A pentagon operating nut is usually ordered by its point-to-flat dimension, not across corners, and the opening direction is identified by the arrow cast on the bonnet [S3][S6][S1].
The useful decision is straightforward: match the nut geometry and measured dimension, then follow the bonnet arrow rather than assuming left-hand opening or counterclockwise rotation [S1][S2].
How Pentagon Nut Size Is Measured
For a five-sided operating nut, the specified dimension is point to flat, meaning the distance from one vertex to the perpendicular flat surface. This differs from the flat-to-flat measurement used for square and hexagon nuts [S3][S6].
Do not substitute an across-corners dimension for point-to-flat. A pentagon wrench ordered from the wrong reference geometry can seat incorrectly, leave insufficient engagement, or damage the operating nut [S6].
The Kennedy K17 manual identifies the operating nut and describes features intended to simplify operation and maintenance [S3].
How the Opening Direction Is Identified
The opening direction is established by an arrow cast on the bonnet, which provides the authoritative visual indication for turning the operating nut toward the open position [S1].
Operation guidance also calls for turning counterclockwise in the example described, but explicitly states that hydrants are marked with an arrow indicating the correct opening direction [S2]. The mechanical marking therefore takes priority over a generic clockwise or counterclockwise assumption.
Closing is performed in the opposite direction to the bonnet arrow.
Pentagon Nut Against Square and Hexagon Nuts

A pentagon nut is measured point to flat, while a square or hexagon nut is measured flat to flat, or across center between opposing flats [S6]. That geometry difference controls wrench selection before thread form or hydrant model is considered.
Pentagon nuts provide a positive operating interface and commonly occur as the bonnet operating nut on dry-barrel hydrants [S4]. Square and hexagon nuts use a different dimensional convention, so a tool listed for one geometry cannot be assumed to fit the other [S6].
For procurement, the comparison is therefore: pentagon requires point-to-flat measurement; square and hexagon require flat-to-flat measurement; and the applicable hydrant document determines material, thread, and model-specific details.
Selecting the Wrench and Protecting the Nut
A purpose-made hydrant wrench must fit the measured pentagon geometry without damaging the nut. Operating guidance specifically prohibits a pipe wrench because it can damage the hydrant [S2][S5].
Before operating, inspect the bonnet operating nut for tightness, check the cap and side nozzle for damage or obstruction, and verify that the hydrant is not leaking or visibly damaged [S2][S5]. The nut geometry and bonnet arrow should also be included in the field record for each asset.
Non-adjustable hydrant wrench documentation requires a point-to-flat dimension for a pentagon nut and across-center flat-to-flat dimensions for square and hexagon nuts [S6]. This measurement instruction is more useful operationally than a general statement that the wrench must “fit,” because it supports exact tool identification.
Safe Opening and Closing Sequence

Operators should stand behind the hydrant, keep bystanders and objects at least 10 feet away, and wear gloves and safety glasses [S5]. The hydrant valve should be opened slowly to avoid a sudden surge of water that could cause injury or damage to the hydrant and water infrastructure [S2][S5].
That operating instruction is separate from the physical nut size and should be followed where applicable to the jurisdiction and hydrant design.
The hydrant should be closed gradually by reversing the operating direction used to open it [S2]. Forcing a damaged or seized valve shut can damage the hydrant or its components [S2].
Documentation, Limits, and Failure Modes
The most reliable specification record contains the hydrant make and model, nut shape, point-to-flat dimension, thread details if applicable, bonnet arrow direction, and compatible wrench part number. A submittal that identifies only “pentagon nut” is not adequate for exact wrench procurement [S3][S6].
Wrong measurement convention, incorrect opening direction, and non-purpose-made tools create three distinct risks: poor wrench engagement, stem or nut damage, and uncontrolled valve movement. A pipe wrench can damage the hydrant, while forcing a closed valve can damage the valve or stem [S2][S5].
For a broader view of the component and its place in the assembly, see the fire hydrant reference. For comparison with another common hydrant design decision, Fire Hydrant Lateral Diameter and Length Limits covers the branch connection that supplies the hydrant.
Field verification should record the measured point-to-flat size and photograph the bonnet arrow before ordering tools or authorizing operation. Any mismatch between the physical nut, the submittal, and the stored wrench should be resolved before water flow is introduced.