Specify VDI/VDE 3513-2 Accuracy for Rotameters

VDI/VDE 3513-2 expresses variable area flowmeter accuracy through an error limit value G and a linearity limit qG, commonly at 50% of full scale [S1][S2].

Variable area flowmeters are suitable for flow-metering applications involving liquids, gases and steam [S1], and manufacturers may state accuracy according to VDI/VDE 3513 sheet 2 using classes such as 1.6 or 2.5 with a limit value qG [S6].

What VDI/VDE 3513-2 Measures

VDI/VDE 3513-2 provides information on the measuring accuracy of variable area flowmeters while accounting for their greater measuring error in the lower measuring range [S1][S4]. The accuracy specification accounts for the larger relative error that variable area meters exhibit near the lower end of their measuring range [S4].

The current formulation separates two parameters. Error limit value G is the maximum deviation above the linearity limit, expressed as a percentage, while linearity limit qG is expressed as a percentage of full scale [S4]. For a specification of G = 2.5% and qG = 50%, operation at 30% of full scale permits a relative error of 4.166%, calculated as F% = G × qG / q% [S4].

These limits presume installation and operation exactly as specified. Fluid density, viscosity, temperature and pressure must match the calibration conditions, and the manufacturer’s stated accuracy normally applies to the measuring device rather than electrical attachments or other accessories [S4].

Class Numbers, Error Limits and Flow Units

VDI/VDE accuracy class is dimensionless and, under the older class-based calculation, combines two partial errors: three quarters of the class referenced to the measured value and one quarter referenced to full scale [S4]. A manufacturer may instead quote error limit and linearity limit, which are easier to map to a specific operating point [S1][S2].

Class 4 appears in vendor documentation alongside standard accuracy ranges of ±10%, ±5% and ±2% of full scale, but the class number should not be converted into a single universal percentage without checking the stated basis [S7].

For flow-unit calculations under the older formulation, the published relationship is QErr = (3/4 × QMeas + 1/4 × QMax) × F / 100, with QMeas representing the full-scale flow and QMax the measured flow [S4]. This distinction matters because “of reading” and “of full scale” produce different allowed errors at the same flow rate.

Compare the Main Accuracy Formats

VDI/VDE 3513 accuracy class for variable area flowmeters - Compare the Main Accuracy Formats
VDI/VDE 3513 accuracy class for variable area flowmeters - Compare the Main Accuracy Formats

Variable area flowmeter accuracy can be compared against four criteria: basis of error, lower-range behavior, operating-point usability and procurement clarity. VDI/VDE 3513-2 uses G with qG, retains the non-linear error characteristic near the bottom of the scale, permits calculation at a defined operating point and requires both values to prevent a class number being interpreted in isolation [S1][S4].

Product catalogs also distinguish percentage of full scale from percentage of measured value. Full-scale statements are common on less accurate devices, while measured-value statements are generally associated with more precise devices [S4].

Class 1.6, Class 2.5 and Class 4

Class 1.6, Class 2.5 and Class 4 are cited VDI/VDE 3513 accuracy classes offered by manufacturers, but the class alone does not reveal whether the stated tolerance applies to the reading or the full-scale span [S6][S7].

Class 4 devices are also marketed with standard accuracy ranges of ±10%, ±5% and ±2% full scale, which indicates that the available class designation does not guarantee one universal accuracy figure [S7]. A defensible datasheet should therefore state the class, G, qG, calibration conditions and whether accessories are included, rather than writing only “VDI/VDE 3513 class.”

For applications with a stable operating point, calculate the allowed error at that point using the stated G and qG. For variable flow, evaluate several operating points, including the minimum normal flow and the point immediately below qG [S4]. This avoids buying a nominally precise class for a duty cycle concentrated near the bottom of the scale.

Where the Method Fits, and Where It Does Not

VDI/VDE 3513 accuracy class for variable area flowmeters - Where the Method Fits, and Where It Does Not
VDI/VDE 3513 accuracy class for variable area flowmeters - Where the Method Fits, and Where It Does Not

VDI/VDE 3513-2 is appropriate for local and process indication with variable area meters used for liquids, gases and steam, especially where the float position provides a direct readable indication [S1]. These meters can cover laboratory flow requirements and high industrial flow rates, with glass tubes for extremely low-pressure conditions and metal tubes for high-pressure, high-temperature, aggressive or opaque fluids [S1].

The method is not a substitute for application-specific flow calculation, installation design or instrument selection.

For custody transfer, turbine or other high-accuracy flow measurement may be a better specification than a rotameter when the commercial consequence of error dominates. For simple local indication with acceptable lower-range degradation, a variable area meter can remain economical and requires no external power for local reading [S1].

Installation, Scale and Fluid Effects

Accurate class compliance depends on more than the label. Calibration must match the specified density, viscosity, temperature and pressure, while the instrument must be installed and operated as required [S4]. ABB’s handbook identifies 1/2-inch to 2-inch meter tubes for viscosity effects and density corrections, showing that tube size and fluid properties remain part of the measurement calculation [S1].

Scale interpretation also has a fixed procedure. The upper edge of the float’s largest diameter indicates the flow value, and any replacement scale must align its marked reference point precisely with the meter-tube scale [S5]. A percent scale and a water flow scale in L/h are provided as a double scale, with special scales available in m³/h, GPM and for media such as HCl, NaOH and air [S5].

The same reference covers meter tubes from 1/16 inch to 2 inches in its design sections, including tri-flat glass tubes, plain tapered glass tubes, bead-guide glass tubes and plain tapered metal tubes [S2]. The broad design range does not mean every accuracy class, tube material and fluid combination is interchangeable.

Convert the Class into a Purchase Requirement

VDI/VDE 3513 accuracy class for variable area flowmeters - Convert the Class into a Purchase Requirement
VDI/VDE 3513 accuracy class for variable area flowmeters - Convert the Class into a Purchase Requirement

A purchase specification should name VDI/VDE 3513 Sheet 2, state the accuracy class, and define G and qG separately. For example, a meter specified at G = 5% and qG = 50% has a maximum permitted deviation of ±5% at or above 50% full scale, subject to the stated calibration and installation conditions [S5].

Do not convert Class 4 into “±4%” without confirming the manufacturer’s stated basis, and do not treat a 50% linearity limit as zero error below 50% full scale. At 30% full scale, G = 2.5% and qG = 50% produce a 4.166% relative-error allowance [S4].

The verifiable next step is to obtain the manufacturer’s current accuracy declaration, including the class, G, qG, fluid conditions, range and accessory exclusions. This reading plus range accuracy method provides a useful cross-check when comparing instruments that state accuracy in different ways.

Frequently asked questions

What accuracy values should be stated for a rotameter specified to VDI/VDE 3513-2?

State the error limit value G, the linearity limit qG, the accuracy class, calibration conditions, and whether the stated tolerance includes accessories. The class number alone does not identify whether error is referenced to the measured value or full scale.

What relative error is permitted at 30% full scale when G is 2.5% and qG is 50%?

The permitted relative error is 4.166%, calculated as F% = G × qG / q%. This calculation applies when installation, operation, and fluid conditions match the specified calibration conditions.

Do VDI/VDE 3513-2 Class 1.6, Class 2.5, and Class 4 each correspond to one fixed accuracy percentage?

No. The class is dimensionless and does not reveal the error basis by itself; Class 4, for example, appears with accuracy ranges of ±10%, ±5%, and ±2% of full scale. Procurement specifications must therefore include G, qG, and the manufacturer’s stated basis.

When should a variable area meter be replaced by turbine or another high-accuracy meter?

Consider turbine or another high-accuracy flowmeter when commercial custody-transfer consequences dominate the measurement error. VDI/VDE 3513-2 is better suited to local or process indication for liquids, gases, and steam where lower-range accuracy degradation is acceptable.

10 sources
  1. Handbook for Variable Area Flowmeters
  2. Variable Area Flowmeter Basic Fundamentals and ...
  3. Variable Area Flowmeter: Basic Fundamentals and ...
  4. Variable Area Flow Meter - Accuracy according to VDI/VDE 3513
  5. Type 335/350/123 Variable Area Flowmeter
  6. Variable Area Flow Meter (Rotameter) Selection Guide (6 days ago)
  7. Variable Area Flow Meters
  8. Variable area flow meters
  9. KROHNE applies new VDI/VDE 3513 guideline (Jun 4, 2009)
  10. What is Flow Meter Accuracy? Definition & Specs (May 29, 2026)

Need to source matching manufacturers or get a quote?

SpecForge connects industrial buyers with verified manufacturers. Submit your requirement and we will route it to matched suppliers.

Submit RFQ now →
Ask SpecForge AI