Linear heat detector cable monitors heat continuously along its installed length, making it suitable for cable trays, conveyors, tunnels, cable risers and other long or inaccessible runs [S1].
Digital LHD activates when a specific temperature is reached along the cable, while analog LHD can indicate the approximate location of the heat event [S1][S6].
How Linear Heat Detection Covers Continuous Assets
Linear heat detection replaces a chain of point detectors with a heat-sensitive cable whose alarm threshold can be reached at any point along the route. This arrangement covers long, narrow or irregular spaces where fixed detectors would be impractical to position and maintain [S1].
Linear heat sensing cables can extend over 1 km, but installation-limited distances may require multiple cable segments [S2][S5].
For a tunnel, conventional heat detectors may cost less where accessible ceiling space provides a suitable mounting arrangement. Linear cable is generally easier to route along a cable tray, but installation convenience does not by itself establish code compliance or make detection mandatory [S2].
Digital and Analog Cable Compared
Digital, discrete or fixed-temperature cable responds when a specified temperature is reached, while analog cable detects changing thermal conditions and can identify the approximate location of the heat event along the run [S1][S6].
Non-resettable digital systems must have the affected section replaced after an alarm. Resettable analog systems can be reused following an alarm, and the analog arrangement generally provides better incident-location information [S5].
Linear and spot-type heat detectors may operate across similar temperature ranges, but selected linear systems extend to approximately 155°F to 356°F. Actual selection must follow the approved cable rating, ambient conditions and project fire strategy [S2].
Choose the Alarm Threshold and Cable Class

The cable alarm temperature must be selected from the approved product range for the protected equipment, not from a generic operating-temperature label. Linear heat detection cables trigger an alarm when a section reaches a set temperature [S1].
HDC68 and HDC105 linear heat detector cables are designed to monitor abnormal heat increase and help prevent escalation to a full fire event, illustrating that nominal cable models and their thresholds must be matched to the installation instruction [S3].
These certifications belong to named products and cannot be transferred to an unspecified substitute cable [S5].
Install Along Tunnels and Cable Trays
Tunnel installations must account for the full route length, whether cable trays are covered, expected temperature extremes and air velocity near the protected equipment. These variables affect whether a linear cable, point heat detector, aspirating smoke detection or another measure is appropriate [S2].
The cable should be routed along the cable tray or protected asset so a developing hot spot intersects the sensing element. Run geometry, branch points and local obstacles determine whether the route is continuous or must be divided into separately monitored segments [S1][S2].
When a section of continuous heat-sensing cable reaches a set temperature, it triggers an alarm identifying the general area where the heat event occurred [S1]. Equipment selection also requires attention to the protected control cable, because insulation damage, overload or an adjacent hot component can create the abnormal heat condition that the LHD system is intended to identify.
Match the System to Industrial Exposure

Linear heat detection is well suited to cable trays, conveyor belts, tunnels, and other long, narrow, or hard-to-access spaces where installing point detectors at regular intervals is impractical [S1].
KiddeFenwal offers LHS linear heat sensor cable, and its served-industry listings include data centers, petroleum oil and gas, battery energy storage systems, paint booths and flammable-material storage, and transportation infrastructure [S4].
Temperature rating alone does not define suitability. Ambient range, cable length, mounting arrangement, required alarm threshold, panel protocol, reset behavior and the protected equipment's failure mode must all be compatible. If the cable route passes near a heat detector or other fire-protection device, the design should avoid redundant coverage that creates nuisance alarms without improving response.
Verify Failure Response and Sourcing
A digital cable alarm requires replacement of the affected section, while an analog system can be reset after the condition is investigated. That difference affects spare-cable stock, inspection workflow and the operational consequences of a nuisance alarm [S5].
Integration with a control unit and fire alarm panel remains mandatory for both approaches. The panel must support the selected alarm type and provide the required alarm zone, status indication and notification interface; a compatible cable connected to an unsuitable control unit does not create a complete detection system [S1].
Specification records should identify the cable model, approved operating-temperature class, control unit, segment length, installed route, mounting method and panel input. These six items provide the traceable basis for verifying tunnel and cable-tray coverage and for comparing alternatives such as addressable and conventional heat detectors.
The next engineering check is to divide each tunnel and cable-tray route into measured segments, compare the selected cable's approved alarm temperature and maximum run length with the ambient design range, and confirm panel compatibility before ordering.