A 10 kVA high-frequency inverter can run four HIB 100A dam vibrators simultaneously, subject to the manufacturer’s stated output rating and matching cable sizes [S6].
For several high-frequency vibrators, the converter must handle the combined operating kVA, startup demand, output frequency and voltage, cable losses, thermal limits, and any duty-cycle peaks.
Start with simultaneous load kVA
Calculate the operating kVA of every vibrator connected at the same time, then add them. For comparison, one 10 kVA high-frequency inverter is rated to operate four HIB 100A dam vibrators concurrently [S6]. That is a vendor configuration, not a universal rule for every vibrator type or cable arrangement.
Do not select the converter from motor horsepower alone. A drive should be checked against motor rated power, rated current, starting current, load torque, and the acceleration profile [S2][S3]. High-frequency vibrator systems can also use low-voltage, high-frequency outputs, so the input kVA and output kVA must be treated as separate design points rather than interchanged.
For a frequency converter, the available continuous rating must cover the simultaneous load plus the required margin. For example, a 7.5 kW, three-phase 400 V motor drawing 14.73 A requires a drive with maximum continuous output current of at least 14.73 A for the stated constant-torque or square-torque case [S2].
Check the output voltage and frequency
A converter selected only by kVA can therefore be electrically incompatible with the vibrator if its voltage, frequency, phase arrangement, and connection method differ.
The EXEN HD2100A example provides 10 kVA for four HIB 100A vibrators and lists cable sizes of 3.5 mm², 5.5 mm², and 8.0 mm² [S6]. Those conductors must be assessed for installation method, length, current, thermal rating, and voltage drop. Cable size cannot be copied between installations without checking the same variables.
Their kVA ratings are not directly interchangeable because the output voltage and current differ.
Separate continuous load from peak duty

An intermittent load needs both a continuous kVA calculation and a peak-load check. A 45 kVA peak operating at 40 percent duty produces an RMS equivalent of 28.5 kVA, but the 45 kVA peak still requires sufficient short-duration capacity [S1].
Overload capability must be read as a percentage, a permitted duration, and a specified pre-load condition. Those figures describe distinct operating events and cannot be treated as interchangeable.
For multiple vibrators, calculate the aggregate kVA during startup and simultaneous full-load periods rather than averaging them away.
Compare the main sizing approaches
Rated-current selection is the most direct approach when measured operating current is available: choose a converter whose continuous output current is at least the motor current for the applicable load characteristic [S2]. For constant or square-torque loads, the cited selection rule sets the continuous current requirement at or above 14.73 A for the 7.5 kW example [S2].
Motor-power selection is useful for initial equipment checks. A converter rated at or above the motor’s rated power is a starting point, but starting current and acceleration torque still require verification [S3]. Constant-torque applications require a drive with sufficient overload torque for starting and sudden load increases.
Transformer-based sizing is a separate upstream calculation. The contrast shows why transformer sizing, drive output rating, and across-the-line starting requirements must not be collapsed into one calculation.
Match the vibrator duty and operating pattern

High-frequency vibrators are not automatically constant-torque loads merely because they are construction tools. The starting torque, operating torque, mechanical losses, and thermal behavior of each model must be established from its data. Conveyors and machine tools are classified as constant-torque loads, while fans and pumps fall within variable-torque applications where speed changes materially affect demand [S2][S3].
The load classes also affect energy demand. For centrifugal pumps and fans, the power requirement increases as speed increases. A vibrator that develops load differently under startup must receive a separate starting and acceleration calculation.
For simultaneous equipment, identify whether every vibrator starts together or whether the system staggers starts. The former requires aggregate peak current and kVA, while staggered starting may reduce the instantaneous demand but must still respect each motor’s permitted start interval and the converter’s thermal model.
Verify the cable, thermal, and protection limits
The 10 kVA EXEN configuration lists 3.5 mm², 5.5 mm², and 8.0 mm² cable sizes [S6]. Cable selection must also account for conductor length, output frequency, installation temperature, grouping, and the protection arrangement. High operating current creates both conductor heat and voltage drop, and the acceptable result depends on the motor and cable limits specified for the installation.
Verify the converter against its actual operating altitude and ambient temperature, because a nameplate capacity measured under prescribed conditions does not guarantee the same continuous output in a hotter enclosure or at high altitude. The overload rating also depends on the load already present when the overload begins, not merely on the percentage stated in a catalogue [S1].
Use the vibrator nameplate data for rated current and kVA, and obtain the converter data for continuous output current, apparent power, overload percentage, overload duration, pre-load condition, output voltage, and output frequency. For more detail on the motor side, AC motor data should be used to establish rated current, starting current, and mechanical load rather than inferred from kW alone.
Build a defensible multi-vibrator specification

A purchasable specification should state the number of simultaneous vibrators, each motor’s rated kW, current, and voltage, the vibrator’s rated frequency, starting method, aggregate operating kVA, maximum startup kVA, duty profile, ambient conditions, cable lengths, and cable sizes. It should also identify whether one converter or several converters serve the load. [S2]
Two reference configurations illustrate the scale of variation. The FC-401 is a single-purpose 380 V, 50 Hz to 48 V, 200 Hz converter for high-frequency induction motors [S5], while the EXEN HD2100A is a 10 kVA unit specified for four HIB 100A dam vibrators with three listed cable sizes [S6]. A project drawing combining both would have different output and cabling requirements and should not be treated as one common drive.
The final acceptance check is straightforward: the specified continuous kVA and current must exceed the simultaneous operating demand, the starting event must remain inside the overload window and pre-load condition, the 48 V or other required output must match every connected vibrator, and the cables must be rated for the calculated current and voltage drop. A comparison of brushless and universal-motor concrete vibrators can then support motor selection without changing the electrical sizing calculation.