Air Intake Noise Control Enclosure

An air intake noise control enclosure is the acoustically treated box, plenum or housing fitted to the air inlet of an engine, gas turbine, compressor, blower or generator set. It combines a weatherproof shell, an air path lined with sound-absorbing ducts or divided by parallel-baffle silencer sections, and in most designs the intake filter stage. The machine breathes at its design flow rate and pressure loss while the tonal and broadband noise that would radiate from the intake is reduced by a stated insertion loss. The purchase balances two demands that pull against each other: every layer of lining and every row of baffles removes noise, and also takes pressure head from the machine that has to draw air through it.

This page treats the enclosure as one product with three jobs: silence the inlet, clean the air and keep the restriction inside the machine's allowance. The chapters that follow set out how intake noise arises and how lining, baffles and reactive chambers remove it, which structural variants exist, which parameters appear on a datasheet, how the sizing arithmetic runs, and what goes wrong in service and in the order. Figures come from the ducted silencer test standards ISO 7235 and ASTM E477, the intake filter standards ISO 29461-1 and ISO 5011, the OSHA occupational noise regulation and technical manual, and application documents published by Caterpillar, Cummins, Parker Hannifin and Vibro-Acoustics. Ranges from general practice are marked as typical.

Schematic longitudinal section of an air intake noise control enclosure: intake air enters through a weather hood and inlet louvre, passes a filter bank and parallel baffles with sound-absorbing infill, and leaves as treated air to the engine, gas turbine or compressor.

Diagram: SpecForge original schematic, drawn for this page.

The buying decision concentrates in four places. First the octave-band insertion loss schedule, read against the noise limit at the fence or at the operator's ear, because a single A-weighted number hides the low-frequency tone that a dissipative lining cannot touch. Second the pressure drop allowance, which a gas turbine pays for in output and heat rate and an engine pays for in derating. Third the filter stage, its efficiency class and its change interval. Fourth the shell: weatherproofing, coating and seals, where water, corrosion and leaks start.

Chapter 1 / 06

What an Air Intake Noise Control Enclosure Is and How It Works

An air intake noise control enclosure is the acoustically treated box, plenum or housing fitted to the air inlet of an engine, gas turbine, compressor, blower or generator set. Air enters through a hood or louver, passes the filter stage, moves through a lined and baffled air path, and leaves through a duct to the machine's air inlet, commonly the turbocharger or the compressor eye. The shell keeps rain, snow and dirt out of that path, the filter removes the dust, and the lining and baffles drain energy from the sound that travels back up the path from the machine. The enclosure is bought against two numbers that pull in opposite directions, an insertion loss and a pressure drop, both stated at the design airflow.

The noise leaving an intake has three origins. A reciprocating engine or reciprocating compressor draws air in pulses, once per intake event, and the unsteady flow leaves the inlet as a tone at the firing or intake frequency together with its harmonics. A fan, a turbine or a Roots blower adds a blade-pass tone, fixed by the number of blades and the shaft speed, to broadband turbulence noise from the fast air leaving the wheel; a screw compressor tones in the same way, in discrete volumes. Every bend, filter face and baffle adds more broadband noise, and turbulence reaching the blades of an axial fan can create 10 to 15 dB or more of excess fan sound power. The OSHA technical manual lists internal combustion engines, reciprocating compressors, centrifugal compressors, rotary positive displacement units, industrial fans and gas turbines among typical silencer applications.

A dissipative lining removes sound by friction. Air particles at the lining surface move in and out of the pores of a porous material and lose energy to viscous drag, so a wave decays steadily along the duct instead of passing through. The lining is either fixed to the inner faces of the shell and duct or built into splitters, also called parallel baffles, that stand in the air stream so that no sound has a clear line to the outlet. The fibrous fill is basalt, mineral wool or ceramic based, at densities of 56 to 128 kg/m3 (3.5 to 8 lb/ft3), and it sits behind a sound-transparent facing such as perforated plate with an open area of 15 to 33% or a fine wire mesh screen. The facing has to protect the fill from the air flow without shutting it off from the sound.

Each mechanism works best in its own band, and that decides the layout. The OSHA technical manual rates dissipative silencers as very good from 500 to 2,000 Hz and above 2,000 Hz, with low-to-medium pressure loss, and poor below 500 Hz. Low-frequency sound therefore needs the reactive mechanism: an expansion chamber, a sudden change of cross-section, or a resonator tuned to one tone reflects sound back toward the source so that it interferes with the oncoming wave. Reactive elements give good low-frequency attenuation and can be designed to minimize pure tones, but they work over a relatively narrow band and cost high-to-medium pressure loss. A combination unit is a reactive chamber with absorption added for the high frequencies.

Moving air changes the result, which is why ratings are taken with airflow. Sound traveling against the flow, as it does in an intake, gains low-frequency attenuation over the still-air case, while the velocity gradient at a baffle surface shifts the frequencies at which the unit performs best. The baffles also raise noise of their own, the flow noise or regenerated sound that the test standards report as a sound power level in each band. High-frequency sound, with a wavelength short beside the gap between baffles, beams straight through the passages. Staggering the baffles so that no line of sight runs from inlet to outlet adds up to about 10 dB at high frequency and no appreciable amount at low frequency, and thicker baffles add little beyond the depth sound can reach.

The parts of a complete enclosure follow the air. An inlet hood or weatherhood with a coarse screen or louver keeps out rain and large objects, and a moisture separator or mist eliminator may follow on turbine duty. The filter stage comes next, one or more rows of elements in frames that seal to the housing, with a differential pressure gauge across it to show when they are loaded. The silencer section, lining or baffles, occupies the plenum behind the filters. The outlet duct carries the air to the machine through a flexible connection that takes up relative movement, and a differential pressure transmitter can carry the filter and overall restriction readings to the control room. Drains sit at the low points, and access doors serve every filter row.

Chapter 2 / 06

Air Intake Noise Control Enclosure Types and Structural Variants

The simplest variant is the lined plenum. The inner faces of a sheet steel box carry absorptive material behind perforated sheet, the air turns once or twice inside, and a lined duct joins the box to the machine. The mass of the shell does part of the work: a dense outer casing with sound-absorptive material on its interior surfaces is the standard construction of an acoustic enclosure, and a well-designed and nearly airtight one can give as much as 30 to 40 dB of noise reduction. An intake enclosure cannot be airtight, because it has to pass the machine's air, so it behaves as a partial enclosure and the opening that admits air also lets noise out. The design answers by keeping the number of openings small, facing them away from listeners and lining the path through each one.

Where the plenum alone cannot give the required loss, a parallel-baffle section is built into it. The attenuation of the least-attenuated sound mode grows linearly with the length of the baffles measured along their perforated faces, and for a given length it depends on the ratio of that length to the width of the air passage between them. Narrow gaps and long modules attenuate more. Two effects cap the result: sound that flanks around the section, and the flow noise the baffles generate themselves. In large gas turbine exhaust silencers the peak attenuation seldom exceeds 45 to 55 dB for these reasons, and the oblique-wave attenuation that adds to the plane-wave result is capped at about 5 to 10 dB at high frequency.

The fill and its facing are where the dissipative variants differ. Standard construction is acoustic-grade glass fiber sealed behind perforated metal. The flow resistivity of turbine-grade fill, about 15,000 to 40,000 MKS rayls per meter at ambient temperature, sets where it works: fill of low resistivity attenuates low frequencies better and high frequencies worse than fill of high resistivity. A film-faced baffle places a thin plastic film between the perforated metal and the fiber to keep out moisture and dirt, at some cost in attenuation, so an acoustical spacer is added between metal and film. A no-media baffle is void of absorptive fill altogether and suits air that would clog or wet the fiber. Soft limp blanket fills gain low-frequency performance that is lost once the fill is compressed or settles.

Reactive and combination enclosures are built for the low-frequency tones that lining passes. The body is a chamber or a series of chambers joined by changes of cross-section, with tuned resonators where one tone dominates and absorptive lining on the chamber walls for the upper bands. Such units are usually custom designs, and their materials stand up to high-temperature and corrosive air. They suit the slow firing frequency of a large gas engine, the pulse of a low-speed Roots blower, and the low-frequency content that carries over long distances to a property line. Grade names borrowed from exhaust silencers, industrial, residential and critical, should not be accepted in their place: exhaust silencers carry those names with typical attenuation of 12 to 18 dB(A), 18 to 25 dB(A) and 25 to 35 dB(A), but an intake rating has to be an octave-band schedule.

The filter stage has its own variants, and the enclosure is often specified around them. Static systems for rotary machinery normally use several stages: a coarse stage for the bulk of the dust, a fine stage for the remainder, and an optional EPA or HEPA stage where the air is very dirty or the machine is sensitive. ISO 29461-1 covers static elements of this kind, including those with an efficiency of 85% or more for the most penetrating particle size. On dusty sites a self-cleaning filter with a pulse system takes the place of the static stages. Engine enclosures take dry elements with a safety element behind the primary one, and a precleaner where dust is heavy, at a restriction of 0.25 to 1.5 kPa (1 to 6 in. H2O).

The boundary against neighboring products is worth fixing. A pneumatic silencer is a small exhaust muffler screwed onto the port of a compressed-air cylinder or valve; it quiets air escaping to atmosphere and has nothing to do with the air a machine draws in. A whole-machine acoustic hood, or canopy, surrounds the engine, alternator and radiator of a generator set; the air intake enclosure is the treated air path alone, and on a packaged set it is one element inside that hood. The enclosure sits between the atmosphere and the machine's air inlet. Upstream of it are weather, dust and neighboring exhaust outlets. Downstream are the turbocharger or compressor, the ventilation equipment that may share the duct, and the instruments that measure restriction.

Chapter 3 / 06

Air Intake Noise Control Enclosure Key Specifications and Standards

The datasheet of an intake enclosure carries four laboratory quantities. Insertion loss is the difference in sound pressure level at a fixed point before and after the silencer is placed in the duct, reported in octave bands, commonly from 31.5 Hz to 8,000 Hz, with and without airflow. Pressure drop, strictly the total pressure loss, is stated at one or more airflows. Flow noise is the sound power the unit generates in each band while air passes through it. Shell transmission loss is the reduction of sound passing through the casing, which matters where the enclosure stands near listeners or feeds a duct that carries noise out before it is fully attenuated. ASTM E477 notes that insertion loss varies with frequency and with the direction and speed of airflow, and that pressure drop and airflow-generated noise both rise with air speed, so data are needed at several airflows.

The measurement standards agree on those quantities and differ in scope. ISO 7235 specifies laboratory methods at ambient temperature for the insertion loss, flow noise and total pressure loss of ducted silencers of all types, air intake applications included, and warns that results in situ differ because the sound and flow fields differ; pressure loss reads lower in the laboratory than in the installation. ASTM E477 makes the same measurements for duct liner materials and prefabricated silencers of building ventilation systems and excludes reactive mufflers, so a reactive intake chamber is proven on a test rig based on the method. On the limit side, the OSHA regulation 29 CFR 1910.95 permits 90 dB(A) over an 8-hour day, measured on the A scale at slow response, and requires a hearing conservation program from an 8-hour average of 85 dB(A), with feasible engineering controls first.

The filter stage carries its own standards and ratings. ISO 29461-1 gives test methods for static filter elements in the intake systems of rotary machinery such as stationary gas turbines, compressors and other stationary internal combustion engines. Elements of lower efficiency are tested by the ISO 16890 series, whose first part, ISO 16890-1, sets the particulate matter efficiency classification, and elements of 85% or more by the most penetrating particle size are classed as EPA or HEPA. ISO 5011 covers the air cleaners of internal combustion engines and compressors and reports airflow restriction, dust collection efficiency and dust capacity; one engine maker asks for 99.5% minimum efficiency on that dust test. The same guide wants inlet air of 15 to 32 degrees Celsius (60 to 90 degrees Fahrenheit), never above 45 degrees Celsius (113 degrees Fahrenheit), and total duct restriction below 0.5 kPa (2 in. H2O).

ParameterTypical value or rangeWhat it decides
Insertion loss by octave band31.5 to 8,000 Hz band centersNoise reaching the receiver in each band; the figure to guarantee
Dissipative section, working band500 to 2,000 Hz and above 2,000 HzMid and high frequency tones and turbulence noise; weak below 500 Hz
Reactive section, working bandLow frequency, narrow bandFiring and blade-pass tones; needs a custom design
Perforated facing, open area15 to 33%Protection of the fill against the air flow
Fill density56 to 128 kg/m3 (3.5 to 8 lb/ft3)Flow resistivity, hence the band attenuated
Silencer pressure drop, ventilating practiceup to 85 Pa (0.35 in. water)Energy lost to the fan or machine; flow noise
Total intake restriction, enginesbelow 0.5 kPa (2 in. H2O)Filter life, derating, turbocharger life
Air velocity in intake piping10 m/s (2,000 fpm) maximumDuct bore, noise and restriction
Air velocity at the inlet louver2.5 to 3.6 m/s (500 to 700 fpm)Inlet area; carry-over of rain and snow
Duct vacuum, structural design12.5 kPa (50 in. H2O)Shell and stiffener gauge of a suction plenum
Filter efficiency, engine99.5% minimum, ISO 5011 testDust reaching the cylinders and turbocharger
Filter efficiency, turbine85% or more for EPA and HEPACompressor fouling and erosion
Inlet air temperature15 to 32 degrees Celsius (60 to 90 degrees Fahrenheit)Air density, power and heat rate
Workplace noise limit90 dB(A) for 8 hoursInsertion loss needed at the operator position
Chapter 4 / 06

Air Intake Noise Control Enclosure Selection and Duty Calculations

Selection runs in a fixed order. Establish the noise reaching the receiver in each octave band without treatment, set the limit to be met, and the gap is the insertion loss to buy. Then check that the enclosure delivering that gap fits inside the pressure drop the machine can spare, at the site's airflow and weather.

The required insertion loss comes from a path calculation that starts at the source. The octave-band levels of everything that contributes are added logarithmically, never by plain addition: two equal sources raise a level by about 3 dB(A), and 89, 90.5 and 92 dB(A) combine to 94.4 dB(A). The natural attenuation of the duct and plenum is subtracted, and the positive difference between what remains at the receiver and the limit in each band is the insertion loss to specify. Distance helps: in a free field the level falls by 6 dB(A) for each doubling of distance, so a set rated at 95 dB(A) at 7 meters (23 feet) reads about 72 dB(A) at 100 meters. A reflecting wall adds about 3 dB(A), and property-line limits of 60 dB(A) by day and 50 dB(A) at night are common.

Inside the enclosure, geometry is matched to frequency. Attenuation of the least-attenuated mode is linear in the length of the baffles along their perforated faces and depends on the ratio of that length to the width of the air passage, so low-frequency duty calls for narrow passages, long modules and fill of low flow resistivity, near 15,000 MKS rayls per meter at the bottom of the usual range. Making baffles thicker buys little: past the depth sound can penetrate into the fill, extra thickness adds only a small low-frequency gain while it shrinks the open flow area, which raises velocity, self-generated noise and pressure drop. For high-frequency tones the passages are kept narrow or the baffles staggered, because short wavelengths otherwise beam straight through them.

Pressure drop follows the square of velocity. Doubling the air speed multiplies the loss by four, which is why silencer families are graded by velocity, from ultra low classes rated 0 to 2.5 m/s (0 to 500 fpm) up to high velocity classes rated 6.4 to 10.2 m/s (1,250 to 2,000 fpm). The catalog figure is then multiplied by inlet and outlet system-effect factors: a centrifugal fan set hard against the inlet carries a factor of 1.5 and a mitered elbow without turning vanes at the discharge a factor of 2.9. One engine guide's worked case, 36.7 m3/min (1,292 cfm) through 152.4 mm (6 in.) pipe with 3 m (10 ft) of straight run and 3 elbows, loses 1.02 kPa (4.07 in. H2O), twice the 0.5 kPa (2 in. H2O) it allows.

What restriction costs depends on the machine. For a gas turbine a common rule of thumb allows about a 0.4% loss of power output and a 0.1% rise in heat rate for every 250 Pa (1 in. water gauge) of inlet pressure drop, and turbines are rated at 15 degrees Celsius (59 degrees Fahrenheit), 60% relative humidity and sea level. For a diesel or gas engine, excessive vacuum at the turbocharger inlet reduces power capability and degrades performance, the intake restriction is an emissions-critical parameter, and each engine has a maximum total restriction that covers dirty filters, ducts, vents and silencers together. A heavier filter stage and more ducting derate the engine and shorten turbocharger life, so the enclosure's share has to be agreed with the engine maker before the silencer is lengthened.

Airflow sets the size. The design flow is read from the machine data sheet at its reference conditions and corrected to site temperature, because volumetric flow grows with absolute temperature for a constant mass flow. Face area is that flow divided by the velocity limit of each element: the free area at the inlet louver, the filter face, and the gaps between baffles. For the ventilation louvers of a generator set room, the Cummins manual applies a 122 m/min (400 fpm) limit and obtains 9.2 m2 (99.2 ft2) of effective flow area; the same arithmetic sizes the louver of an intake enclosure. Finally the unit's own noise is checked: silencer selection guidance asks for a flow-noise evaluation whenever pressure drop, system effects included, exceeds 85 Pa (0.35 in. water).

Selection factorWhat to establishHow it shapes the enclosure
Source spectrumOctave-band levels at the inlet and the tones presentHow much low, mid and high frequency insertion loss to buy
Receiver limitProperty-line, community or workplace limit and its distanceThe gap in each band becomes the specified insertion loss
Low-frequency toneFiring or blade-pass frequency of the machineReactive chamber or resonator; narrow passages; low-resistivity fill
High-frequency toneBlade-pass and turbine tones above 2,000 HzDissipative lining; staggered baffles; lined outlet duct
Pressure drop allowanceEngine or turbine restriction budgetBaffle thickness, passage width, face area and length
AirflowDesign flow at site temperature and altitudeSize of the louver, filter face and silencer module
Inlet air qualityDust load, moisture, salt, nearby exhaustsFilter stages and efficiency class; facings; coatings
ClimateDew point near freezing in winter; coastal siteInlet heating, drains, aluminum or coated shell
Maintenance accessElement size, change interval, drain pointsDoor positions, withdrawal space, instrument taps
Chapter 5 / 06

Air Intake Noise Control Enclosure Installation, Maintenance, and Typical Failure Modes

Most enclosures that disappoint in service were badly connected rather than badly designed. The machine vibrates and the shell does not, so every joint between the two is a place where either dirt gets in or noise gets out. The points that follow track the air from the hood to the turbocharger.

The enclosure and its ducting carry their own weight. An air cleaner system should never be mounted on the engine block or on any engine component, because the engine is not built to carry it and its vibration would pass into the structure and the piping. Ductwork beside the engine is supported so that no load reaches the turbocharger, and the flexible connection is made as close to the engine as practical. Joints are flanged with gaskets in preference to threaded connections, and rivets are not used, because debris from them can work loose and enter the turbocharger. Where air cleaners are remote, every joint is airtight, since a leak downstream of the filter admits unfiltered air.

Flexible connections serve two purposes at once. They take up the misalignment, relative movement and vibration between engine and enclosure, and they break the structure-borne path by which engine shake would make the duct and shell radiate. On engine intakes a flexible rubber fitting engages the duct by 50 to 200 mm (2 to 8 in.) and is kept away from exhaust heat that would perish the rubber; on ducts too large for such a fitting a fabric expansion joint takes the movement in the same way. Vibration from the skid anchors, pipes and conduits reaches a building by the same route and is treated with flexible connections there too. Airborne flanking is closed by seals: any gap through which air can pass lets a significant amount of noise pass as well, and the casing's transmission loss should exceed the insertion loss expected by at least 10 dB.

Weather protection is part of the acoustic design, because a blocked or wet enclosure is a restricted one. The inlet is shielded from direct rain and snow by a cap or hood carrying a coarse screen against large objects, and the hood is shaped to add as little restriction as possible. Rain-trap louvers give the air a tortuous path at low velocity so that drops coalesce before the filter; limiting inlet velocity to 2.5 to 3.6 m/s (500 to 700 fpm) keeps most rain and snow out of a generator room. Water that does enter needs a drain and must not pond where the intake can pick it up again. Where humidity is high and the air manifold can cool below the dew point, a float-operated drain valve removes its condensate. Access doors serve every filter row and every drain.

Maintenance centers on the filter and the fill. Elements are changed on the differential pressure reading rather than on a calendar: a direct-reading differential pressure gauge is connected between the duct and a straight length of pipe upstream of the turbocharger, or a latching service indicator shows when the element needs attention, and where outside air is used the indicator must sense the atmosphere the air was drawn from. The primary element is changed without disturbing the safety element behind it, so that dirt held in the housing is not dumped into the engine, and the engine is never run without its air cleaner. The absorptive fill is inspected at outages. Loose fill settles under gravity, vibration and thermal cycling, leaving voids at the top of each baffle, and the compacted part attains a higher flow resistivity with slightly reduced mid-frequency attenuation.

The failure modes follow from those duties. Water ingestion comes from an unshielded inlet, a louver run above its velocity limit, or ice: in saturated air with the dew point near freezing, small pressure and velocity changes at the inlet release moisture that freezes on the element, cutting the flow area and raising the pressure differential until power falls and fuel consumption rises. Corrosion attacks the perforated liner and the shell where moisture is trapped, faster in salt air within 97 km (60 miles) of the sea, where aluminum housings or an epoxy coating replace coated steel. Starving the engine is the end state of neglected restriction. Tonal breakthrough shows up when a reactive unit is asked to work outside the narrow band it was tuned for, or when high-frequency sound beams through passages left too wide.

  1. Prove the duct clean and remove the blanking plate ahead of the turbocharger; the plate carries a warning tag, and the duct is inspected immediately before the first start.
  2. Shut and seal every access door, check the flexible connection for correct engagement and freedom from strain, and confirm with a vibration analyzer that the shell is isolated from the machine.
  3. Run at full load with clean elements, traverse the inlet face with an anemometer to confirm even velocity, and record the restriction across the filter and across the whole enclosure.
  4. Measure the noise at the specified distance with a sound level meter and an octave band analyzer, with the background more than 10 dB(A) below the machine.
  5. File both sets of readings as the baseline for later checks on filters, seals and infill.
ItemTrigger or intervalFailure if neglected
Filter elementsDifferential pressure at the maker's change pointRising restriction; derating and loss of power
Absorptive fillInspection at each major outageSettled or wet fill; mid-frequency attenuation falls
Perforated liner and facingsVisual check for corrosion and holesFill erosion and debris drawn into the machine
Seals, gaskets and door latchesEvery reassemblyFlanking noise; unfiltered air bypassing the filter
Drains and condensate trapsRegular draining, more often in humid airWater ingestion; corrosion from trapped condensate
Flexible connectionsCheck for heat damage, offset and strainVibration passed to the duct; cracking and leaks
Inlet hood, louvers and screensClear of debris, snow and ice before startIcing and blockage; flow area lost
Clamps and flange fastenersCheck after the first running periodDirt ingestion through a loosened joint
Noise and restriction baselineAfter installation and after major workGradual loss of performance goes unnoticed
Chapter 6 / 06

Air Intake Noise Control Enclosure Industry Applications and Procurement Checks

Intake enclosures serve any machine whose inlet is loud enough to matter. Standby diesel generator sets take them as part of a sound-attenuated canopy, where the inlet duct commonly carries ventilating air for the room as well as combustion air, so its louver is sized for both flows. Gas engines driving compressors or pumps need them for low-frequency pulsation, and gas turbines for intake tones and for the filter house that stands around the silencer. A Roots blower or a turbo blower on aeration duty, centrifugal compressors and axial compressors, and large industrial fans are all standard silencer applications. The enclosure is a weatherproof housing at the same time, and the box that silences an outdoor set also keeps snow and driven rain off its filters.

A purchase order for an intake enclosure states performance as numbers with a test behind them. The insertion loss is guaranteed band by band from 31.5 Hz to 8,000 Hz at the design airflow, tested to ISO 7235 or ASTM E477, with pressure drop and flow noise at the same airflow and at the maximum continuous flow. The supplier is asked for data at several airflows and for the laboratory report itself, since both standards warn that installed performance departs from laboratory performance, and ISO 7235 states that pressure loss in the installation will be higher. Where the order states a sound pressure level rather than an insertion loss, it names the distance and the measurement condition, because noise levels only compare when they are converted to the same distance base, and a property-line limit is verified at the property line.

Materials follow the site. In salt air every enclosure part is galvanized, powder coated or painted with a salt-resisting paint, with care where moisture can be trapped; within 97 km (60 miles) of salt water aluminum is preferred to coated steel, and stainless steel is specified where cold-rolled steel would corrode. The fill is glass fiber, rock wool or basalt, with its density and facing stated, and a film facing or no-media construction is written in where the air is wet or oily. Instrument connections are listed as well: taps for a differential pressure gauge or manometer across the filter and across the silencer, a dust detector on the clean side of the filter on turbine duty, and the alarms that go with them. Any transmitter or damper actuator mounted outdoors needs its own IP enclosure rating or NEMA enclosure rating, independent of the acoustic shell.

A complete inquiry states, in this order: the machine, its airflow at site conditions and its maximum allowable intake restriction; the octave-band noise at the inlet and the limit at the receiver with its distance; the insertion loss required in each band and the test standard for proving it; the pressure drop and flow noise allowed at design and maximum flow; the filter stages, their efficiency class under ISO 29461-1, ISO 16890-1 or ISO 5011, and the change-out differential pressure; the inlet air temperature range and the site's dust, humidity, salt and freezing conditions; the materials and coatings for shell, liner and fill; the duct size, flange type and the position of the flexible connection; and the instruments, access and drains required. The buyer asks in return for laboratory reports at several airflows, a statement of how far installed pressure drop will exceed the laboratory value, the weight and outline drawing, the maintenance schedule with its element change criteria, and a warranty that names the guaranteed insertion loss and pressure drop.

FAQ

How does an air intake noise control enclosure work?

It forces the inlet air through a path that absorbs or reflects the sound traveling out of the machine. In a dissipative section, fibrous lining behind a perforated facing turns sound energy into heat by friction, which works well from 500 Hz upward and poorly below 500 Hz. In a reactive section, expansion chambers and tuned resonators reflect low-frequency tones back so that they cancel. Most enclosures combine the two, then add a filter stage and a weatherproof shell around them. The machine draws its design airflow through the same path, so the enclosure is rated by two numbers that work against each other: the insertion loss it gives and the pressure drop it costs.

What types of silencer are built into an air intake noise control enclosure?

Three families are used. Lined plenums cover the inner faces of the box with absorptive material and let the air turn inside. Parallel-baffle sections stand splitters in the air stream, so attenuation grows with their length and with the narrowness of the gaps; baffles may be filled with glass fiber or rock wool, film faced against moisture, or built with no fill at all. Reactive and combination units use chambers and resonators for low-frequency tones and add lining for high frequencies. The filter stage varies alongside: static coarse, fine and EPA or HEPA stages on turbines, panel elements with a safety element on engines, and self-cleaning stages on dusty sites.

Which specifications matter most on an air intake noise control enclosure?

Start with insertion loss in octave bands from 31.5 Hz to 8,000 Hz, with and without airflow, because one A-weighted number can hide a low-frequency tone. Next the pressure drop at the design airflow: a gas turbine loses about 0.4% of output and gains 0.1% in heat rate per 250 Pa (1 in. water gauge) of inlet drop, and an engine derates when its restriction limit is exceeded. Then the flow noise the unit generates itself, the open area of the perforated facing, typically 15 to 33%, the fill density and the shell's transmission loss. For the filter stage, the efficiency class and the dust test behind it decide what reaches the machine.

How do you size an air intake noise control enclosure?

Work from the noise gap and the pressure budget. Add the octave-band levels of every source logarithmically, subtract the natural attenuation of the duct, and the positive difference from the limit in each band is the insertion loss required. Divide the design airflow by the allowed face velocity to get louver and filter areas; inlet velocity is commonly held to 2.5 to 3.6 m/s (500 to 700 fpm) to keep out rain and snow, and piping to 10 m/s (2,000 fpm). Then size the baffle section, long modules and narrow passages for low frequencies, and check that its catalog pressure drop stays inside the machine's allowance once inlet and outlet system effects are added.

How is an air intake noise control enclosure installed and maintained?

Mount the enclosure and its ducting on their own supports, never on the engine or turbocharger, and join the outlet to the engine with a flexible connection that engages the duct by 50 to 200 mm (2 to 8 in.) and stands clear of exhaust heat. Use gasketed flanges rather than rivets, and blank the turbocharger inlet until the duct has been proved clean. In service, change filter elements on the differential pressure reading, drain condensate traps, and inspect the baffles for fill that has settled or got wet, since compacted fill loses mid-frequency attenuation. Replace seals and gaskets whenever the enclosure is reassembled, because small gaps let noise and unfiltered air through.

What drives the cost and lead time of an air intake noise control enclosure?

Attenuation demand is the first driver. Sound attenuation takes material and space, so an enclosure asked for a large insertion loss needs longer or more baffles, a heavier shell and a larger footprint, and it costs more and takes longer to build than a weather hood. Custom reactive sections for low-frequency tones are engineered one-off and add lead time. Material choice follows: stainless steel costs more than cold-rolled steel, aluminum and special coatings are needed near salt water, and EPA or HEPA filter stages add to the filter bill. Finally the site: a louver or duct run longer than first planned, and instruments such as a differential pressure transmitter, add engineering time.

Which standards and noise limits apply to an air intake noise control enclosure?

ISO 7235 and ASTM E477 are the laboratory methods for the insertion loss, flow noise and pressure drop of ducted silencers; ISO 7235 excludes reactive silencers for motor vehicles and warns that installed results differ from laboratory ones. The filter stage is tested under ISO 29461-1 for rotary machinery, ISO 16890-1 for particulate matter efficiency classes and ISO 5011 for engine and compressor air cleaners. In United States workplaces the OSHA regulation 29 CFR 1910.95 permits 90 dB(A) over an 8-hour day and starts hearing conservation at an 8-hour average of 85 dB(A), with engineering controls required first. Outdoor installations also face local property-line limits, often 60 dB(A) by day and 50 dB(A) at night.

Sources

  1. ISO 7235, ducted silencer laboratory measurement
  2. ASTM E477, duct liner materials and prefabricated silencers
  3. Caterpillar, Air Intake Systems application and installation guide
  4. Cummins, liquid cooled gen set application manual
  5. OSHA, 29 CFR 1910.95 occupational noise exposure
  6. Vibro Acoustics, Silencer Selection Instructions