The method pairs one Pt100 with one temperature transmitter, stores its measured temperature-resistance characteristic in the transmitter, and uses the Calendar van Dusen equation for linearization [S1][S2].
Why the Standard Pt100 Curve Is Not Enough
Those classifications apply to the RTD element, while an installed measuring point also includes the transmitter, wiring, thermal response, and process environment. A transmitter configured only with standardized IEC 60751 coefficients cannot compensate for the individual resistance-temperature curve of the connected sensor [S1][S2].
A real sensor may differ because of platinum and manufacturing variation, so a generic transmitter can assign the wrong temperature even when the resistance measurement itself is precise [S1].
Calendar van Dusen Constants and Linearization
The sensor-specific relationship is represented by the Calendar van Dusen equation, RT = R0[1 + AT + BT² + CT³(T - 100 °C)], with R0 representing the sensor resistance at 0 °C [S1].
The coefficients are then programmed into the transmitter paired with that sensor, replacing the standard coefficients used for an ordinary Pt100 [S1][S2].
Matching is not limited to checking the nominal 100 Ω resistance. It calibrates the complete sensor characteristic, allowing the transmitter to correct the curve rather than merely calculate temperature from an assumed ideal curve [S2].
Measured Accuracy Gains Across Applications

The matched sensor and transmitter accuracy is ±0.11 °C, which is over three times better than a standard grade A sensor with ±0.35 °C accuracy. This comparison depends on the specified sensor and transmitter combination, not on transmitter model alone [S6].
The transmitter converts the RTD resistance signal into the configured temperature output after applying the stored constants [S1].
Choosing the Correct Sensor and Transmitter
Configuration starts with the sensor designation: Pt100 and Pt1000 are not directly interchangeable because their resistance ranges and measurement-circuit requirements differ [S5]. The connected instrument must support Pt100 measurement, including the temperature-resistance relationship and relevant temperature coefficients.
The transmitter also needs the correct RTD input type and connection configuration. A Pt100 RTD selected for 2-wire, 3-wire, or 4-wire measurement has different lead-resistance behavior, so transmitter configuration and installation wiring must be treated as part of the measuring point [S5].
The approach suits critical chemical-process control, reactor monitoring, heat-exchanger inlet and outlet measurements, distillation troubleshooting, and other applications where a small temperature offset can influence control or product quality [S2][S3].
Installation and Calibration Constraints

Calibration accuracy does not remove thermal lag. A Pt100 can take a long time to reach the device-under-test temperature, and its thermal mass and resistance to the measured surface can create errors larger than the electrical measurement uncertainty [S4].
Four-wire measurement can help remove lead-resistance effects, but it does not correct poor thermal coupling. Probe dimensions, mounting method, immersion depth, insulation, and environmental exposure must be evaluated separately from the sensor's resistance tolerance [S4][S5].
Calibration should therefore use a stable thermal environment and enough settling time for the sensor to approach the reference temperature. The selected points must also cover the intended operating range because the A, B, and C coefficients are derived for a defined temperature interval [S1][S4].
The calibration record should identify the sensor serial number and transmitter serial number as a matched set. Replacing one component without checking compatibility can invalidate the stored sensor-specific curve and the accuracy achieved through matching [S2].
Procurement and Maintenance Requirements
IEC 60751 class limits describe sensor deviation from the ideal curve at the stated test condition, not the complete field error of the transmitter and thermowell assembly [S2][S3].
Require the transmitter data set to include the sensor's R0 value and the A, B, and C constants, or a dedicated matched-part number. The factory document for a matched pair should identify both components and preserve their traceability [S1][S2].
Maintenance checks should verify that the transmitter still contains the intended constants, that the sensor has not been replaced, and that wiring configuration remains unchanged. A field comparison against a reference thermometer can verify the installed error, but it cannot repair an incorrect sensor-to-transmitter pairing by itself [S2][S7].
For Pt100 thermowell assemblies, the mechanical fit and insertion condition can be as important as the electrical match; further guidance is available in the guide to replaceable Pt100 thermowell inserts.
Track the sensor-specific calibration data, operating range, and transmitter configuration through commissioning, and repeat the comparison after sensor replacement, thermowell work, or any change to the 2-wire, 3-wire, or 4-wire connection.