pt100 transmitter engineering range setup matters because the transmitter, configured range, wiring, and sensor must be treated as one error budget, not as separate accuracy claims.
Pt100 versus Pt1000 for long installations

A Pt100 has 100 Ω nominal resistance at 0 °C, while a Pt1000 has 1000 Ω, giving the Pt1000 ten times the base resistance and a larger resistance change for the same temperature variation [S3].
The higher resistance of a Pt1000 reduces the proportional effect of cable resistance and generally improves noise immunity compared with a Pt100 [S3]. It can also support economical two- or three-wire installations, while Pt100 measurements commonly use three- or four-wire circuits where lead-resistance compensation matters [S3].
Element tolerance class remains a separate decision. A Class A Pt100 and a Class A Pt1000 have nearly identical specified temperature accuracy when manufactured to the same class, because the principal difference is resistance value rather than tolerance class [S3].
Procurement and inspection controls
Specify the nominal resistance, IEC 60751:2022 tolerance class, applicable temperature range, element construction, sheath material, wiring method, and required certificate. A calibration certificate does not automatically establish compliance with a particular IEC tolerance class, so the purchase document must state the claim being purchased [S1].
Check resistance at the ice point against the grade-specific window: Class A is 99.94 to 100.06 Ω and Class B is 99.88 to 100.12 Ω [S2].
For a PT100 RTD, also verify immersion depth, sheath compatibility, response time, sealing, vibration resistance, and the transmitter specification. A precise element installed with inadequate immersion, unstable connections, or excessive measuring current will not deliver its catalog tolerance [S1].
Engineering selection rule

Calculate the maximum allowed error at the normal operating temperature, not at 0 °C. Compare that value with the grade formula and construction-specific range, then add lead resistance, transmitter error, installation effects, and any required safety margin [S1][S2].
For a laboratory or reference measurement, specify Class AA if the stated accuracy requires it and the temperature lies within the element’s valid range. For critical industrial control, Class A is normally the first candidate. Class B is the sensible default for general monitoring, while Class C is justified mainly where a wider temperature range is more important than tight accuracy [S2].
The next procurement check is documentary: confirm that the quotation names IEC 60751:2022, the exact class, element type, maximum operating temperature, and test tolerance. For high-accuracy installations, request traceable comparison data and verify the assembled loop rather than accepting the bare element specification alone [S1][S2].