For a hoist, a geared limit switch is the practical choice when travel must be derived from drum or gearbox rotation, while a rotary cam limit switch is the more specific mechanism for multiple shaft-position trips.
The decision is driven by input geometry, number of functions, reset behavior, and the required separation between slowdown, normal stop, and emergency overtravel.
Define the input and measurement requirement
Geared cam limit switches use a geared input and a series of cams to measure shaft rotations. In crane-hoist service, the lower operating position and the emergency end position can therefore be assigned to different cams [S2]. The device is not necessarily the cam mechanism itself: the cam is the position-setting element, while the gear reduction determines range and resolution.
A rotary cam limit switch directly interprets rotation of its operating shaft. The cam drives a follower or shuttle, which operates the electrical contact through a snap action [S3]. This arrangement suits winch drums, hoists, lifts, screw jacks, platforms, gate travel, and other moving equipment where motion is represented by shaft rotation [S1].
For a new hoist, write the mechanical basis into the specification before selecting a switch. Identify whether the driving member is the drum, drum gear, gearbox output, or an auxiliary shaft, and state the number of shaft revolutions per unit of hook travel. That calculation determines the reduction ratio and the physical spacing between cam positions; it is not an installation detail to leave to the switch supplier [S2][S7].
Compare the two switch architectures
On range and adjustment, the geared type offers upper, lower, and intermediate limits with adjustment across the movement range represented by the input shaft [S1]. The plain rotary cam type is also shaft-position based, but its practical range depends more directly on the number and spacing of cams than on a reduction gearbox [S2][S3].
On installation effort, a geared unit requires mechanical coupling and gear-ratio validation. A direct rotary unit requires shaft alignment and adequate torque transfer, but eliminates one reduction stage. On the SX1 hoist, the upper limit uses a hook-operated limit switch with two switches providing trip positions for normal operation and an extra degree of safety.
On maintenance, both approaches depend on correct mounting, cam integrity, and microswitch action. Cam contact gives defined switching points, while installation errors can produce premature failure even when the switch itself is suitable [S3]. Direct-drive rotation also transfers drum torque, shock, vibration, and contamination into the switch, while a gear train changes the operating torque seen by the cam mechanism and introduces gear backlash that must be included in repeatability assessment [S2][S7].
Match the switch to the hoist function

Use a geared limit switch when the hoist already exposes a usable rotary input and the design needs several position-dependent commands. Gemco describes geared rotary switches for upper, lower, and intermediate limits, with applications including crane and winch drums, hoists, lifts, screw jacks, and platforms [S1]. This is the normal choice when travel is intentionally tied to drum or gearbox rotation.
Use a rotary cam limit switch when the input shaft turns directly with the controlled mechanism and the required outputs are a small number of fixed cam angles. The cam engages a lever or plunger and makes or breaks the contact [S3]. This arrangement is direct, compact at the point of measurement, and easy to inspect for cam wear and contact setting.
Use separate mechanisms when different limits need different physical references. In the SX1 arrangement, the upper limit is hook-operated and the lower limit is drum-activated; the lower trip is adjustable by repositioning its bracket, while the upper setting is fixed [S5]. That arrangement is not interchangeable with a gearbox-mounted rotary switch without changing the safety concept and commissioning procedure.
These attributes belong to the cited switch element and must be confirmed for the assembled product rather than assumed for every cam switch.
Set slowdown, stop, and overtravel independently
A hoist limit switch can provide distinct slowdown, normal-stop and final-overtravel functions.
The extreme upper function is an overtravel protection device and is not intended to serve as the automatic operating stop [S5]. On the SX1 hoist, the lower limit switch is drum-activated, and its setting is adjustable by repositioning the switch on its bracket. These are application requirements that belong in the trip-setting sheet and acceptance test.
Separate the normal operating point from the final emergency point in the commissioning plan. One crane-hoist implementation describes an operator signal at the lower operating position and automatic drive shutdown at the emergency end position [S2]. That arrangement creates an operational tier before the protective tier, provided the controller logic and reset requirements are designed accordingly.
For every trip, record drum angle, hook position, commanded motion, resulting contact state, and reset behavior. A hook-operated design with two upper trip positions requires manual reset after the extra safety switch is operated, whereas the lower position in that example permits the load block to be lowered after the normal trip [S5]. The reset sequence must be tested, not inferred from contact labels.
Check installation, environment, and lifecycle constraints

Mount the rotary device where shaft alignment, backlash, vibration, and access to cams can be controlled. A gearbox-mounted unit in the documented SX2–SX7 design is turned directly by the drum gear and uses 4 microswitches [S5]. A geared architecture is more tolerant of high shaft speed because reduction lowers cam speed, but it adds coupling, lubrication, backlash, and gearbox-wear considerations [S2][S7].
Do not use the published contact count as a substitute for function definition. Four microswitches can represent 4 independent functions only if the cam positions, wiring, contact logic, and controller response are coordinated. For safety-critical shutdown, verify whether the contact opens positively, whether the downstream device removes hazardous drive energy, and what happens after a wire break or actuator failure [S2].
For a new installation, the more defensible comparison is: geared rotary versus direct rotary cam. The geared rotary option wins when a known drum or gearbox input and several adjustable travel positions are required, at the cost of added gearing and coupling. The direct rotary cam option wins when the shaft angle already equals the required limit angle, the trip count is modest, and simpler mechanics matter more than range reduction [S1][S2][S3][S7].
Specify contacts, settings, and acceptance tests
Specify the number and purpose of contacts before ordering. For example, one hoist rotary limit switch uses 4 microswitches with the identification sequence S1 phase-sequence supervision, S2 extreme upper limit, S3 slowdown, and S4 extreme lower limit [S5]. This is a functional allocation, not a universal terminal order, so it should be treated as an application example rather than copied into an unrelated hoist specification.
Define the normal stop, slowdown zone, final upper overtravel, and lower trip as separate acceptance criteria. Require proof that the slowdown function changes from high speed to slow speed, that the extreme upper trip acts when the maximum permitted drum winding and rated headroom are reached, and that the lower trip leaves no fewer than 2 wraps on each rope anchorage [S5].
Verify environmental requirements at the assembled-device level. The cited S870 element is rated up to IP67 and has self-cleaning contacts, while the geared assembly must also withstand the shock and vibration conditions associated with crane-hoist service [S2]. Electrical ratings, contact arrangement, positive opening, actuator travel, and reset behavior must be confirmed from the selected product documentation.
Document the interface between mechanical limit detection and the control system. A conventional limit switch provides discrete electrical states; it does not by itself establish motor torque, braking performance, rope condition, or overload protection. Those functions require separate drive controls and protection measures, while the limit switch supplies the selected position command.
Select by shaft reference, trip logic, and maintenance

Choose a geared limit switch when the design requires multiple adjustable limits referenced to drum or gearbox rotation, and when reduction can improve cam resolution without unacceptable backlash. Choose a direct rotary cam limit switch when the controlled shaft already rotates through the needed angles and fewer discrete cam positions are required [S1][S2][S7].
Choose a separate hook-operated upper limit when the upper travel reference must follow the hook or load block rather than drum rotation, but account for rope stretch, load swing, and the fixed-setting implications shown in the SX1 design [S5]. A single mechanical reference should not be assumed to represent the true hook position under every rope and load condition.
The practical recommendation for a geared rotary hoist is to require separate slowdown, normal operating, and final overtravel trips, with commissioning based on actual drum-to-hook travel rather than switch-shaft angle alone. For a direct rotary cam design, use the same functional separation, but retain the simpler input train and verify torque, wear, and cam-position repeatability. In both cases, the acceptance test must demonstrate the required contact state, drive response, reset condition, and remaining rope configuration at the lower trip [S2][S5].
The next engineering record should contain the calculated drum-revolutions-to-hook-travel ratio, one diagram per cam trip, the electrical logic for every contact, and witnessed test results at each trip point. Those four records expose ratio mistakes, duplicated trip functions, and unsafe reset arrangements before the hoist enters service.