Four common pressure sensor output categories are millivolt, voltage, 4–20 mA current, and digital signals, with practical choices determined by noise, cable length, resolution, and controller compatibility [S1][S4][S5].
The first three are analog formats, while the fourth covers digital protocols such as HART, Modbus, and IO-Link; frequency outputs also remain an established interface category [S1][S2][S5][S6].
Four Output Families and Their Electrical Boundaries
The practical answer is four families: millivolt or bridge output, voltage output, current-loop output, and digital output. A millivolt sensor with 10 mV/V sensitivity and a 5 VDC supply produces 0–50 mV at full scale, while a pressure transmitter commonly uses a 4–20 mA loop [S1].
Voltage examples include 0–5 V, 0–10 V, 0.5–4.5 V, and 1–6 V. Current examples include 4–20 mA in 2-wire or 4-wire arrangements, and digital interfaces include HART, Modbus, IO-Link, RS-485, I²C, and proprietary formats [S1][S2][S7][S8].
This classification is about the electrical interface, not the physical sensing principle. Piezoresistive, capacitive, piezoelectric, and resonant elements can each be packaged with different output electronics, so sensor technology and signal format must be specified separately [S3][S5].
Millivolt Output for Short-Distance Precision Circuits
Millivolt or bridge output provides a raw bridge signal that must be conditioned and processed to convert the output level into a calibrated pressure reading. The full-scale output of a pressure sensor is proportional to the measured pressure and must be conditioned and processed to obtain a calibrated pressure value.
A 10 mV/V sensor powered by 5 VDC reaches 50 mV at full scale, while a 2 mV/V element reaches 10 mV under the same supply. These are low-level bridge measurements that require controlled grounding, shielding, regulated excitation, and carefully selected amplifier gains [S1].
Voltage Output for Short, Direct Controller Inputs

Voltage output provides a simple interface where the controller or data-acquisition system accepts an analog voltage directly. Documented examples include 0–5 V, 0–10 V, 0.5–4.5 V, and 1–6 V, so an electrical range alone does not identify the transmitter [S2][S5][S7][S8].
Commercial examples illustrate the available scale: DDM lists 0.5–4.5 V sensors with pressure ranges from 5 to 250 bar and compensated temperatures from −40°C to +180°C, while other 0.5–4.5 V devices cover up to 200 bar relative pressure, 300 bar overpressure, and 400 bar burst pressure [S2].
4–20 mA Current Loop for Process Instrumentation
Pressure sensors can generate an output signal proportional to the measured pressure, and the listed pressure sensors include models with a 4–20 mA output.
The listed pressure sensors include a model with a two-wire 4–20 mA output.
Available pressure ranges are device-specific. DDM examples include gauge pressure from 100 mbar to 150 bar, absolute pressure from 2 bar to 150 bar, and compensation from −40°C to +125°C for one 4–20 mA model [S2]. These specifications show why a pressure range, reference type, output format, and temperature band must appear together on an instrument datasheet [S2].
Digital Output for Diagnostics and High-Speed Data

Digital pressure-sensor outputs listed in the supplied sources include HART, Modbus, IO-Link, I²C, and RS-485. For a signal calibrator, the communication protocol and register map matter as much as the pressure range and accuracy.
Output Comparison Across Four Decision Criteria
Matching Output to Application and Measurement Type

Pressure sensors measure gauge, absolute, differential, or sealed-gauge pressure, but output format does not determine reference type. A gauge sensor reads relative to atmosphere, an absolute sensor references perfect vacuum, and a differential sensor measures the difference between two pressure points [S5].
For hydraulic and pneumatic control, a 4–20 mA transmitter is a practical baseline for a noisy plant loop, while 0–10 V may fit a local controller input. Compact machinery and OEM modules can use voltage or digital outputs where cable length is short and the controller supports the same interface [S1][S2][S5].
Frequency-based output is the fourth broad category in some interface catalogs but should not be confused with the four signal families used here [S1][S6]. The additional standard pressure transmitter output signals reference provides a useful second-level comparison for industrial current and voltage selections.
Procurement and Commissioning Checks
A correct purchase requires at least six controlled fields: measured pressure type, calibrated range, output signal, supply voltage, electrical connection, and environmental limits. Examples in the research span 100 mbar to 150 bar, 0–250 bar, −40°C to +125°C, and −40°C to +180°C, showing that output selection cannot replace full specification review [S2].
For analog devices, verify the exact zero and full-scale points. A request for “voltage output” leaves 0–5 V, 0–10 V, 0.5–4.5 V, and 1–6 V as possible interpretations [S2][S7][S8]. For 4–20 mA devices, confirm whether the installation is 2-wire or 4-wire and calculate the loop burden against cable length [S1].
For digital devices, freeze the protocol, baud rate, data format, register map, and device parameters before quotation. For millivolt sensors, specify excitation voltage, sensitivity in mV/V, bridge resistance, cable length, and required signal-conditioning gain [S1][S2].
The next actionable check is to match the selected output to the actual receiving input, then validate its range, calibration span, power budget, wiring plan, and diagnostic requirements against the manufacturer datasheet before approving a device.