NAMUR Open Architecture provides secure access to process data through a secondary communication channel that does not interfere with the control system.
Designed for brownfield plants and modular greenfield installations, NOA supports field-device monitoring, fleet management, process analysis and optimization and is described in NAMUR Recommendation NE 175.
What NAMUR Open Architecture Changes
NAMUR Recommendation NE 175 defines NOA as an architecture that makes production data easily and securely usable for plant and asset monitoring as well as optimization [S1]. It opens the classical automation pyramid by transferring data over a second communication channel while leaving the established control structure and automation system unaffected [S1].
This arrangement separates deterministic process control from monitoring and optimization data. Field devices remain part of the control layer, while analytics applications receive contextualized production information through the secondary channel [S3]. The result is lower coupling between IT and OT lifecycles without exposing the core control loop to write-back or interference [S3].
NOA Selection Criteria and Recommendation Scope
NOA is appropriate when a plant needs production, diagnostic or asset data for monitoring and optimization but its certified DCS or PLC architecture cannot be modified safely [S1][S3]. It supports existing brownfield systems, and compatibility with Advanced Physical Layer (APL) and the modular approach (MTP) extends the concept to modular greenfield installations [S1].
The architecture is not a replacement for deterministic control, safety instrumentation or real-time process automation. It is also not a license for unrestricted write access from cloud or enterprise applications. NOA instead provides controlled data access for measurement, analysis, diagnostics and operational optimization [S3].
A condition monitoring system is a suitable destination for NOA data because device status and diagnostic information can support early failure detection. A data logger can collect trends from the secondary channel, while a monitoring terminal can present plant or fleet information outside the core control environment.
Compare NOA, Direct Integration and Unified Namespace

The main choice is not between competing monitoring architectures but between access methods. NOA creates a defined secondary path, direct integration links an application more closely to an automation system, and a unified namespace focuses on consistent naming and information representation across systems. The 2024 comparison identifies NOA as an extension of the Classical Automation Pyramid and cites NE 175 as its specification [S6].
Against four decision criteria, NOA scores well on brownfield compatibility because it avoids alteration of the core system, and on modular extensibility because it can coexist with MTP and Ethernet-APL [S1]. Direct integration can offer fewer architectural layers but creates tighter coupling and greater change risk.
Its strongest engineering case is therefore not faster analytics, but controlled separation between plant control and data-driven applications.
Four Recommendations Define the NOA Building Blocks
This structure assigns explicit responsibilities to modeling, protection, request validation and aggregation rather than treating secure access as one network feature.
PA-DIM is the selected information model [S5]. A detection and analysis apparatus can therefore receive structured process information rather than relying on vendor-specific exports, provided the selected system implements the applicable models and interfaces.
For fleet or plant management, this creates a controlled route for diagnostics and asset-performance information, including comparison of as-designed engineering data with as-installed plant information [S4].
Security and Request Verification

That distinction matters when operational suggestions travel back toward plant systems. The 2017 convergence work described a cloud use case in which requested messages required authenticity verification before operational or process-management changes were accepted [S4]. This is materially different from simply allowing an analytics platform to read unrestricted plant data.
For a monitoring terminal, the practical boundary is explicit: consume approved measurements and diagnostics, keep deterministic control in the automation layer, and place verification logic between monitoring requests and any downstream action [S1][S3].
Brownfield, Greenfield and Mobility Use Cases
NOA supports at least four named operating scenarios: monitoring field devices, process analysers and electrotechnical equipment; plant or fleet management of mechanical equipment; access to additional data; and implementation of additional measurements for process optimization [S1]. Existing plants can expose data from smart sensors, field devices, mobile devices and pervasive IT equipment through the secondary channel without changing the automation system [S1].
Greenfield projects can combine NOA with Ethernet-APL and MTP so diagnostic information is available as part of modular plant design [S1][S3]. In brownfield projects, an edge collector or data logger can handle local acquisition, while the aggregating server consolidates data for plant-level analytics [S1][S7].
The 2017 working-group examples included exporting instrument trends to a cloud, performing calculations from multiple instrument values in the cloud, verifying requests, and comparing as-designed engineering data with as-installed plant information [S4]. These examples define useful acceptance tests for an NOA implementation.
Implementation Limits and Acceptance Tests

NOA does not remove the need for device compatibility, semantic mapping or cybersecurity engineering. PA-DIM remains the selected information model, but useful delivery still depends on devices and gateways exposing the required parameters and descriptors [S3][S5]. Legacy equipment may require data acquisition through supported interfaces such as HART diagnostics rather than direct access to every controller memory area [S3].
An acceptance test should verify that monitoring traffic follows the secondary path, that the core automation system remains unaffected, and that requests crossing the IT and OT boundary are authenticated under NE 178. Further checks should confirm that data semantics follow PA-DIM, that NE 176 information is consistently applied, that NE 177 zones restrict access, and that the NE 179 aggregation function produces usable plant and fleet views [S1].
Performance expectations should also be separated by layer. Level 1 and Level 2 functions remain subject to strict real-time and availability requirements, while Level 3 processing may operate on timescales from minutes to hours [S5]. NOA is not a mechanism for moving fast control loops into an IT analytics layer.
A practical next move is to select one brownfield use case, map its field parameters to PA-DIM, and define the NE 177 security boundary before specifying the NE 179 aggregation service. That sequence turns NOA from an abstract architecture into a testable plant data project.