Calculate outrigger pad pressure as pounds or newtons divided by square inches or square metres, using the maximum loaded outrigger reaction rather than the crane’s total weight [S3][S4].
The result must remain below the allowable pressure at the setup position, with a 350 kN outrigger load and 200 kPa allowable ground pressure requiring at least 1.75 m² of bearing area [S3].
Core outrigger pressure equation and unit selection
Ground bearing pressure equals load divided by contact area: GBP = force ÷ area [S2][S4]. Force may be expressed in pounds, kips or kilonewtons, while area may be in square inches, square feet or square metres.
Keep US customary units paired correctly: pounds divided by square inches produces PSI, and pounds divided by square feet produces PSF. In SI units, kilonewtons divided by square metres produces kPa. One psi equals 6.895 kPa, while one psf equals 0.04788 kPa.
A worked example using 50,000 lb over 500 in² produces 100 psi [S2]. In SI terms, a 350 kN load requires 1.75 m² at 200 kPa. A 1.4 × 1.4 m mat supplies 1.96 m² and reduces pressure to 178.6 kPa, whereas a 1.5 × 1.5 m mat supplies 2.25 m² and reduces pressure to 155.6 kPa [S3].
Select the governing outrigger reaction load
Use the maximum outrigger reaction force listed for the crane configuration, boom angle and working radius. Do not substitute gross vehicle weight, gross load weight or an equal share among four outriggers [S4][S5].
One sizing method multiplies the outrigger load by a safety factor before dividing by allowable ground pressure: required area = outrigger load × safety factor ÷ allowable pressure [S4]. The reaction changes with boom angle and radius, so the calculation should cover the worst configuration within the planned lift [S4].
Rotating a crane also shifts reactions between corners. As the crane moves through its working sector, one outrigger may carry a greater reaction than the others, making equal load distribution across all pads an unsafe assumption [S5]. For a truck-mounted crane, the manufacturer load chart and configuration-specific support information remain the controlling inputs.
Verify ground pressure at the actual setup position

Allowable ground pressure is a site-specific limit, not a universal constant. Indicative values range from about 300 kPa for rock or well-compacted aggregate to 200 kPa for compacted fill, 120 kPa for sandy or loose soil and 75 kPa for soft or reclaimed ground [S4]. These are screening references only, and unusual or critical setups require site-specific geotechnical confirmation [S4].
Four practical sources of capacity information are manufacturer load charts, soil bearing-capacity charts, site geotechnical reports and ground-pressure calculators [S2]. For a complex site, use the geotechnical result at the pad position rather than selecting a generic soil category. The calculation cannot resolve buried services, backfilled trenches, voids, settlement, nearby excavations or uneven settlement [S3].
Manitowoc offers Outrigger Pad Load Calculators and a Ground Bearing Pressure Estimator [S1]. These tools can check a defined configuration, but the input load and allowable site pressure still require traceable engineering information.
Compare pad and mat sizing options
The minimum bearing area is force divided by allowable ground pressure [S3]. For a square mat, divide the calculated area by one and take the square root; for a round mat, use the square root of four times the area divided by pi [S3].
A manufacturer-rated timber or engineered pad is appropriate when its published load rating, dimensions and full-contact footprint suit the outrigger float. A steel crane mat can spread a larger reaction over a broad area, but its bending, shear and punching resistance must be verified. A flexible mat may bend under a small float, concentrating pressure and leaving less effective bearing area than its nominal dimensions [S3].
Against four decision criteria, rated pads score well for controlled installations because their capacity and footprint are documented. Timber cribbing can accommodate irregular float sizes, but each layer must be arranged to resist crushing, bending, shear and shifting [S5]. Steel mats offer large bearing areas for high reactions, yet require structural and ground checks. Loose soil or improvised packing offers no defensible capacity and should not be treated as engineered support.
OSHA 1926.1402 requires cranes to be assembled on firm, drained and adequately graded ground, with blocking, cribbing, pads or mats providing adequate support and levelness [S5]. ASME B30.5-3.2.1.5 requires blocking beneath outrigger floats, when required, to have sufficient strength and suitable thickness, width and length to support the float, transmit the load, and prevent shifting, toppling or excessive settlement [S5].
Install and verify the bearing system

Place the support on level, prepared ground with full contact and no voids or high spots. Centre the outrigger float on the pad or mat, inspect for cracking, rot, warping or other damage, and avoid stacking mats or improvising packing unless the arrangement has been designed [S3].
Do not count a mat’s full nominal area automatically. The contact area formula assumes even load distribution across that area, which depends on mat stiffness, thickness, overall size and the float footprint. The mat manufacturer’s rating or a temporary-works designer must confirm that the full area participates [S3].
Support requirements for a concrete pump truck and a truck-mounted concrete pump must also be derived from their specific outrigger reactions and setup geometry. The same pressure equation applies, but the load cases and pump configuration are not interchangeable with those of a truck-mounted crane.
Record the calculation before setting the crane
Record the governing outrigger force, allowable ground pressure, selected support dimensions, calculated pressure, safety factor and source documents in the lift plan. Use consistent units and recalculate for each pad if the site permits different support conditions or if the crane configuration changes [S3][S4].
Check the calculated result against the support product’s rated capacity and the crane manufacturer’s instructions, then monitor crane level during setup and operation [S5]. A trackable verification record should show force, area, resulting pressure, allowable limit and the named source for each input. For setup engineering, see Excavator vs Wheel Loader Ground Pressure on Soft Soil.