Standard Pressure Transmitter Output Signals

A standard industrial pressure transmitter usually outputs a proportional 4–20 mA current signal, with 4 mA at the lower range and 20 mA at the upper range [S1][S2].

The output depends on the installed instrument: 0–5 V, 0–10 V and 1–5 V are also used, while raw pressure transducers may provide millivolt excitation-dependent outputs [S3][S4].

4–20 mA Is the Standard Process Output

Industrial pressure transmitters condition the sensor output and commonly provide a 4–20 mA current signal [S1][S3]. At the calibrated lower measurement limit, the transmitter draws 4 mA; at the calibrated upper limit, it draws 20 mA [S2].

This relationship is linear: 4 mA represents the minimum or zero pressure, while 20 mA represents the maximum selected range. For an example spanning 0–100 psi, 4 mA corresponds to 0 psi and 20 mA corresponds to 100 psi, subject to the transmitter’s configured range.

The 4 mA lower point provides a live zero. A reading at 0 mA can therefore indicate a broken wire, open circuit or failed transmitter rather than a valid zero-pressure condition [S2]. This diagnostic distinction is one reason current output is used in oil and gas, water treatment, pharmaceutical and manufacturing applications [S2].

Voltage Outputs Are Also Available

Conditioned pressure transmitters can output 0–5 V or 0–10 V, and some designs use 1–5 V [S1][S3]. These are analog voltage signals proportional to the measured pressure. Unlike a 4–20 mA loop, the output level is generally not dependent on the sensor excitation voltage [S5].

Voltage output is suitable for short cable runs and control systems with compatible analog inputs.

Voltage signals are also used where the receiving device expects 0–5 V or 0–10 V. The receiver must match the selected range, because a 0–10 V transmitter connected to a 0–5 V input can overload the input or produce an incorrect pressure indication.

Millivolt, Current and Digital Options

what electrical signal does a standard pressure transmitter output? - Millivolt, Current and Digital Options
what electrical signal does a standard pressure transmitter output? - Millivolt, Current and Digital Options

Pressure transducers are described by three output families: millivolt, amplified voltage and 4–20 mA [S4]. A raw millivolt output depends on excitation. At 2 mV/V with 10 V excitation, full scale is 20 mV; with 5 V excitation, the same sensor produces 10 mV [S5].

Millivolt devices are generally low-cost, but the signal is intended for short distances and is susceptible to electrical interference. An amplifier can raise the output when a stronger signal or longer transmission distance is required [S5].

Digital transmitters are a separate option and require a compatible communications protocol, such as I²C, SPI or UART in the cited device examples [S5]. A pressure transmitter selected for a PLC or control system must therefore match the controller input, protocol, power supply and signal topology.

How To Choose The Correct Output

The selection should begin with the receiver input: 4–20 mA for a conventional PLC or DCS current input, 0–5 V or 0–10 V for a matching voltage input, and a matching digital interface for a bus-based device [S3][S5].

Current signals are less affected by voltage drops over long connections than voltage signals [S2]. A cited technical comparison distinguishes millivolt-output pressure sensors from devices with other output types, but does not specify a maximum cable-run distance [S5].

Two-wire 4–20 mA instruments use the same pair of conductors for power and signal, simplifying installation compared with three- or four-wire field devices [S2]. The related guide to two-wire pressure transmitter wiring for 4–20 mA loops covers the loop wiring in detail.

Transmitter Versus Raw Transducer Output

what electrical signal does a standard pressure transmitter output? - Transmitter Versus Raw Transducer Output
what electrical signal does a standard pressure transmitter output? - Transmitter Versus Raw Transducer Output

A raw pressure transducer converts mechanical force into a millivolt or voltage signal, while a pressure transmitter adds amplification, linearization and compensation to generate a standardized output [S1][S3]. That conditioning makes the transmitter suitable for direct integration with process-control equipment.

Millivolt outputs may be unlinearized and require stable excitation, whereas amplified voltage and 4–20 mA outputs are easier to map into a pressure reading [S3][S5]. For calibrated process measurements, the pressure sensor output and protocol selection guide provides a useful framework for matching the sensor to the control architecture.

Application And Diagnostic Constraints

A current-loop transmitter suits long cable runs, noisy plants and installations where wire resistance or voltage drop could affect a voltage signal. It also supports a useful open-circuit diagnostic because the normal low state is 4 mA, not 0 mA [S2].

Voltage output suits compact machinery, test equipment and short installations where the controller already accepts 0–5 V or 0–10 V [S4][S5]. Millivolt output belongs mainly in short-cable sensing arrangements where excitation and grounding are controlled, and digital output suits systems that require protocol communication, configuration or additional device information [S5].

For any selected device, the nameplate or datasheet must confirm the output range, calibrated pressure span, power requirements and communication method. These parameters determine whether the transmitter connects directly to the PLC, DCS or data-acquisition input, and they should be checked before a pressure transmitter is installed.

Frequently asked questions

What output signal does a standard industrial pressure transmitter normally provide?

A standard industrial pressure transmitter normally provides a proportional 4–20 mA current signal. It draws 4 mA at the calibrated lower measurement limit and 20 mA at the calibrated upper limit.

Does a 4–20 mA pressure transmitter output 0 mA for zero pressure?

No. A 4 mA output represents the calibrated minimum or zero-pressure condition, so 0 mA generally indicates a broken wire, open circuit or failed transmitter rather than valid zero pressure.

Which pressure-transmitter output is most suitable for long cables and electrically noisy installations?

Use a 4–20 mA output for long cable runs and noisy installations because it is less affected by voltage drop and electromagnetic interference.

Can a 0–10 V pressure transmitter connect directly to a 0–5 V PLC input?

No. The receiver must match the transmitter output range because a 0–10 V signal connected to a 0–5 V input can overload the input or produce an incorrect pressure indication. Verify the output range, power requirements and signal type in the datasheet before installation.

7 sources
  1. All About Pressure Sensors
  2. All about pressure transmitters with 4-20mA (Nov 4, 2025)
  3. What Is a Pressure Transmitter? Understanding the Key ... - SenTec (May 22, 2026)
  4. Defining a Pressure Transducer
  5. Pressure Sensor Readings (Pressure Transducer, Pressure Transmitter) (Aug 16, 2022)
  6. How does a pressure transmitter work?
  7. What Signal does Pressure Transmitter Output? (Dec 12, 2024)