Selection must combine valve torque or thrust, worst-case differential pressure, minimum hydraulic supply, fail-safe position, stroke time, environmental exposure, and maintainability rather than rely on actuator output alone [S4][S5].
Where Hydraulic Actuation Fits
Hydraulic actuators convert pressurized oil into mechanical force for linear or rotary motion, making them suitable for pipeline isolation, wellhead protection, compressor stations, emergency shutdown, and other high-load flow-control duties [S1][S3]. A published oil and gas sector estimate placed approximately 75% of valves under actuator automation in 2015, but that historical figure should not be treated as a specification or market forecast [S4].
Use hydraulic actuation when the application requires heavy-duty motion, a remote or hazardous installation, or fast valve movement. Do not select it merely because the valve is large: the package must include a suitable hydraulic power unit, tubing or piping, filtration, controls, and a maintenance strategy [S5].
Electric actuators are normally preferable for precise positioning, clean environments, and sites without hydraulic infrastructure, while pneumatic actuators offer fast fail-safe response where clean, dry instrument air is dependable [S2][S3][S5]. For valve-position control, the broader control valve selection for oil and gas duty still governs the process sizing before actuator mechanics are selected.
Choose the Mechanical Geometry
Linear actuators deliver straight-line force and suit reciprocating or gate-type motion; rotary actuators deliver torque for quarter-turn and multi-turn valves [S3]. In the oil and gas actuator portfolio, rotary vane, helical spline, linear, scotch yoke, and rack and pinion designs cover distinct force, torque, and packaging requirements [S1].
The geometry must match the valve interface, stroke, output speed, and available installation envelope. The rack and pinion actuator is a natural choice for compact quarter-turn packages, while the scotch yoke actuator generally serves larger high-torque ball valves.
Size Output Against the Worst Valve Case

For quarter-turn valves, size from maximum break-to-open torque, run torque, and end-to-close torque; for linear valves, size from the maximum required thrust. Published valve torque is not the actuator output, and the actuator must deliver enough force to seat the closure member against the required shut-down leakage class [S4][S5].
This range is an engineering practice stated in the selection guide, not a universal code requirement. Excess margin is not a free safety margin: an oversized actuator can overload or damage the valve stem if the closure member jams [S5].
Also compare actuator output with the valve manufacturer’s maximum stem torque or thrust limit [S5].
Set Fail-Safe Action and Power Architecture
Define fail-closed, fail-open, or fail-in-place from the process hazard review, and then verify that the hydraulic power architecture can physically achieve that position when power, signal, or hydraulic pressure is lost [S5].
Emerson’s portfolio includes gas hydraulic linear operators, gas-over-oil actuators, and hydraulic wellhead protection systems, confirming these architectures are established rather than hypothetical [S1].
Do not assume that fail-safe means fail-closed. A cooling-water valve may be required to fail open, while a fuel-gas valve may be required to fail closed, and the final action must follow the hazard analysis [S5]. The related hydraulic valve actuator includes the controls and position-feedback decisions that must be coordinated with the mechanical package.
Control the Stroke Time and Duty

For ESD duty, derive the allowed closing time from the safety requirements specification and include signal delay, solenoid response, hydraulic-system response, and valve travel rather than quoting actuator catalog speed alone [S5]. Oil and gas services often impose closure requirements because isolation time affects the isolation reliability and consequence of release.
Use an electric actuator when modulating response, repeatable positioning, network feedback, and low maintenance outweigh the hydraulic package complexity. A pneumatic actuator is more direct when clean, dry instrument air at a dependable pressure supports fast spring-return operation.
Account for Oil, Heat, and Hazardous Environments
Hydraulic-system design must address working-fluid compatibility, temperature, viscosity, contamination, seals, and fire risk. The oil seal is a critical wear interface, while a failed hydraulic pump or hydraulic valve can remove the stored energy needed for the required stroke. [S2]
Operating temperature affects both the power unit and the actuator because hydraulic oil viscosity changes with temperature, and the selected fluid must remain within the actuator manufacturer’s allowable range. Filter the oil, control contamination, and include local isolation and pressure indication so a degraded circuit can be detected before an ESD demand.
For hazardous-area installations, specify certified electrical and solenoid components for the designated area classification rather than assuming a hydraulic actuator is exempt. Hydraulic fluid may be combustible, stored hydraulic energy may remain after shutdown, and line-gas-powered systems require their own process and hazardous-area review. Applicable ATEX, IECEx, NEC, or national rules depend on the installation and certification route; do not assign a certification designation without an approved equipment schedule.
Match the Package to Lifecycle Cost

A hydraulic actuator is not a standalone asset: the hydraulic power unit, accumulator, reservoir, filtration, piping, controls, position feedback, tubing, and seals determine operating reliability. The selection and sizing guide identifies electro-hydraulic and gas-over-oil systems as carrying higher cost and greater maintenance than simpler pneumatic packages [S5].
Compare the options against the same four criteria:
Use the hydraulic option when the valve output, installation environment, and fail-safe case justify the added maintenance. Do not use it for an ordinary small isolation valve where electric actuation is available and the safety case does not require stored hydraulic energy.
Issue a Complete Purchase Specification
The actuator datasheet should identify valve type and size, break-to-open torque, run torque, end-to-close torque or linear thrust, maximum differential pressure, stem material and allowable thrust, closure-member design, rotation angle, stroke, and required stroke times [S4][S5]. Include the power medium, minimum and maximum operating pressure, fluid and ambient temperature limits, allowable viscosity, sealing arrangement, mounting interface, and corrosion protection.
For control duty, specify the actuator as part of the complete control loop, including the required action, travel cutoff, feedback type, positioner interface, hydraulic control manifold, and diagnostic requirements [S4]. For quarter-turn packages, use the hydraulic actuator reference to compare the system-level actuator package with the valve-specific conversion mechanism.
Before approval, run the selected model through three checks: deliver valve output at minimum supply pressure, demonstrate the specified fail-safe stroke within the safety timing budget, and confirm that maximum actuator output does not exceed the valve stem limit [S5]. Record these results in the valve-actuator sizing sheet and obtain agreement from both the valve and actuator manufacturers.