An insulation resistance tester, historically called a megohmmeter or by the trade name Megger, applies a controlled DC voltage across electrical insulation and measures the tiny leakage current that flows, then reports the result as a resistance in megohms (MΩ), gigohms (GΩ), or teraohms (TΩ). It is the workhorse instrument for proving that conductors are safely isolated from earth and from each other, used during installation verification, predictive maintenance of motors and transformers, and fault diagnosis on cables and switchgear.
Unlike a dielectric withstand (hipot) test, which is a destructive pass or fail proof, insulation resistance measurement is non-destructive and repeatable, so the same asset can be trended over years. Modern instruments add time-resistance diagnostics such as the Dielectric Absorption Ratio and Polarization Index to separate reversible moisture effects from genuine insulation aging.
Photo: Megger Ltd., CC BY 3.0, via Wikimedia Commons
This guide is written for procurement engineers and design engineers specifying or comparing insulation resistance testers. It covers six chapters, from working principle and instrument classes through diagnostic test methods, the standards that govern them, and the specification parameters that drive a buying decision, followed by seven selection FAQs and a maker comparison. All parameters reference the public standards IEC 61557-2, IEC 60364-6, IEEE 43-2013, and IEEE 95, and verified manufacturer datasheets from Fluke, Megger, and Hioki.
Chapter 1 / 06
What an Insulation Resistance Tester Is
An insulation resistance tester is a measuring instrument that determines the resistance of electrical insulation by applying a known DC voltage and measuring the resulting leakage current. By Ohm's law, the instrument divides the applied voltage by the measured current to display a resistance value. Because good insulation passes only nanoamps to a few microamps even under a kilovolt of stress, the resulting resistance is enormous, ranging from a few megohms for marginal insulation to tens of teraohms for clean, dry, high-grade dielectric. The instrument therefore needs a stable high-voltage DC source and a high-impedance current front end, two features that distinguish it from an ordinary ohmmeter or multimeter, which test at only a few volts and cannot stress insulation meaningfully.
The reason DC is used rather than AC is that AC would drive a continuous capacitive charging current through the unavoidable capacitance of windings and cables, masking the true leakage. With DC, the capacitive charging current decays after the first seconds, the polarization (absorption) current decays over minutes, and what remains is the steady conduction current that actually reflects insulation quality. This three-current behavior, capacitive charge, dielectric absorption, and conduction leakage, is the physical basis for the time-resistance diagnostics covered in Chapter 3.
The instrument has a long industrial lineage. The trade name Megger, still used generically in the field, dates to a hand-cranked generator instrument introduced in the early twentieth century by the British firm now known as Megger. The hand-crank magneto produced the test voltage mechanically, and the moving-coil ratiometer displayed megohms directly without a separate battery. Modern instruments replace the crank with a battery-fed DC-DC converter that regulates the output voltage electronically, and replace the analog ratiometer with a microcontroller that can log, time, and compute ratios automatically.
Three engineering attributes define the quality of an insulation resistance tester: the maximum test voltage it can deliver into a real capacitive load while holding regulation, the top of its resistance range and the noise floor at that extreme, and its measurement accuracy expressed under IEC 61557-2. A cheap unit may claim a high voltage but sag badly when connected to a long cable that draws charging current, producing optimistic readings. A quality instrument holds its rated voltage within a few percent even into a microfarad-scale load, which is what makes its readings traceable and comparable over time.
In application scale, insulation resistance testers span from 9 V battery handhelds verifying a domestic ring main at 500 V, to 100 W bench instruments testing 13.8 kV stator windings at 5 kV, to 15 kV diagnostic sets characterizing transmission cables and large generators. There is no single universal instrument, and the essence of selection is matching the asset voltage class, the required resistance ceiling, and the diagnostic depth to a specific instrument class.
Chapter 2 / 06
Instrument Types and Classes
Insulation resistance testers divide into four practical classes by test voltage and intended use: low-voltage handheld testers, insulation multimeters that combine the function with a DMM, high-voltage diagnostic testers, and continuous or online monitors. Choosing the wrong class is the most common procurement error: buying a 1,000 V handheld for a 6.6 kV motor leaves the winding under-stressed and the diagnostic worthless, while buying a 5 kV bench set for routine appliance checks wastes budget and portability. The table below summarizes the four classes.
Class
Test Voltage Range
Typical Resistance Ceiling
Typical Use
Low-voltage handheld
50 to 1,000 V
200 GΩ
LV installation verification, panel and cable checks
Insulation multimeter
50 to 1,000 V
2 GΩ
Combined DMM plus insulation for electricians
High-voltage diagnostic
500 V to 15 kV
10 to 35 TΩ
MV motors, generators, transformers, cables
Online / continuous monitor
Low DC bias
Asset dependent
IT-system insulation monitoring, fixed install
Low-voltage handheld testers are battery-powered units that deliver fixed steps of 50, 100, 250, 500, and 1,000 V DC. The Megger MIT400/2 series, for example, offers those five steps plus a variable mode adjustable from 50 to 1,000 V in 10 V increments, and reads up to a 200 GΩ ceiling. These instruments target low-voltage installation verification under IEC 60364-6 and BS 7671, where the standard test is 500 V DC with a 1 MΩ minimum. They typically integrate continuity and voltage functions and carry CAT III or CAT IV safety ratings for live distribution boards.
Insulation multimetersfuse a true-RMS digital multimeter with an insulation tester in one handheld, trading top-end resistance range for convenience. The Fluke 1587 FC provides 50, 100, 250, 500, and 1,000 V test voltages and measures insulation from 0.01 MΩ to 2 GΩ, while the simpler Fluke 1577 offers 500 V and 1,000 V and reads 0.1 MΩ to 600 MΩ. Their appeal is a single tool for an electrician who needs voltage, resistance, continuity, and insulation in the field, rather than the teraohm ceiling a maintenance engineer needs for clean machine windings.
High-voltage diagnostic testers deliver 2.5, 5, 10, or 15 kV DC and push the resistance ceiling into the teraohm decade so that very clean insulation does not saturate the reading. The Hioki IR3455 is a 5 kV instrument reading up to 10 TΩ, and the Megger MIT500 and S1 families and the BM5200 5 kV unit add automated PI, DAR, step-voltage, and dielectric-discharge programs. This class is mandatory for medium-voltage motors, generators, transformers, and cables, where a 1,000 V test would not properly stress 6.6 or 13.8 kV insulation.
Online and continuous insulation monitors are a distinct category: fixed devices that watch the insulation of an energized ungrounded (IT) power system in real time, alarming when resistance to earth falls below a set threshold. They are common in hospitals, ships, mining, and traction supplies where a first earth fault must not trip the supply. Although they share the underlying physics, they are specified by alarm threshold, response time, and system voltage rather than by a portable test program.
Chapter 3 / 06
Diagnostic Test Methods
Beyond a single spot reading, insulation resistance testers run several timed methods that exploit how the three component currents (capacitive charge, dielectric absorption, and conduction leakage) decay at different rates. Each method extracts a different diagnostic signal, and the higher methods cancel out temperature and equipment size, which a raw spot reading cannot. The table below compares the four mainstream methods.
Method
Duration
What It Computes
Good Result
Spot reading
15 to 60 s
Single IR value at fixed time
Above asset minimum
DAR
60 s
R(60 s) / R(30 s)
≥ 1.4
PI
10 min
R(10 min) / R(1 min)
≥ 2.0 (Class B/F/H)
Step voltage (SV/DAR step)
Multi-step
IR at rising voltages
Stable across steps
Spot reading is the simplest method: apply the test voltage, wait a fixed dwell time (commonly 60 seconds so the capacitive surge has settled), and record one resistance value. It is fast and adequate for go or no-go installation checks against a fixed limit, such as the IEC 60364-6 requirement of 1 MΩ at 500 V. Its weakness is that the absolute value depends heavily on temperature, humidity, and asset size, so a single number means little for trending unless it is temperature-corrected and compared like-for-like.
The Dielectric Absorption Ratio (DAR) divides the resistance read at 60 seconds by the resistance read at 30 seconds. Because both readings come from the same test seconds apart, temperature and size effects cancel, leaving a clean measure of how completely the absorption current has decayed, which reflects moisture and contamination. A DAR below about 1.25 flags wet or dirty insulation, while 1.4 and above is generally healthy. Its great advantage is speed: a meaningful diagnostic in 60 seconds rather than the ten minutes a PI demands.
The Polarization Index (PI) divides the resistance at 10 minutes by the resistance at 1 minute and is the primary diagnostic for rotating machinery under IEEE 43-2013. Clean, dry insulation keeps absorbing charge for many minutes, so its resistance climbs and the ratio is high; wet or aged insulation reaches steady conduction quickly, so the ratio approaches one. IEEE 43-2013 sets the acceptable minimum at 2.0 for Class B, F, and H insulation and 1.5 for Class A. Importantly, the 2013 standard notes that for very modern, dry windings reading above 5 GΩ at one minute, the PI can be misleadingly low and may be disregarded.
Step voltage testing applies the test in rising voltage steps, for example 1, 2.5, and 5 kV, holding each step for a set time and recording the resistance. Healthy insulation gives a near-constant resistance across steps because it is ohmic, whereas insulation with voids, cracks, or moisture shows a marked drop as the higher field ionizes defects, revealing weakness that a single-voltage test would miss. A related method, the dielectric discharge (DD) test defined in some standards, measures the reabsorption current one minute after the test voltage is removed to assess multi-layer insulation and is offered on high-end diagnostic sets.
Chapter 4 / 06
Governing Standards and Acceptance Limits
Insulation resistance testing is governed by a layered set of standards: one that defines what a compliant instrument must do, and several that define what a given asset must read to be accepted. Buying an instrument that does not meet the instrument standard, or applying an acceptance limit from the wrong asset standard, are both common and consequential mistakes. The table below lists the standards a procurement engineer should know.
Standard
Scope
Key Requirement
IEC 61557-2
The measuring instrument
Accuracy class, test-voltage tolerance, safety
IEC 60364-6
LV installation verification
≥ 1 MΩ at 500 V; ≥ 0.5 MΩ at 250 V (SELV/PELV)
IEEE 43-2013
Rotating machine windings
PI ≥ 2.0; min IR 100 MΩ (form-wound)
IEEE 95
AC machine insulation (2.3 kV+)
High-direct-voltage test method
BS 7671
UK wiring regulations
Aligns with IEC 60364-6 limits
IEC 61557-2 is the instrument standard. It specifies the accuracy classes, the permissible tolerance on the delivered test voltage, the minimum short-circuit (test) current the instrument must supply, and the operational safety requirements for equipment that measures insulation resistance in distribution systems up to 1,000 V AC. When a datasheet claims compliance with IEC 61557-2, it is asserting that its stated accuracy and voltage regulation hold under defined operating uncertainties, which is what makes readings from different compliant instruments comparable.
IEC 60364-6 governs the verification of low-voltage electrical installations. It requires a 500 V DC test for circuits rated up to 500 V, with a minimum acceptable insulation resistance of 1 MΩ, and a 250 V DC test with a 0.5 MΩ minimum for SELV and PELV circuits. Higher-voltage installation circuits up to 1,000 V are tested at 1,000 V DC with the same 1 MΩ floor. BS 7671, the UK IET Wiring Regulations, adopts these same test voltages and limits, so an instrument and procedure suitable for one is suitable for the other.
IEEE 43-2013, the recommended practice for testing insulation resistance of rotating machinery, is the controlling document for motors and generators. It defines the PI and DAR methods, mandates correcting spot values to a 40 degrees Celsius base, and sets recommended minimums: 100 MΩ for form-wound stator windings built after about 1970, and 5 MΩ for random-wound windings and form-wound coils rated below 1 kV. For AC rotating machines rated 2,300 V and above, IEEE 95 (the recommended practice for high-direct-voltage insulation testing of such machinery) covers the higher-voltage step and ramp methods used for acceptance and maintenance of large apparatus.
Two practical cautions follow from these limits. First, every asset class has its own number, so an installation reading of 2 MΩ that comfortably passes IEC 60364-6 would be a serious concern on a large form-wound motor expected to exceed 100 MΩ. Second, a widely used field rule of thumb, one megohm per kilovolt of rating plus one megohm, is a quick sanity check, not a substitute for the governing standard or the manufacturer specification. For acceptance testing of new apparatus, always defer to the equipment maker's stated minimum.
Chapter 5 / 06
Key Specification Parameters
Comparing datasheets is the core of selection. A given instrument may list dozens of figures, but only a handful drive the buying decision: test voltage steps, the top of the resistance range, accuracy class, short-circuit current, the available diagnostic programs, and the safety category. Each is explained below.
Test voltage and regulation. The headline figure is the set of DC test voltages, from 50 V on a handheld to 15 kV on a diagnostic set, but the figure that separates good instruments from poor ones is voltage regulation under load. A real motor winding or cable presents microfarads of capacitance, drawing a large charging current at the start of a test. The Megger MIT400/2 series, for example, advertises feedback-controlled output that holds overvoltage to within 2 percent, against an industry norm of 10 to 20 percent; tight regulation keeps the applied stress correct and the reading trustworthy.
Resistance range and resolution. The top of the range must comfortably exceed the highest resistance the clean asset will read, or the instrument saturates and the diagnostic is lost. Insulation multimeters such as the Fluke 1587 FC top out near 2 GΩ, low-voltage handhelds such as the Megger MIT400/2 reach 200 GΩ, and high-voltage diagnostic sets such as the Hioki IR3455 reach 10 TΩ. For trending clean machine windings, headroom into the teraohm decade is essential; for go or no-go LV checks against a 1 MΩ floor, a gigohm ceiling is ample.
Accuracy. Accuracy is specified under IEC 61557-2 and is usually quoted as a percentage of reading plus a number of digits, for example plus or minus 3 percent of reading plus 5 digits over a defined range. Because the same insulation can read across several decades depending on temperature and dwell, headline accuracy matters most when an absolute number is being compared against a contractual acceptance limit; for ratio tests such as PI and DAR, repeatability and a stable test voltage matter more than the last percent of accuracy.
Output signal and recording. Modern instruments add data interfaces and automated programs that turn the meter from a single-reading device into a trending tool. Capabilities to look for:
Automated PI and DAR: the instrument times the 30 s, 60 s, 1 min, and 10 min points and computes the ratios without manual stopwatch work.
Step-voltage and DD programs: pre-programmed ramps for diagnostic testing of large apparatus.
Temperature correction: on-board correction of spot readings to the 40 degrees Celsius IEEE 43 base when a temperature is entered or a probe is connected.
Logging and wireless: internal memory plus Bluetooth or USB to a maintenance app, for example Fluke Connect on the 1587 FC, so results are traced against the asset record.
Guard terminal: a third terminal to bypass surface leakage, essential for accurate volume-resistance readings on contaminated insulators.
Short-circuit current and safety category. IEC 61557-2 requires a minimum test current so the instrument can charge a capacitive asset in reasonable time, typically rated at 1 mA or more. The safety category, CAT III or CAT IV at a stated voltage, governs whether the instrument and its fused leads can be used safely on live distribution boards before isolation, and is non-negotiable for industrial field work. Automatic discharge of the tested asset at the end of a run is a further safety must-have on any capacitive load.
Chapter 6 / 06
Selection Decision Factors
To turn the preceding five chapters into a specific model, work through the decision sequence below. Most selection mistakes are not a single wrong figure but a premature decision at the wrong level, such as fixing on a brand before the asset voltage class and required diagnostics are settled. These eight steps make a reusable RFQ template.
Asset voltage class: First decide the highest equipment rating you must test. Up to 1,000 V favors a handheld or insulation multimeter; medium-voltage motors, transformers, and cables from 2.4 to 13.8 kV demand a 5 kV or higher diagnostic set so the insulation is properly stressed.
Required test voltages: Confirm the instrument provides the specific DC steps your standards call for, such as 250, 500, and 1,000 V for IEC 60364-6 work, plus a variable mode if you test electronics or capacitors that cap the allowable voltage.
Resistance ceiling: Pick a range with headroom above the cleanest asset you will read. Teraohm ceilings for machine windings, gigohm ceilings for LV installations. A saturated reading is a wasted test.
Diagnostic depth: Decide whether you need spot readings only, or automated DAR, PI, step-voltage, and dielectric-discharge programs for predictive maintenance and trending of rotating machinery.
Accuracy class and standard: Require IEC 61557-2 compliance and check the percent-of-reading accuracy against any contractual acceptance limits you must certify against.
Safety category and leads: CAT III or CAT IV at the working voltage, fused leads, automatic discharge, and live-circuit detection that inhibits a test if voltage is present. These protect the operator on industrial sites.
Recording and temperature correction: For maintenance programs, choose on-board logging, wireless transfer, and IEEE 43 temperature correction so results are comparable year over year without manual spreadsheets.
Total cost of ownership: Purchase price plus annual calibration (insulation testers should be calibrated yearly to keep readings traceable), lead and probe replacement, and the cost of unplanned downtime a missed diagnosis would cause. A diagnostic set that catches a failing winding pays for itself in one avoided motor failure.
One last frequently overlooked dimension is serviceability and calibration support: whether the maker offers local calibration laboratories, accredited (for example ISO 17025) certificates, firmware updates, and spare leads and probes. An instrument whose calibration must be shipped overseas for weeks each year is a poor fit for a busy maintenance team. Fluke, Megger, Hioki, Chauvin Arnoux, and Kyoritsu all maintain regional service and calibration networks, which makes them dependable choices for fleets of instruments that must stay in certification.
FAQ
What is the difference between an insulation resistance tester and a hipot tester?
An insulation resistance tester (megohmmeter) applies a moderate DC voltage, typically 50 to 5,000 V, measures the resulting leakage current in the nanoamp to microamp range, and reports a resistance in megohms or gigohms. It is a non-destructive condition check that you can repeat indefinitely on the same asset. A hipot (dielectric withstand) tester applies a much higher AC or DC voltage, often two times the rated voltage plus 1,000 V, for a fixed time to prove the insulation will not break down. Hipot is a pass or fail proof test that stresses the dielectric and can damage marginal insulation. Use the megohmmeter for trending and maintenance, hipot for type and acceptance proof. Many bench units combine both functions.
What test voltage should I apply for a given equipment rating?
A common field convention is to apply a DC test voltage at least equal to, and usually well above, the equipment AC RMS rating. Typical practice: 24 to 50 V circuits use 100 V, 100 to 500 V circuits use 500 V, 600 V class equipment uses 500 to 1,000 V, and medium-voltage motors and cables from 2.4 to 13.8 kV use 2,500 to 5,000 V. IEC 60364-6 specifies 500 V DC for circuits up to 500 V and requires at least 1 megohm, with 250 V DC and 0.5 megohm for SELV and PELV circuits. IEEE 43 recommends 500 to 1,000 V DC for windings rated up to 1,000 V and 1,000 to 5,000 V DC above that. Never exceed the manufacturer maximum DC voltage on electronics or capacitors.
What are the DAR and PI tests and what values are acceptable?
Both are time-resistance ratios that cancel out temperature and equipment size, leaving a pure measure of insulation dryness and cleanliness. The Dielectric Absorption Ratio (DAR) is the resistance read at 60 seconds divided by the resistance at 30 seconds, a 60-second diagnostic. The Polarization Index (PI) is the resistance at 10 minutes divided by the resistance at 1 minute. Per IEEE 43-2013, a PI of 2.0 or higher is acceptable for Class B, F, and H insulation, and 1.5 or higher for Class A. A DAR below 1.25 suggests moisture or contamination, while 1.4 or above is generally good. IEEE 43 notes that for very dry, modern insulation reading above 5 gigohms at one minute, the PI may lose meaning and can be disregarded.
Why must insulation resistance readings be temperature-corrected?
Insulation resistance is strongly temperature-dependent: it roughly halves for every 10 degrees Celsius rise and doubles for every 10 degrees Celsius fall in winding temperature. A reading taken on a hot motor right after shutdown can look alarmingly low, while the same insulation cold reads ten times higher. IEEE 43-2013 requires correcting all spot insulation-resistance values to a common 40 degrees Celsius base using a coefficient KT before comparing against limits or historical trends. Time-ratio tests such as DAR and PI are inherently temperature-independent because both readings are taken under the same conditions minutes apart, which is why they are preferred for trending. Always log the winding or ambient temperature alongside every reading.
What does the guard terminal do and when do I use it?
The guard terminal is a third connection that returns surface leakage current to the instrument without it flowing through the measurement circuit. On a contaminated or damp insulator, current creeping across the surface can dominate the reading and make good bulk insulation appear faulty. By wrapping a bare wire around the insulator surface and connecting it to guard, that surface path is bypassed, so the meter measures only the volume leakage through the bulk dielectric. Use guard when testing cables with exposed surface contamination, bushings, switchgear, and any asset where you must separate surface from volume resistance. On a clean, dry asset the guard connection makes little difference and can be omitted.
What is the minimum acceptable insulation resistance value?
It depends on the asset and the governing standard, not a single universal number. IEC 60364-6 requires at least 1 megohm at 500 V DC for low-voltage installation circuits, and 0.5 megohm at 250 V DC for SELV and PELV. IEEE 43-2013 recommends a minimum corrected to 40 degrees Celsius of 100 megohms for form-wound stator windings built after about 1970, and 5 megohms for random-wound windings and form-wound coils rated below 1 kV. A widely cited rule of thumb for cables and machines is 1 megohm per kV of rating plus 1 megohm. For trending, the absolute number matters less than a sustained downward trend across periodic tests on the same asset.
Which manufacturers and series are common for insulation resistance testers?
For low-voltage handheld work up to 1,000 V, the mainstream choices are the Fluke 1587 FC and 1577 insulation multimeters, the Megger MIT400/2 series, the Hioki IR4000 series, the Kyoritsu 3000 series, and the Chauvin Arnoux CA 6500 family. For high-voltage diagnostic testing of motors, cables, and transformers, common 5 to 15 kV instruments include the Megger MIT500 and S1 series, the Megger BM5200, the Hioki IR3455 5 kV tester, and the Fluke 1550C and 1555 with PI, DAR, and step-voltage modes. Select by maximum test voltage, top of the resistance range, accuracy class to IEC 61557-2, and whether you need automated PI, DAR, and temperature correction.