A silicon resonant pressure sensor achieved 10 Pa output resolution across a 70 MPa range, with long-term stability of approximately 40 Pa/month.
Stability Performance and Measurement Scale
The tested sensor measured from atmospheric pressure to 70 MPa absolute pressure and resolved 10 Pa.
Pressure sensitivity averaged -2,037.4 ppm/MPa, with a standard deviation of 5.8 ppm/MPa across 50 sensors [S1]. Separate pressure and temperature resonators were calibrated at appropriate points, while mounting each resonator on a cantilever reduced strain noise transmitted from the package [S1].
This performance places long-term drift far below the 0.1% five-year stability class associated with mono-crystalline silicon sensors, although the figures apply to different constructions and should not be treated as equivalent laboratory results [S7]. For transmitter specifications, this distinction matters because a resonant pressure transmitter requires both sensor drift and complete electronics calibration to be considered.
How Resonant Silicon Pressure Measurement Works
Pressure deflects a diaphragm and creates strain in a silicon resonator, causing its resonance frequency to shift; the frequency change is converted into a pressure value [S2]. Yokogawa developed a new silicon resonant strain sensor by mounting it on a thermal stress compensation structure and driving the gauge electrostatically.
A later electrostatic design was intended to reduce power consumption and support wireless measurement and Industrial Internet of Things applications [S2].
For engineers evaluating sensor families, that distinction separates it from generic pressure sensors and makes temperature compensation, excitation electronics, and package-stress control central to stability verification.
Selection Criteria Across Silicon Technologies

Resonant silicon is appropriate when low drift, high resolution, repeatability, and operation across demanding pressure ranges matter more than a low purchase price [S1][S2][S3]. Conventional silicon pressure transducers have a high mV/V output signal, high overpressure capability, and very good non-linearity, hysteresis, and repeatability measurement precision.
The table compares published outcomes, not a guarantee of equivalent products. Sensor architecture, sealing, media isolation, installation stress, calibration, and the test reference can change the field result even when the underlying material is similar [S1][S4][S5][S7].
Absolute and Differential Transmitter Applications
Volume-shrinkage resonant silicon supports absolute-pressure measurement from atmospheric pressure to 70 MPa [S1]. A flexible fabrication route was used to produce MEMS resonant pressure transducers for pressure ranges from 1 bar to 700 bar in fully oil-isolated hermetic packages.
For differential service, Yokogawa's DPharp series uses a silicon resonant strain gauge to infer diaphragm strain and calculate differential pressure [S2]. A procurement specification for a differential pressure transmitter should identify whether the resonant element is isolated from the process media and how temperature compensation is performed, not merely whether the datasheet says silicon MEMS.
The technology is not the automatic choice for every line. A simple low-cost pressure point, a highly corrosive medium without a compatible diaphragm, or an installation that introduces severe package or piping stress can undermine the laboratory advantage.
Failure Modes and Long-Term Validation

Long-term stability is not a property of the resonator alone. The volume-shrinkage design used separate pressure and temperature resonators and limited package-transmitted strain noise through cantilever mounting, showing that mechanical isolation and thermal compensation are part of the stability architecture [S1].
A flexible fabrication route was used to produce a hermetically packaged MEMS resonant pressure transducer for pressure ranges from 1 bar to 700 bar.
Field failure mechanisms include zero drift from package stress, thermal mismatch, seal or oil degradation, corrosion, and calibration shift. Silicon-on-sapphire eliminates bonding agents between the sensing layer and substrate that could age, and its sapphire isolation contributes to low hysteresis and strong corrosion resistance [S5]. For lab comparison, the required reference instrument, range, media, temperature exposure, and acceptance interval must be stated before a drift claim is accepted.
Media Compatibility and Packaging Constraints
Resonant silicon sensors require a pressure-transfer path from the measured medium to the sensing diaphragm, so wetted materials and seals remain separate design variables. A silicon-on-sapphire construction can use a welded titanium diaphragm and titanium threaded port without an O-ring seal, operate from -1 to 5,000 bar, and provide sensitivity of 10 to 20 mV/V [S5].
That combination targets proof-pressure, transient, chemical-resistance, and high-temperature applications, while a high-range resonant transducer from 1 to 700 bar relies on fully oil-isolated hermetic packaging [S4]. Neither result authorizes an arbitrary gas or liquid to contact the diaphragm, and the material specification must cover the actual process medium.
For an absolute pressure transmitter, the cited 70 MPa device offers a benchmark for resolution and annual drift. For lower-pressure systems, the practical question is whether that stability justifies the added cost of a resonant sensor compared with a conventional transmitter whose installed accuracy, repeatability, and recalibration interval meet the process requirement [S1][S3][S6].
Procurement and Calibration Requirements

A defensible stability specification should state the drift as pressure units per month or year and as a percentage of full-scale range, then identify the reference, duration, pressure range, temperature conditions, sample size, and media exposure [S1]. The 0.0007% FS/year figure cannot be compared fairly with a 0.1% five-year rating unless both are normalized to the same interval and span.
The 50-sensor sensitivity population provides a useful manufacturing benchmark: the mean pressure sensitivity was -2,037.4 ppm/MPa and the standard deviation was 5.8 ppm/MPa [S1]. For production acceptance, calibrated pressure and temperature points should cover the working span, while the frequency shift and compensation method should be documented for diagnostics.
Verification should also include zero return, repeatability, hysteresis, temperature cycling, proof pressure, and media compatibility. A resonant design is especially attractive when pressure variation must be resolved at the 10 Pa level, but calibration and installation still affect total uncertainty. Calculate Total Probable Error for Pressure Transmitters remains necessary when combining sensor accuracy, electronics, and process-loop effects.
The trackable procurement signals are the manufacturer-specified drift limit, the test interval, the reference barometer or calibrator, and the full-scale range; without those four items, a long-term stability claim is not comparable across resonant, mono-crystalline, diffused, and silicon-on-sapphire pressure technologies.