An aftercooler is a heat exchanger mounted immediately downstream of the last compression stage of a compressed air system, cooling the discharged air so that most of its water vapor condenses while it is still in one place and can be drained before the air dryer, the receiver, and the distribution piping. Air leaves a screw or reciprocating compressor at 80 to 120 deg C, holding several times the water a cool pipe can carry; the aftercooler brings it to within 5 to 15 K of the cooling medium, drops the bulk of that load into a moisture separator, and passes air at perhaps 25 to 40 deg C on to the next stage of treatment. Air-cooled designs use a fan and finned coil, rejecting heat to ambient, while water-cooled designs run shell and tube or plate geometry against a cooling water circuit, and both are rated by capacity at stated inlet temperature, outlet temperature or approach, and pressure drop.
Procurement engineers meet these coolers in two situations: buying them built into a new compressor package, where they are often bundled and their rating deserves the same scrutiny as the compressor itself, and retrofitting them onto installations whose dryers, receivers, and piping are drowning in condensate the plant never intended to carry. The decision this page settles is what the cooler must be specified to deliver on paper: the outlet temperature and approach at the site's worst ambient or cooling water condition, the pressure drop budget, the condensate separation and drain arrangement, and the split of labor between the aftercooler and the dryer behind it. The answer lands as an RFQ line set covering capacity, approach, medium conditions, pressure drop, materials, and drain type, and every chapter below feeds that line set so the water leaves the system where the drawing says it should.
This page treats the aftercooler as a purchasing object: what cooling air temperature actually does to the water it carries, how air and water cooled designs differ in approach and siting, how pressure drop and drain hardware decide whether the condensate ever leaves, and how capacity, medium conditions, and materials combine into a defensible RFQ. It is written for engineers who issue purchase specifications, not for readers who want a brochure summary.
Chapter 1 / 06
What an Aftercooler Is and What Is Being Decided
The problem being solved is water, carried invisibly. Atmospheric air enters the compressor with humidity, and compression concentrates it: at 8 bar, a cubic meter of compressed air holds the water vapor of eight cubic meters of intake air in one, and at 90 deg C it holds all of it as vapor. Somewhere downstream the air cools to ambient, and if that somewhere is the piping, the water condenses in the pipes, corrosion and freeze and ruined point-of-use treatment follow. The aftercooler chooses the somewhere deliberately: it cools the air immediately after compression, in a vessel fitted with a separator, so the water condenses where a drain can remove it. Everything else the component does, protecting the dryer, stabilizing the receiver, improving volumetric delivery, follows from that one decision.
What is actually being decided in this purchase is four guarantees. First, thermal duty: the cooler must reach the specified outlet temperature at the site's worst design condition, summer ambient for air-cooled units or the supply water temperature for water-cooled ones, at full compressor flow, and the rating must state those conditions rather than a laboratory pair. Second, pressure drop: every millibar the cooler adds is permanent energy loss downstream of the compressor, and the budget is typically tens of millibar for well-sized units, proportionally more for compact ones. Third, condensate handling: a separator with effectiveness worth its name, and a drain, timer, float, or zero loss electronic, matched to the site's energy and environmental standards. Fourth, medium compatibility and siting: air-cooled units need ambient air and reject their heat into the room, water-cooled units need a cooling water circuit with its own quality and pumping story, and the choice between them is an infrastructure decision as much as a thermal one.
Against its neighbors the aftercooler occupies deliberate ground. The air dryer behind it removes the vapor that remains after cooling, to a dew point the aftercooler cannot reach: a cooler delivering air at 35 deg C leaves a pressure dew point of 35 deg C, while a refrigerated dryer reaches 3 deg C and a desiccant unit minus 40 or beyond, so the cooler is the bulk stage and the dryer the polishing stage, never alternatives. The intercooler inside the compressor, cooling between stages, improves compression efficiency and lives inside the compressor package; the aftercooler cools after the last stage and exists for the water, and the two are confused mostly by name. The air-cooled heat exchanger as a process product cools process streams in fin-fan banks under API 661 family practice; the compressed air aftercooler is a smaller, packaged cousin, bought on capacity and approach rather than on process exchanger datasheets. A dry cooler or cooling tower serves the plant water circuit that a water-cooled aftercooler plugs into, one step removed from the air path. The aftercooler takes the narrow territory between compressor discharge and dryer inlet, and nothing else in the plant holds that position.
References that organize the datasheet are manufacturer and machinery standards rather than a single component code. Compressor package practice, ISO 1217 for acceptance testing of displacement compressors context and the package standards around it, treats the aftercooler as part of the compressor train with its outlet temperature guarantee. Heat exchanger construction follows the manufacturer's mechanical standards, with pressure parts to PED or, where specified, ASME practice, and materials certificates where the site requires them. Condensate drains carry their own energy logic: zero loss electronic drains are standard on new plants, timer drains on legacy ones, and oil carrying condensate falls under the site's water treatment obligations, an emulsion separation story that begins at this drain. A datasheet that quotes capacity without inlet and medium conditions, or outlet temperature without approach, is a price tag, not a specification.
The RFQ should also name the train so the package checks out as a system. Upstream, the compressor defines the duty: a screw compressor at 8 bar and 40 cubic meters per minute discharging at 95 deg C, or a reciprocating compressor, centrifugal compressor, scroll compressor, or diaphragm compressor with its own discharge temperature signature, and the cooler is sized from that signature at full flow. Downstream, the receiver, the air dryer, and the filtration train receive the cooled air, with a temperature transmitter on the cooler outlet telling the dryer whether its inlet limit is respected, since refrigerated dryers commonly cap inlet at 50 to 60 deg C. In that train a coalescing filter catches the oil aerosol and fine mist that no moisture separator intercepts, a dew point transmitter after the dryer is the only instrument that proves the delivered pressure dew point instead of assuming it, and where the plant feeds an on-site nitrogen generator, its PSA or membrane skid is one more downstream customer that depends on this cooled, dried feed air. Around the cooler itself, a pressure gauge or pressure transmitter across it reads the fouling trend, a check valve arrangement may be needed on the water side, a ball valve isolates for maintenance, and a Y strainer protects the water circuit connection. Stating the whole train in the RFQ lets one supplier check temperatures, dew point staging, and drain compatibility across the package in a single pass.
Chapter 2 / 06
How Cooling Turns Vapor into Drainable Condensate
The arithmetic is saturation, and every specifier should run it once by hand. Water vapor capacity of air rises steeply with temperature: air at 8 bar and 90 deg C holds roughly 424 grams of water per cubic meter of compressed air at that condition, while the same air cooled to 35 deg C holds about 39 grams. Cooling therefore condenses around 90 percent of the water load in one exchanger, and each further 10 K removes most of what remains, in a curve that flattens as it falls. This is why the aftercooler does the bulk of the water work and why the dryer's job is measured in single digit grams: the division of labor is physics, not preference. It is also why outlet temperature is the performance number: 5 K warmer air out of the cooler can nearly double the load the dryer sees, and the dryer, sized on a datasheet inlet temperature the site never sees in summer, becomes the bottleneck that shows up as wet air at the tools.
Approach temperature is the honest way to read any quotation. For an air-cooled aftercooler, approach is the difference between cooled air outlet and ambient dry bulb; practical packages deliver 10 to 15 K family at full flow, better with oversized coils and fan power. For a water-cooled unit, approach is against the cooling water inlet, and shell and tube or plate designs reach 5 to 10 K family. A quotation stating 25 deg C outlet with no ambient or water condition attached is meaningless, and the RFQ fixes this by demanding the rating at the site's design condition: summer ambient from the site meteorological basis for air-cooled units, or the cooling water supply temperature at coincident load for water-cooled ones. Altitude derates air-cooled capacity both through air density and fan performance, and coastal or dusty sites add fouling margins that a fair datasheet will price.
Separation is where condensate becomes removal. Cooling the air is necessary but not sufficient: the droplets must be intercepted before the gas turns the next corner, and the aftercooler package therefore ends in a moisture separator, a cyclonic or baffle chamber that spins the flow or forces direction changes so droplets deposit on walls and drain to the sump. Separator effectiveness is stated as removal at a droplet size band, commonly better than 95 to 99 percent of droplets above roughly 5 to 10 micron, and the residual passes to the dryer as vapor plus fine mist, which the dryer's own separator catches. The sump connects to the drain, and the drain is the component that decides whether the separated water actually leaves: a missing or failed drain refills the separator and re-entrains water, converting a healthy cooler into an expensive elbow.
Pressure drop is the operating cost side of the purchase. Air at 8 bar crossing the cooler and separator loses energy permanently, and the pressure drop at full flow is a datasheet row worth comparing: compact add-on coolers run higher proportional drop, sometimes 100 to 200 millibar family, while generously sized integrated units hold tens. Each 100 millibar of extra drop at the compressor inlet condition costs a fraction of a percent of compressor power, continuous, which prices the difference between a well-sized and a marginal cooler over a decade. The drop also rises with fouling, both on the air side, dust and oil varnish on fins and tubes, and on the water side, scale, so the clean cooler figure should be quoted with the fouled allowance the maintenance plan accepts, and a differential pressure reading across the cooler belongs in the plant's condition monitoring set.
A worked example fixes the whole chain. Take a 45 kW screw compressor delivering 5.5 cubic meters per minute, roughly 195 scfm, at 8 bar with discharge at 95 deg C and site humidity that loads the air with 2.4 kilograms of water per hour. An air-cooled aftercooler rated 5.5 cubic meters per minute, inlet 95 deg C, ambient 35 deg C design, outlet 45 deg C, approach 10 K, condenses about 2.1 kilograms per hour of water at the drain, passing 0.3 kilograms per hour as vapor at a pressure dew point of 45 deg C. A refrigerated dryer behind it takes the dew point to 3 deg C, condensing nearly all of the remainder at its own drain. If the same cooler were quoted to 40 deg C outlet at 25 deg C ambient only, the summer day at 35 deg C would deliver 50 deg C air, double the vapor load forward, and stress the dryer past its rating; the specification, not the hardware, is what fails. The numbers in the example are family figures for scale, and the method is the deliverable: state conditions, read approach, run the water balance, check the dryer.
Chapter 3 / 06
Types, Construction, and Duty Boundaries
Two cooling architectures cover the catalogs, with packaging variants inside each. The air-cooled aftercooler passes compressed air through a copper tube, aluminum finned coil while an axial fan, electric or in some packages motor driven off the compressor, pushes ambient air across it; heat lands in the compressor room or the package canopy, and no water connection exists. The water-cooled aftercooler passes air through a shell and tube or compact plate core against plant cooling water; heat leaves with the water to the cooling tower or dry cooler circuit, and the unit is compact and quiet. Between them sit the packaged variants: coolers integrated in the compressor package, sharing canopy, fan, and controls, and add-on or retrofit coolers, standalone units bought to fix a wet system or to supplement an integrated cooler that cannot reach summer outlet targets.
Construction choices carry the warranty in both architectures. Air-cooled coils are copper tube with aluminum fins, epoxy or e-coated fins in coastal or aggressive ambients, with the air side bore often galvanized or stainless for hygiene duty; the fan is direct drive axial in most packages, with sound levels of 70 to 85 dB(A) family at 1 m where no canopy attenuates it, a siting constraint as real as the thermal one. Water-cooled cores are copper or stainless tube in steel or stainless shells, plate cores in brazed or gasketed form for compactness, and the water side demands the quality story every heat exchanger in the plant already knows: strainer protection, velocity limits, and a fouling allowance in the rating. Motors on fans run fixed speed as standard, with VFD fan control appearing on packages where ambient swing is wide and energy or outlet temperature stability matters, trimming fan power in cool weather and holding approach in hot.
Boundaries are worth stating bluntly. The aftercooler does not replace the air dryer: 35 deg C pressure dew point air is wet air for any plant that runs tools, and the cooler's job ends at bulk removal. It is not an intercooler, which cools between compression stages for efficiency and lives inside the compressor; retrofitting a between-stage duty is a compressor engineering project, not a catalog purchase. It is not a process air-cooled heat exchanger under API 661 style practice, which cools process streams in banks with engineered bundles and is purchased on a different datasheet. And a cooler cannot be asked to fix a wrong compressor discharge temperature: a reciprocating unit running hot because of valve wear, or a screw unit with a failed oil cooler, will overwhelm an aftercooler sized for the healthy signature, and the correct purchase in that case is the compressor service. The duty map below pairs common installations with the construction that survives them.
Installation
Construction to specify
Construction to avoid
Screw compressor package, temperate site
Integrated air-cooled cooler, 10 to 15 K approach fan
Add-on cooler duplicating an adequate integrated unit
Hot climate, water circuit available
Water-cooled shell and tube with strainer and fouling margin
Air-cooled unit rated only at 25 deg C ambient
Wet legacy piping retrofit
Add-on air-cooled with separator and zero loss drain
Cooler without separator, relying on the receiver to catch
Coastal site, salt air
Coated fins, sealed fan motor, corrosion margin
Bare aluminum fins with unsealed motor
Low noise indoor plant room
Water-cooled core or attenuated canopy fan
Bare axial fan at 85 dB(A) beside an office wall
High purity or food air
Stainless air side, hygiene drain and materials letter
Galvanized bore with unlisted paint contact
Wide ambient swing site
Fan with VFD or two speed control on outlet temperature
Fixed speed fan freezing the winter approach
Compressor running hot from wear
Compressor service first, cooler sized after
Aftercooler upsized to mask a sick machine
Chapter 4 / 06
Key Specification Parameters
The table below decodes the datasheet lines that decide whether a quoted cooler matches the system. Each row is a purchase defining parameter; the paragraphs after the table explain what to demand and what a weak answer looks like.
Attribute
Typical range or options
What it decides
Capacity and flow basis
m3/min or scfm at stated pressure and inlet temperature
The duty point every other number reads against
Outlet temperature and approach
Approach 5 to 15 K by design and medium
Water load forward and dryer inlet respect
Design ambient or water condition
Summer dry bulb or coincident water supply temperature
Whether the rating survives the worst site day
Pressure drop
Tens to about 200 millibar family at full flow
Permanent energy loss and fouling headroom
Cooling architecture
Air-cooled fan and coil or water-cooled shell and tube or plate
Siting, noise, and the water circuit dependency
Separator effectiveness
95 to 99 percent removal above 5 to 10 micron family
Whether condensed water actually leaves the air
Drain type
Float, timer, or zero loss electronic
Condensate removal reliability and air waste
Materials
Copper or stainless air side, fin coating options
Corrosion life in coastal, chemical, or hygiene duty
Noise
70 to 85 dB(A) family at 1 m for air-cooled fans
Plant room acceptance and siting constraints
Instrumentation
Outlet temperature and differential pressure reading
Fouling trend and dryer inlet protection
The outlet temperature row deserves a paragraph of its own because it is where quotations hide. A stated outlet without its ambient or water condition is unverifiable; the strong datasheet reads capacity, inlet temperature, outlet temperature, and medium condition as one set, and adds the approach so two coolers can be compared on a level line. Demand the rating at the site's design condition, and where the site meteorological basis gives a summer dry bulb above the datasheet ambient, ask for the derated figure or the next size. The same discipline applies to the pressure drop row: quote at full flow, state whether clean or design fouled, and price the difference against compressor energy over the service life.
The separator and drain rows decide whether the thermal work pays off. Demand the separator effectiveness statement with its droplet size basis, and specify the drain by type with the zero loss electronic option as the default on new plants, timer drains accepted on legacy scope with their air waste priced. Where the compressor is lubricated, the condensate carries oil and the drain connection is the beginning of the emulsion treatment obligation, so the RFQ should name the condensate routing and the site's treatment interface. The comparison table below compresses the evidence checks into the form a specification meeting can argue from.
Evidence demanded
Strong answer
Weak answer
Rating basis
Flow, inlet, outlet, medium condition as one set
Outlet temperature with no ambient stated
Worst day performance
Derated figure at site design ambient or water
Only the 25 deg C catalog condition quoted
Pressure drop
Full flow figure, clean and fouled allowance
Low drop claim with no flow basis
Separator proof
Removal percent at droplet size band
Moisture separator listed with no effectiveness
Drain scope
Type stated, zero loss option priced, routing named
Drain excluded, site to provide
Corrosion margin
Coated fins or stainless where site air demands
Bare aluminum assumed everywhere
The instrumentation row closes the specification. A temperature reading on the cooler outlet protects the dryer inlet limit and verifies the approach in service, and a differential gauge or transmitter across the cooler trends fouling on both sides of the exchanger; neither instrument costs a tenth of one wet-system callback, and both produce numbers the next RFQ reuses. The quotation that quotes the exchanger and leaves drain, instrumentation, and medium conditions as site exercises is not a complete quotation.
Chapter 5 / 06
Selection Decision Factors and RFQ Language
The decision sequence is short enough to run as a checklist in a specification meeting, and each step eliminates a class of quotations before price comparisons begin.
Fix the duty from the compressor: type, flow at pressure, discharge temperature signature, and the water load the site humidity implies, because the cooler is sized from the machine, never the reverse.
Set the design condition honestly: summer ambient from the site meteorological basis for air-cooled units, coincident cooling water temperature for water-cooled ones, with altitude and fouling margins priced.
Choose the architecture on infrastructure: no water circuit or heat wanted in the room points air-cooled; water circuit present, tight siting, or noise limits point water-cooled.
Fix the outlet target against the dryer: respect the dryer's inlet temperature cap with margin, and remember each 5 K warmer doubles the remaining vapor load forward.
Budget the pressure drop: tens of millibar for generously sized units, and price any excess as compressor energy over the service life.
Specify the separator and drain: effectiveness with droplet basis, zero loss electronic drain as the new plant default, and condensate routing named for the oil and water story.
Match materials to the air: coated fins and sealed motors coastal, stainless air side for hygiene or high purity duty.
Fix the evidence set: rating at site conditions, derated worst day figure, drop at full flow clean and fouled, separator effectiveness, and materials certificates where the site audits them.
Against neighboring equipment, the comparison a specifier actually needs runs as follows, and it belongs here in the selection chapter rather than in the page title. A refrigerated or desiccant air dryer removes the vapor the cooler leaves, to dew points the cooler cannot reach, and the two are stages in series, not competitors; sizing the dryer for the cooler's actual summer outlet temperature is where the pair is usually mis-specified. A dry cooler or cooling tower rejects the water side heat of a water-cooled aftercooler through the plant circuit, one step removed from the air. A plate heat exchanger or shell and tube heat exchanger may literally be the core inside a water-cooled aftercooler, purchased then on process exchanger practice. The intercooler between stages is compressor internals and stays there. The aftercooler wins its narrow post-discharge territory on one argument: it is the cheapest place in the system to remove the most water, and every kilogram it drains is a kilogram the dryer, receiver, and piping never see. Choose it on the water balance, not on the coil that quotes lowest.
The application map below turns that comparison into a table the project file can carry.
Application
Package to specify
Check before order
New screw compressor 7 to 8 bar
Integrated air-cooled cooler with separator and zero loss drain
Package outlet temperature at site summer ambient
Reciprocating compressor, hot discharge
Add-on heavy duty cooler sized on actual signature
Valve condition first; cooler after the service
Water-cooled plant with tower circuit
Shell and tube aftercooler with strainer and fouling margin
Coincident water temperature at full tower load
Wet piping retrofit at a food plant
Add-on stainless cooler, hygiene drain, materials letter
Condensate routing to emulsion treatment
Desert or high altitude site
Oversized air-cooled with fan control and derate check
Density and fan derate documented
Compressor room near offices
Water-cooled core or attenuated package
Sound data at 1 m against site limit
The RFQ block should be written once and reused. A complete block reads: compressor type, capacity in m3 per minute or scfm, working pressure, and discharge temperature at full load; required outlet temperature and the basis, with the dryer inlet cap stated; design ambient dry bulb or cooling water supply temperature and flow at coincident condition; acceptable pressure drop at full flow, clean and design fouled; architecture, air-cooled fan and coil or water-cooled core, with packaged or add-on framing; moisture separator effectiveness at droplet basis; drain type with zero loss electronic preferred and condensate routing interface; materials, air side and fins with coating options, water side tube and shell; noise at 1 m where siting matters; instrumentation, outlet temperature and differential pressure provisions; and the evidence set, rating table at stated conditions, worst day derated figure, separator effectiveness, and material certificates where audited. A quotation returned without the condition set, the drop figure, or the drain scope is incomplete at any price.
Chapter 6 / 06
Installation, Standards, Failure Modes, and Maintenance
Installation quality decides whether the cooler holds its approach. Air-cooled units need the fan's air path respected: clear inlet and discharge, no recirculation from a wall or adjacent package, and the heat they reject accounted in the room ventilation balance, because a cooler fighting its own recirculated air loses its approach quietly. Water-cooled units need the water circuit discipline every exchanger deserves, a Y strainer at the connection, velocities in the design band, isolating ball valves for tube-side service, and the fouling allowance the rating assumed actually maintained by the water treatment program. Mount the separator drain with its line falling to the condensate point, no traps that hold water, and bring the outlet temperature reading to where operations reads it, since it is the number that says the dryer is protected. On retrofit installs, locate the cooler as close to the compressor discharge as practical, because the pipe between them condenses water too, unseparated, and that water arrives at the cooler already liquid.
Commissioning practice proves the rating and the drain. At full compressor load and design or near-design medium condition, log inlet and outlet air temperatures and the ambient or water state, and verify the approach against the datasheet; a miss here, found on the first hot day of the first summer, is a warranty conversation, and the same numbers logged routinely are the baseline for fouling trends. Verify the drain by observing discharge, float action or electronic cycle, and measure the condensate over a timed interval against the water balance calculation; a drain that never fires while the separator sump fills is a failed drain wearing a healthy cooler's reputation. Check the pressure drop across the cooler at commissioning as the clean datum, and log the differential reading location so the same points are read every time.
The standards context is package and machinery practice. Compressor acceptance and package rating context comes from ISO 1217 family practice for displacement compressors, and the aftercooler's guarantee reads inside the compressor package datasheet when integrated or on its own rating sheet when add-on; pressure parts follow PED or specified ASME practice with material certificates where audited; the drain and condensate story connects to the site's environmental obligations for oil carrying water. Sound data where relevant follows the package's noise basis. A specification that states the rating conditions and the certificate expectations by name transfers the burden of proof to the supplier, which is where it belongs.
Failure modes in service follow a short and predictable list. Fin fouling on air-cooled coils: dust, oil mist, and plant air varnish coat the fins, approach widens, outlet climbs, and the dryer inherits the load; the fix is scheduled coil cleaning, monthly to quarterly by environment, and the differential and outlet temperature trends are the alarm. Water side scaling on water-cooled cores: the same story in mineral, approach widens first at full load, and the water treatment program plus periodic mechanical or chemical cleaning is the countermeasure. Drain failure: float drains stick open and waste air or stick closed and flood the separator, timer drains clog at the orifice, and electronic zero loss units fail on sensor or solenoid; the drain is the highest maintenance density component on the package and deserves the spares and check schedule of a wearing part, because it is one. Separator re-entrainment: a sump overfilled by a lazy drain or a velocity over design shreds separation effectiveness, and wet air downstream of a dry-looking cooler is the symptom; the drain fix and the flow check resolve it. Corrosion: bare aluminum fins in salt or chemical air white rust and lose surface, coated fins hold years longer, and stainless air side ends the conversation where hygiene or aggressive condensate demands it. Fan and motor faults: bearing wear moves the fan down its curve quietly, motor trips stop cooling abruptly, and a fan VFD fault on controlled packages leaves the cooler at full or zero fan depending on failure mode; both are found by the outlet temperature alarm reading and the ear.
Maintenance intervals scale with environment more than hours. Air side cleaning lands monthly in dusty plants, quarterly in clean rooms; water side inspection rides the plant's exchanger program, annual open and inspect on open circuits, condition based on closed treated loops. The drain is checked weekly by observation and serviced on the manufacturer's cycle, with a spare on the shelf. The instrumentation set, outlet temperature and differential pressure, is read into the trend file monthly, and every reading is a number the next RFQ can use: approach at conditions, drop at flow, drain interval at load. None of these checks costs a tenth of one wet line callback, and the file they build is how a purchasing file gets smarter instead of just older.
FAQ
Should I choose an air-cooled or water-cooled aftercooler?
Air-cooled units need no water circuit, are simpler to site as add-ons, and put their heat into the room air, which the ventilation design must carry. Water-cooled units are compact, quiet, and reach closer approaches against a cooling water circuit, but inherit the water quality, strainer, and fouling story of that circuit. If the plant already runs a tower or closed loop with capacity, water-cooled usually wins; otherwise air-cooled is the default.
What approach temperature should I expect?
Practical air-cooled packages deliver cooled air about 10 to 15 K above ambient dry bulb at full flow, better with generous coils and fan power. Water-cooled shell and tube or plate cores reach about 5 to 10 K above the cooling water inlet. Always demand the outlet temperature stated together with its ambient or water condition, and check the figure at your site's design day, not the catalog's 25 deg C.
Does an aftercooler replace the air dryer?
No. The aftercooler removes the bulk of the water by cooling to maybe 35 deg C, which is a pressure dew point of 35 deg C: fine for bulk removal, wet for any real plant. The refrigerated or desiccant air dryer behind it takes the dew point to 3 deg C or minus 40 and beyond; the cooler is the bulk stage, the dryer the polishing stage, and sizing the dryer on the cooler's actual summer outlet temperature is what makes the pair work.
What drain should the separator have?
Zero loss electronic drains are the modern default: they sense condensate, discharge it, and close without wasting compressed air. Float drains are simple but stick in either direction; timer drains waste air on every cycle and clog at the orifice. Because the condensate from a lubricated compressor carries oil, the drain line also starts the emulsion treatment obligation, so name its routing in the specification.
What is the difference between an aftercooler and an intercooler?
An intercooler sits between compression stages inside the compressor train, cooling partially compressed air to reduce the work of the next stage; it is compressor internals. The aftercooler sits after the last stage and exists to condense water where a drain can remove it, protecting the dryer and piping. Retrofitting between-stage cooling is a compressor engineering project, not an accessory purchase.
How much pressure drop should the cooler add?
Generously sized integrated units hold tens of millibar at full flow; compact add-on coolers may run 100 to 200 millibar family. Every millibar is permanent compressor energy, so quote the drop at full flow, clean and fouled, and price the difference over the service life. A rising differential trend on the installed unit is also the cleanest fouling alarm the cooler has.
Do hot climates or altitude change the sizing?
Yes. Air-cooled capacity derates with ambient, since the approach is against it, and with altitude through thinner air and reduced fan performance; a cooler quoted at 25 deg C ambient can miss its outlet target by 10 K on a 40 deg C day, doubling the vapor load the dryer sees. Ask for the derated rating at the site's design condition and price the next size if the margin is thin.