REQUEST FOR QUOTE Request a quote
SpecForge Editorial Team

Steam Separator Sizing and Selection: Spec Map, Velocity Bands, and Pressure Drop

Table of Contents
  1. Two accepted sizing methods: droplet settling vs. Souders-Brown
  2. Steam chart axis logic: pressure, flow, and ΔP together
  3. Velocity and pressure drop: the 60 ft/s design target
  4. Compressed air cross-check: same vessel, different axes
  5. Where centrifugal separators fail: high velocity, fouling, and pulsating flow
  6. Selection shortlist: 1,000 lb/h to 10,000 lb/h at saturated steam
Steam Separator Sizing and Selection: Spec Map, Velocity Bands, and Pressure Drop

A centrifugal steam separator is specified to remove entrained moisture from saturated or superheated steam lines, with published charts calibrated to 99% capture of droplets larger than 10 microns [S4].

Selection is governed by three coupled variables: saturated steam mass flow, operating pressure, and acceptable pressure drop across the vessel. For a design case at 180 psi g (12.4 bar g) and 1,100 lb/h (500 kg/h), Spirax Sarco S5/S6 charts show a 1¼ in separator running near 60 ft/s (18 m/s) line velocity with approximately 0.5 psi (0.03 bar) pressure drop [S3].

Two accepted sizing methods: droplet settling vs. Souders-Brown

Engineers size gas-liquid separators by either the droplet settling theory method or the Souders-Brown approach, both of which yield a maximum allowable superficial velocity that the vessel must not exceed at design flow [S6].

Droplet settling equates the terminal settling velocity of a target droplet size (commonly 100-150 microns for bulk knock-out) to a fraction of the gas superficial velocity, with the design K-factor adjusted for pressure, density, and demister efficiency. The Souders-Brown correlation compresses those terms into a single empirical constant K_SB, historically in the 0.1-0.4 ft/s range for vertical separators without a mist eliminator, and rising above 0.5 ft/s when a knitted mesh pad is fitted downstream [S6]. Because the Souders-Brown K constant is purely empirical, Moshfeghian recommends corroborating it against droplet settling theory whenever the service diverges from hydrocarbon three-phase duty [S6].

Steam chart axis logic: pressure, flow, and ΔP together

Steam sizing charts use pressure on the vertical axis, mass flow on the horizontal axis, and differential pressure on a secondary Y-axis, with one diagonal performance curve per vessel size [S4]. The procedure is to draw a horizontal line at the design PSIa to the ΔP axis, then a vertical line at the design lb/h; the separator size is read where the two lines intersect the nearest diagonal performance curve [S4].

The original FD Separators performance data traces back more than 50 years of laboratory testing on steam and compressed air, and the resulting charts and formulas underpin most current web-based sizing calculators [S4]. Since centrifugal vortex separators have an infinite turndown ratio, separation efficiency is maintained even at the lower pressures experienced during start-up and shut-down, provided the unit was correctly sized for the design case [S4].

Velocity and pressure drop: the 60 ft/s design target

Steam Separator sizing and selection guide - Velocity and pressure drop: the 60 ft/s design target
Steam Separator sizing and selection guide - Velocity and pressure drop: the 60 ft/s design target

Steam velocity at the separator inlet should be held near 60 ft/s (18 m/s) for the S5/S6 size range, with line velocity read off the chart as a function of pipe size and saturated steam flow [S3]. For the 1¼ in (DN32) unit at 1,100 lb/h and 180 psi g, the chart returns approximately 60 ft/s; for the ½ in unit at the same conditions the velocity climbs above 100 ft/s, which is outside the shaded "better than 99% separation efficiency" band [S3].

Pressure drop is read by plotting the intersection of the chosen separator size with the line velocity. At 180 psi g and 1,100 lb/h, a 1¼ in S5/S6 separator incurs about 0.5 psi (0.03 bar) loss, which is generally acceptable on a 180 psi distribution main [S3]. Wright-Austin's saturated steam capacity chart tops out near 10,000 lb/h on a 6 in line and falls to 220 lb/h on a ½ in line, with all curves anchored to the same SCFM conversion [S7].

Compressed air cross-check: same vessel, different axes

The same physical S5/S6 vessel is rated on a separate compressed-air chart, but with volumetric SCFM on the horizontal axis instead of steam mass flow [S3]. For 100 SCFM at 100 psi g, a 1¼ in separator again sits inside the 99% efficiency shaded band with ΔP of about 0.15 psi (0.01 bar); pushing to 350 psi g and 350 SCFM on a 1 in body lifts velocity toward 120 ft/s and ΔP to roughly 3 psi (0.2 bar) [S3].

Because the air and steam curves are derived from the same physical test matrix, the vendor recommends that the air chart be used for any non-steam gas service, including nitrogen, CO2, and natural gas, with appropriate compressibility adjustment [S4]. A cyclone separator sized on the steam chart and then operated on hot air at the same mass flow will over-predict capacity, since volumetric flow rises with temperature at constant mass flow.

Where centrifugal separators fail: high velocity, fouling, and pulsating flow

Steam Separator sizing and selection guide - Where centrifugal separators fail: high velocity, fouling, and pulsating flow
Steam Separator sizing and selection guide - Where centrifugal separators fail: high velocity, fouling, and pulsating flow

Performance drops sharply when the unit is fed flow above its design velocity or mass, because re-entrainment of the separated film on the vessel wall begins to dominate capture efficiency [S5]. TLV's published guidance is explicit: a separator's performance decreases if it is faced with a flow of higher velocity or mass than it is designed to handle, which is why the steam chart's "shaded band" exists [S5].

Three duty classes routinely violate that envelope and should be redirected to alternative internals. First, superheated steam with no entrained moisture is wasted capital on a centrifugal, since there is no coalescing film to throw off; a simple inline silencer or none at all is sufficient. Second, fouling or scale-forming feedwater (e.g. high-hardness boiler make-up) blinds the vanes within weeks, and a steam trap station placed downstream will not compensate for carryover slugs. Third, reciprocating-compressor discharge or PRV-downstream lines carry pulsating flow, which throws the vortex off-tune; a baffle-type or mesh-pad separator with a larger residence volume is the standard fix.

Selection shortlist: 1,000 lb/h to 10,000 lb/h at saturated steam

For saturated steam distribution headers in the 1,000-10,000 lb/h range, the practical shortlist is the FD Separators centrifugal line, the Spirax Sarco S5/S6 family, and the Wright-Austin 316L stainless cyclone. All three publish charts grounded in the same droplet-settling physics and rate at 99% capture above 10 microns [S4][S3][S7].

A side-by-side on four decision criteria reads as follows: (1) Line size fit, where FD and Wright-Austin offer ½ in through 6 in in matching increments and Spirax Sarco mirrors the same envelope; (2) Pressure drop, where the Spirax S5/S6 chart returns 0.5-2 psi (0.03-0.14 bar) across its working band versus 0.3-1 psi (0.02-0.07 bar) for FD's similar-dimension units at matched conditions [S3][S4]. (3) Material, where 316L stainless is standard across all three for clean steam, with carbon steel offered for utility headers; (4) Lead time and documentation, where Spirax Sarco ships the pre-printed TI-S99-10-US chart as part of the data packet [S3].

For a small clean-steam skid under 200 lb/h, the ½ in or ¾ in body on the S5/S6 chart is the right pick, because larger vessels cannot throttle down to maintain 60 ft/s without an external bypass [S3]. For a 10,000 lb/h distribution main, the 4 in or 6 in body is mandatory, and the design should be cross-checked against the air chart at the same volumetric flow to confirm the ΔP envelope [S3]. Trackable signals to confirm sizing post-installation: upstream pressure gauge vs. downstream pressure gauge at design load, with ΔP target 0.5-1.0 psi (0.03-0.07 bar) for clean steam service; carryover sampling per ASTM E1342 or equivalent at the first PRV downstream. Cross-reference on bearing hardware for header support frames is covered in slewing bearing selection practice.

Frequently asked questions

What inlet line velocity should a centrifugal steam separator be sized for to stay within the 99% efficiency band?

For Spirax Sarco S5/S6 units the design target is approximately 60 ft/s (18 m/s) line velocity at the inlet. A 1¼ in separator at 1,100 lb/h and 180 psi g reads about 60 ft/s, whereas a ½ in unit at the same conditions climbs above 100 ft/s and falls outside the shaded "better than 99% separation efficiency" band.

What pressure drop is typical for a 1¼ in S5/S6 steam separator at 180 psi g and 1,100 lb/h?

The Spirax Sarco S5/S6 chart returns roughly 0.5 psi (0.03 bar) pressure drop for a 1¼ in separator at 1,100 lb/h and 180 psi g, which is generally acceptable on a 180 psi distribution main.

What is the saturated steam capacity range covered by the Wright-Austin capacity chart for centrifugal separators?

The Wright-Austin saturated steam capacity chart tops out near 10,000 lb/h on a 6 in line and falls to 220 lb/h on a ½ in line, with all curves anchored to the same SCFM conversion.

Which three service conditions are explicitly listed as poor fits for centrifugal steam separators?

The article flags three duty classes that exceed the centrifugal envelope: superheated steam with no entrained moisture, fouling or scale-forming feedwater such as high-hardness boiler make-up, and pulsating flow from reciprocating-compressor discharge or PRV-downstream lines. Baffle-type or mesh-pad separators with larger residence volume are the standard alternative for the pulsating case.

7 sources
  1. Separation Capacity of Centrifugal Gas/Liquid Separators (Apr 5, 2026)
  2. Steam Separator Sizing Tool
  3. Sizing Chart for S5 and S6 Separators
  4. How to Size a Moisture Separator | Charts, Formulas ...
  5. Separators and their Role in the Steam System
  6. Gas-Liquid Separators Sizing Parameter
  7. Centrifugal Separator Steam Sizing Chart

Need to source matching manufacturers or get a quote?

SpecForge connects industrial buyers with verified manufacturers. Submit your requirement and we will route it to matched suppliers.

Submit RFQ now →
Ask SpecForge AI