Control System Cordset

A control system cordset is a length of cable with a connector molded onto one or both ends at the factory, made to carry power and signals between a field device and the controller that reads or drives it. The molded joint does three jobs at once: it seals the cable entry against dust and water, it takes the pull on the cable so that the strain never reaches the conductor joints, and it holds the marking that identifies the connection. The usual forms are M8 and M12 sensor and actuator cordsets with A, B, D or X coded contacts, M23 cordsets for drives and encoders, valve connector cordsets, and industrial Ethernet cordsets.

The page is for the engineer who has to specify these assemblies by the hundred for one machine or a whole plant: fix the connector family and coding, the number of contacts, the jacket material, the shield, the degree of protection and the length, then write all of it into a purchase specification. A molded cordset is bought rather than made on site because the joint at the connector is the weak point of a sensor circuit: a conductor soldered and taped by hand cannot be sealed or strain relieved as a factory overmold is, and the result shows as an intermittent signal under vibration or washdown. For that reason a machine builder orders cordsets as standard parts with defined codings, ratings and lengths, by the hundred, and treats them as replaceable items.

A black right angle overmolded M8 connector with a knurled metal coupling ring and a three hole insert, next to a small straight socket with three gold pins, on white.

Photo: Phiarc, CC BY-SA 4.0, via Wikimedia Commons

The buying decision on a control system cordset concentrates in five places. The port on the device fixes the connector family and coding, and a differently keyed plug cannot be mated at all. The wiring drawing fixes the pin count and pin assignment. The environment fixes the jacket: dry interiors, oil and coolant, or cleaning agents. The zone fixes the degree of protection, which holds only on a connection that is mated and tightened to torque. The movement of the machine fixes the mechanical duty and with it the bend radius, the bending cycles and whether a chain rated cable is needed.

Chapter 1 / 06

What a Control System Cordset Is and How It Works

A cordset adds no electronics. It is a chain of copper: stranded conductors of 0.25 or 0.34 mm2, roughly 23 and 22 AWG, joined to gold plated copper alloy contacts that keep their contact resistance low and stable, pressed onto the pins of the device plug by the spring of the socket, and closed by a coupling nut. Current is limited by the heating of the smallest contact in that chain, which is why the IEC pages for both connector families rate them for up to 4 A per contact. The SICK guide adds that this capacity is usually tied to an ambient temperature of no more than 40 degrees Celsius (104 degrees Fahrenheit) at the connector.

Pin assignment follows the wire colors. On the A-coded layout the positive supply is pin 1, the 0 V return is pin 3 and the switching signal is pin 4; the wires are brown, blue and black, a second signal is white on pin 2, and the 5-pin M12 adds a gray center contact on pin 5. A 3-pin A-coded connector occupies pins 1, 3 and 4 and leaves pin 2 empty, which is why a 3-wire sensor can usually be plugged into a 4-pin or 5-pin port. A 2-wire device needs one pair only and is commonly wired to pins 1 and 3, and a 4-wire device uses the white conductor for its second output.

The output type of the sensor does not change the cordset. A PNP sensor sources current, so its black wire connects the positive supply to the input card. An NPN sensor sinks current, so its black wire connects the 0 V line. The cordset carries either one on the same pins, and what has to match is the input at the other end of the run. When an inductive sensor or a limit switch with an M12 port is exchanged on an existing machine, the cordset stays and the input module decides whether PNP or NPN is accepted; a photoelectric sensor with two outputs takes the white wire as well.

The number after the M is the outside diameter of the locking thread in millimeters, and the pitch is 1 mm on both sizes. The coupling nut on a cordset end turns freely while the thread on the device is fixed, so a male cordset end and a female cordset end can be screwed together, and two device sockets cannot. The seal works in two places. At the mating face an O-ring or a profile seal is compressed when the nut comes tight; the washdown cords of SICK use a dual action profile seal that the guide rates above a classic O-ring. At the cable entry the overmold closes the housing around the jacket.

The working parts are few. A plastic contact carrier holds and insulates the contacts and carries the keyway that gives the coding its shape. The housing and coupling nut are polyamide or metal: nickel plated brass where the housing must carry the cable shield, stainless steel where cleaning chemicals attack a plating. The seal is rubber. Inside the overmold each conductor ends on its contact, the shield braid is clamped to the housing where a shield is fitted, and the joint is filled with thermoplastic polyurethane, the material SICK names for overmolding. Beyond the overmold only the jacket restrains the conductors, and a tight bend there does the damage.

A cordset inherits the lowest of three ratings: its cable, its connector and the port it plugs into. The IEC detail specifications for the two connector families set the ceilings that every maker builds to, 250 V on M12 and 50 V AC or 60 V DC on M8 at up to 4 A per contact, and the codings keep differently keyed plugs from mating. In the usual arrangement an I/O module, a PLC or an industrial switch carries the female socket and the field device the male pins. So the cordset that arrives at a sensor ends in a female coupling nut, and a linking cord that enters the I/O socket ends in male pins.

Chapter 2 / 06

Control System Cordset Types and Structural Variants

The base type is the sensor and actuator cordset with an A-coded M8 or M12 end. SICK builds it with 3 or 4 pins on M8 and 3, 4, 5 or 8 pins on M12, as a connecting cable with one molded end and an open cable end, or as a linking cable with a male and a female end, including cords that change from M8 to M12 between the ends. Each end is straight or angled: a straight end lets many ports sit side by side, and a right angle end turns the cable through 90 degrees to save depth behind a device close to a wall or a robot arm. Versions with a status LED are limited to 24 V.

Signal cordsets end where data cordsets begin. A B-coded M12 with 5 pins belongs to fieldbus networks such as PROFIBUS. A D-coded M12 with 4 pins carries two wire pairs, which serve Fast Ethernet at 100 Mbit/s on Cat 5e cable, the speed of PROFINET and EtherNet/IP networks. An X-coded M12 with 8 pins carries four pairs, each in its own quadrant of a cross shaped shield, and reaches 10 Gbit/s on Cat 6A cable. Hybrid cords with an RJ45 plug on one end and an M12 plug on the other join the cabinet to the field. Helukabel lists them from 0.5 to 25 m (1.6 to 82 ft) with M12 on both ends.

Two families stand apart by their ends. The M23 cordset carries the larger multi-pin interface of servo drives and feedback devices: a rotary encoder or an absolute encoder needs more contacts than M12 can hold. One continuous-flex cable catalog lists M23 connection and linking cables for actuator and sensor distribution boxes. The valve connector cordset ends in a flanged plug that fits the square socket of a solenoid coil and carries two power contacts and a protective earth contact through the center screw. Splitters divide one port: a Y cord gives 2 female ends, a T cord gives 3, and the branch currents add up on the single male end. Valve banks are wired this way, one splitter feeding several solenoid valves.

The jacket decides what the cordset survives. PVC is the standard cable for clean interiors: self extinguishing and stable against acids and lyes, but notch sensitive and weak against abrasion. PUR has high tensile strength and resists cracking, notches and wear, which makes it the jacket for machining centers, coolant and drag chains; it also resists hydrolysis and microbes. Polypropylene is the washdown cable, resistant to the cleaning agents of the food industry and to lactic acid, and the only jacket SICK rates up to 105 degrees Celsius (221 degrees Fahrenheit). TPE appears in continuous-flex sensor cables. SICK's compatibility table shows that oil resistance is not general: PUR resists the three ASTM test oils but not diesel oil or gear oil SAE 90, and neither PVC nor PUR withstands acetone, benzene or toluene.

A shield is required where the cord runs as an antenna: beside the output cables of a variable frequency drive, around motor power leads, and on every Ethernet link. A shielded cordset has a braided shield bonded to a metal housing at the plug, and SICK recommends a wraparound 360 degree attachment; a plastic housing without a metal sleeve cannot terminate a shield at all. Shielded variants also carry lower voltage ratings in the SICK tables, 60 V on M12 and 30 V on M8 against 250 V and 60 V unshielded. In a quiet cabinet an unshielded plastic housing is enough and costs less. For moving parts, chain rated cables take a smaller radius and several million bending cycles, and robot tooling needs torsion resistant types.

The cordset is bounded by three neighbors that are sometimes bought instead. A bulkhead pass through connector is a feedthrough: it passes a circuit through a panel wall and is not a cable. A cable gland seals the entry of a control cable or a power cable that is cut, stripped and landed on a terminal block by hand; it closes the hole and relieves strain, and does nothing for the contacts. Control cable and drag chain cable are bulk cable by the meter. The control system cordset sits between the two: between a port on a PLC, a remote I/O module or a cable distribution cabinet at one end, and a device, a splitter or an open end at the other, with the joint made and tested at the factory.

Chapter 3 / 06

Control System Cordset Key Specification Parameters and Standards

A cordset datasheet is one block of electrical data, one of mechanical data and one of environmental data. The electrical block states the coding, the pin count, the rated voltage and the rated current. The mechanical block states nut material, contact plating, mating cycles, bend radius, tightening torque and conductor size. The environmental block states the degree of protection, the approvals, the jacket and the temperature range: for fixed installation the SICK guide gives -30 to +80 degrees Celsius (-22 to +176 degrees Fahrenheit) for PVC, -40 to +80 (-40 to +176 degrees Fahrenheit) for PUR and -40 to +105 (-40 to +221 degrees Fahrenheit) for polypropylene. Values differ by jacket and by maker; the datasheet of the part bought governs.

Two IEC standards cover the connectors themselves. The M12 plug with a screwed coupling nut is specified in IEC 61076-2-101: fixed connectors and free connectors, rewirable or not, with 2 to 17 ways, data at frequencies up to 100 MHz, and signal and power at up to 250 V and 4 A per contact; the current edition replaces its predecessor. The M8 plug is specified in IEC 61076-2-104, with screw or snap locking, 3 to 12 ways, up to 50 V AC or 60 V DC and 4 A. These figures are ceilings for the connector, not the rating of a finished cordset. The PUR cordsets of SICK carry them in full on M12 at 250 V, but its shielded 4-pin versions are rated 60 V on M12 and 30 V on M8.

Two more standards apply in part. IEC 60529 defines the IP Code for enclosures of electrical equipment; IP67 is dust tight and stands for temporary immersion in 1 m (3.3 ft) of water for 30 minutes, and the code belongs to a connection only while it is mated and tightened. IEC 60947-5-2 is the product standard for the proximity sensor family, the inductive sensor, the capacitive sensor, the ultrasonic sensor, the photoelectric sensor and the magnetic sensor that these cordsets feed, and its Annex D covers connector types; the cordset itself is not certified under it. The same SICK guide marks its cords IP65, IP66K and IP67 and, for the washdown range, IP69K, which it defines as protection against high pressure and steam cleaning.

SpecificationValue on the datasheetWhat it decides
Rated voltage, M8up to 50 V AC or 60 V DCLow voltage sensor supply only
Rated voltage, M12up to 250 VSensor supplies and actuator signals
Rated current per contactup to 4 ASum of all devices on one port
Contacts, M8 and M123 to 12 and 2 to 17Wires one end can carry
Conductor cross-section0.25 or 0.34 mm2Volt drop on a long run
Degree of protectionIP65, IP67, IP68 or IP69KDust, splash, immersion or washdown; valid only mated and tightened
Temperature, PVC jacket-30 to +80 degrees Celsius (-22 to +176 degrees Fahrenheit)Freezing or hot zones are outside it
Temperature, PUR jacket-40 to +80 degrees Celsius (-40 to +176 degrees Fahrenheit)Cold stores and coolant flooded machines
Temperature, polypropylene jacket-40 to +105 degrees Celsius (-40 to +221 degrees Fahrenheit)Hot washdown zones
Tightening torque0.4 Nm (0.30 lbf ft) on M8, 0.6 Nm (0.44 lbf ft) on M12Seats the seal without crushing it
Bend radius5 x diameter fixed, 10 x flexingSpace behind every connector
Drag chain usemore than 5 million bending cyclesEntry into an energy chain
Mating cyclescommonly 100 or moreHow often a connection may open
Standard length1 to 20 m (3.3 to 65.6 ft) on M8, 1.5 to 25 m (4.9 to 82 ft) on M12Route length plus a service loop
Chapter 4 / 06

Control System Cordset Selection and Duty Calculations

Selection runs in a fixed order, because each step narrows the next. The port on the device fixes the connector family and coding, the wiring drawing fixes the pin count, and only then do jacket, shield, degree of protection, ends and length come up for decision. The calculations that follow check the chosen cord against the duty.

The first check is made at the device, not in a catalog. The thread size and coding of the port are read off the device drawing, because the keyway of a D-coded plug will not enter an A-coded socket and an X-coded plug fits nothing else. The pin count follows from the device: 3 pins for a 3-wire sensor, 4 or 5 pins for a second output or an IO-Link device, 4 pins for Fast Ethernet and 8 for Gigabit Ethernet. The gender follows from the usual arrangement: the end that arrives at a sensor is female, the end that enters an I/O socket is male. The wiring drawing states which pin carries supply, return and signal.

Current is checked as a sum. One I/O port feeds one device through a plain cord, but through a splitter it feeds two or three, and the currents add on the common end. The sum must stay under the 4 A per contact of the connector and under the rating of the thinnest conductor, with no more than 40 degrees Celsius (104 degrees Fahrenheit) at the connector. Volt drop is checked on long runs: it is twice the length of the cord times the current times the resistance of one conductor per meter, and it is largest on the 0.25 mm2 conductor and on the return that carries the sum of several devices.

Bend radius converts into space. A fixed cord is commonly given 5 times its cable diameter, the figure the SICK guide prints, and a cord that flexes 10 times, so the first clamp or guide must sit far enough behind the overmold to allow that curve. A chain rated cable may run at 5 times its diameter, and one continuous-flex family at 4 times. For an energy chain the machine figures are set against the typical ranges in the SICK guide: travel up to 50 m (164 ft), speed up to 300 m/min (984 ft/min) and acceleration up to 30 m/s2 (98 ft/s2). The PUR sensor cords that SICK marks as suitable for drag chains are credited with over 5 million bending cycles.

Temperature is checked against the place, not the plant. A cord on a weld fixture sees heat that a PVC jacket does not survive; a cord through the door of a freezer needs the -40 degrees Celsius (-40 degrees Fahrenheit) limit of PUR or the polypropylene washdown type. A jacket allowed 85 degrees Celsius (185 degrees Fahrenheit) at the overmold head may still be limited by the device port, which is why the head figure is printed separately in the SICK tables. The degree of protection follows the zone: IP67 for most factories, IP69K where high pressure cleaning hits the connection, and it holds only while the pair is mated and tightened to torque.

The last step is commercial. A standard coding and pin count can be sourced from more than one maker, because connectors with the same coding and pin count mate across brands, and one M12 family covers sensors, Ethernet and power. The points that break interchangeability are the jacket, the length, the approvals and the chemical tests, which differ by maker and must be written into the order. Where the length is unknown until commissioning, field wireable connectors and bulk cable give an exact length and a repair that needs no soldering; where the wiring is repeated by the hundred, factory molded cords give the same quality on every run.

DecisionCondition on the machineWhat to state in the order
Connector family and codingPort on the device: A-coded for sensors and actuators, D or X-coded for Ethernet, B-coded for PROFIBUSThread, coding and gender of each end
Pin count and assignment3 pins for a 3-wire device, 4 or 5 for a second output or IO-Link, 8 for Gigabit EthernetPin assignment and wire colors
Jacket materialPVC indoors, PUR for oil and coolant, polypropylene or TPE for cleaning agentsJacket and the chemical test for the agents used
ShieldNear drives and motors, and on every Ethernet linkShielded cable, metal housing, 360 degree termination
Degree of protectionIP67 for most factories, IP69K for washdown zonesRating, nut material, mated and tightened
Ends and orientationStraight where ports sit side by side, right angle where depth is shortStraight or angled end at each end
Mechanical dutyFixed, flexing, drag chain or robot useBend radius, bending cycles, torsion rating
Current and lengthSum of all devices on one port; route length plus a service loopConductor cross-section and length
Approvals and plant rulesUL listing, food contact materials, silicone free paint shopsCertificates and the cleaning agents tested
Chapter 5 / 06

Control System Cordset Installation, Maintenance, and Typical Failure Modes

Most cordset failures are made during installation and show up months later as an intermittent signal. The paragraphs below keep three paths closed: the bend that breaks a conductor behind the overmold, the nut that is not tight or is too tight, and the shield that is left unconnected.

Routing begins at the overmold. The first guide or clamp is placed so that the cable leaves the connector in a straight line and only then begins its curve, because a bend imposed right at the exit is the commonest cause of a conductor break at that point. Each cord is clamped close to its connector so that a pull on the cable reaches the clamp. Where the run shares a tray or a duct with power cables the cords are kept apart from them, commonly by a metal divider or by a gap of about 200 mm (8 in), and crossings are made at right angles.

Tightening is a torque operation. The M8 nut is brought to 0.4 Nm (0.30 lbf ft) and the M12 nut to 0.6 Nm (0.44 lbf ft) with a torque wrench that clicks at the set value. The washdown M12 cordsets of SICK need the same 0.6 Nm to engage their vibration interlock, which holds against shocks up to 50 g. A nut left loose lets cleaning fluid pass between nut and O-ring; a nut forced past the stop is watertight for a while and destroys the O-ring. The shield is earthed at the housing: the braid is bonded all round to the metal body of the plug, which bears on the metal port of the device and so on the bonded chassis.

Field wireable connectors are assembled on site when the exact length is unknown or a cord has been cut. The stripped conductors are landed on screw terminals, or the connector uses insulation displacement or pierce contacts that cut through the insulation. The cable diameter has to be inside the range the connector accepts; outside it the IP67 rating is lost. SICK rates its field wireable M8 and M12 connectors at IP65, IP67, IP68 or IP69K, the highest figure applying to housings that are screwed together, and for -40 to +85 degrees Celsius (-40 to +185 degrees Fahrenheit) or -25 to +90 (-13 to +194 degrees Fahrenheit). A repaired joint is marked so that it is inspected first.

Cleaning agents decide the life of a cordset in a washdown zone. The compatibility table of SICK rates PVC, PUR and polypropylene against named chemicals and states that the figures apply to unpressurized storage at room temperature. Acetone, benzene and toluene attack all three; weak acids and alkalis such as 10% acetic acid, 10% hydrochloric acid and 10% sodium hydroxide leave PVC and PUR largely intact; lactic acid, the agent that matters in dairies, is fully resisted only by polypropylene. The guide names five cleaning agents that its washdown cords were tested against and asks for any other agent to be tested before use. Warm humid service brings a second attack: microbes and hydrolysis discolor the jacket first and then crack its surface.

Troubleshooting follows the signal. A device that drops out intermittently is checked by flexing the cord behind each overmold and by wobbling the nut while the input is watched; a change with movement locates a broken conductor or a loose contact. A reading that is present but shifted points to moisture in the connector, which shows as green or black deposits on the contacts. Continuity is proved pin by pin with a meter: pin 1 to the positive rail, pin 3 to 0 V and pin 4 to the input, at both ends of a linking cord. A cordset is not repaired by taping or by soldering in a damp zone; it is replaced.

Failure or checkHow it shows and whyAction
Overmold crackingCracks behind the overmold after tight bends or long warm humid service; microbes first discolor, then crack the jacketReplace the cordset and reroute to the bend radius
Moisture ingressCorroded contacts from a nut left loose or an O-ring crushed by over-tighteningTighten to 0.4 Nm (0.30 lbf ft) on M8 and 0.6 Nm (0.44 lbf ft) on M12; replace the cord
Contact corrosionGreen or black deposits and rising contact resistance in washers and coolantsFit washdown rated cords with stainless steel nuts
Vibration looseningIntermittent signal on a vibrating machine; the nut has backed offRe-torque; change to a type with a vibration interlock
Conductor break at the cable exitSignal changes when the cord is flexed just behind the overmoldClamp for strain relief; replace the cord
Jacket attack by chemicalsSticky, swollen or cracked jacket where oils or solvents touch itCheck the agent against the maker's table; change the jacket
Wrong pin assignmentA device that stays silent, or a supply that trips, after a cord is changedProve pins 1, 3 and 4 with a meter against the device drawing
Drag chain wearAbrasion where cords rub in the chain or at the bend pointKeep clearance in the chain; use chain rated cords at 5 x diameter
Chapter 6 / 06

Control System Cordset Industry Applications and Procurement Checks

Machine building takes the largest share. Every machining center wires its inductive sensor, the pressure sensor on its pump unit, the flow sensor on its coolant line and the temperature sensor on its spindle with A-coded cords, in PUR because cutting oil and coolant attack other jackets, and into energy chains on the moving slides. Handling systems and high bay warehouses run the same cords in a cable drag chain for travel of many meters, with chain rated types where the bending cycles run into millions. Robot tooling adds torsion: an articulated robot twists the dress pack on its wrist at every cycle, so robot cords are built to take torsion as well as bending.

Food, beverage and pharmaceutical plants buy the washdown cordset. Cleaning there is high pressure and hot, up to 100 bar (1,450 psi) at 80 degrees Celsius (176 degrees Fahrenheit) in the IP69K test that the SICK guide describes, and the cords are hosed with acid and alkaline cleaners after every shift. The cords for these zones have stainless steel coupling nuts, a dual action profile seal, a hygienic shape without gaps where soil can lodge, polypropylene or PVC jackets overmolded with PUR, and materials accepted for food contact. Dairies add lactic acid to the list, which rules out PVC, and a level switch in a wash tank takes the washdown type as well.

Other industries add their own rules. Automotive paint shops specify cords that are silicone free and free of paint wetting impairment substances, because silicone carried on a cable from another hall causes craters in the paint. Welding lines use radiation cross-linked PVC and PUR jackets that resist welding sparks. Ethernet cordsets with D and X coded ends serve machine vision, motion control and the plant network in all of these industries. Renewable energy, marine and transport installations use the same families, with stainless steel housings where the air is corrosive. Where a displacement sensor has to be swapped for calibration, the molded connector turns a rewiring job into a plug change.

A purchase order for a control system cordset has to state nine things. The connector family and coding of each end; the pin count and the pin assignment with wire colors; the gender and orientation of each end; the jacket material and the chemical or cleaning agents it must resist; whether the cord is shielded and how the shield is terminated; the degree of protection and whether the IP69K washdown test applies; the rated voltage and current, the conductor cross-section and the length; the mechanical duty, fixed, flexing, drag chain or torsion; and the approvals, such as UL listing and food contact materials. The buyer also asks for the torque, the bend radius, the mating cycles and the chemical resistance table, and for a sample tested against the agent that will actually be used. Lead time is driven by standard lengths and codings against cut lengths, special jackets and molded Y or T splitters, which are made to order.

FAQ

How does a control system cordset work?

It is a passive copper path in a sealed housing. Stranded conductors, usually 0.25 or 0.34 mm2, are joined at the factory to gold plated copper alloy contacts, which are pressed onto the pins or sockets of the device plug and locked by a screwed coupling nut. On the A-coded layout the positive supply is pin 1, the 0 V return is pin 3 and the signal is pin 4, carried by brown, blue and black wires. An O-ring seals the mating face and the overmold closes the cable entry, so the connection is tight once it is torqued. IEC 61076-2-101 allows up to 250 V and 4 A per contact on M12.

What types of control system cordsets are there?

They are sorted by the connector on the end. M8 and M12 A-coded cordsets serve sensors, actuators and other 3-wire or 4-wire devices, with 3, 4, 5 or 8 contacts. M12 B-coded cords serve fieldbus networks such as PROFIBUS, D-coded cords carry Fast Ethernet at 100 Mbit/s and X-coded cords reach 10 Gbit/s. M23 cordsets connect drives and encoders, valve connector cordsets plug onto solenoid coils, and hybrid cords join an RJ45 plug to an M12 plug. Ends are straight or right angle, linking cords have a male and a female end, and Y and T splitters divide one port into two or three.

Which specifications matter most on a control system cordset?

The rated voltage first: up to 50 V AC or 60 V DC on M8 and up to 250 V on M12, lower on shielded and LED versions. The rated current comes next, up to 4 A per contact at 40 degrees Celsius (104 degrees Fahrenheit) ambient or less, which matters on splitters. Then the degree of protection, IP67 for most plants and IP69K for washdown, valid only when mated and tightened. The jacket sets the temperature range, -40 to +80 degrees Celsius (-40 to +176 degrees Fahrenheit) for PUR. The tightening torque, 0.4 Nm (0.30 lbf ft) on M8 and 0.6 Nm (0.44 lbf ft) on M12, belongs on the drawing.

How do I choose a control system cordset?

Start at the device port, which fixes the thread and the coding; the wiring drawing fixes the pin count and gender. Choose the jacket next: PVC for dry interiors, PUR for oil, coolant and abrasion, polypropylene or TPE where cleaning agents are sprayed. Choose a shielded cord with a metal housing next to drives and motors and on every Ethernet link, and a plain plastic housing in a quiet cabinet. Match the degree of protection to the zone, IP67 or IP69K. Set the length and the mechanical duty last: a fixed installation needs 5 times the cable diameter in bend radius, a flexing cord 10 times, and an energy chain a chain rated cable.

How do I install and maintain a control system cordset?

Route the cable straight out of the overmold before the first bend, clamp it so that no pull reaches the connector, and keep it away from power cables. Hand start the coupling nut and tighten to 0.4 Nm (0.30 lbf ft) on M8 and 0.6 Nm (0.44 lbf ft) on M12 with a torque wrench; a loose nut leaks and an over-tightened nut destroys the O-ring. In maintenance, look for cracked overmolds, corroded contacts and a nut that has backed off, flex the cord behind each overmold to find a broken conductor, and replace rather than repair a cordset in a wet zone.

What drives the cost and lead time of a control system cordset?

Standard codings, standard pin counts and stock lengths are made in large numbers and cost least; cut lengths, special jackets, shielded versions and molded Y or T splitters are made to order and take longer. The connector metal adds cost: nickel plated brass housings for shielded cords and stainless steel coupling nuts for washdown zones cost more than polyamide. Approvals such as UL listing and food contact compliance, and tests against named cleaning agents, add cost that a food plant cannot avoid. Continuous-flex and torsion rated cables cost more than fixed installation cords. A field wireable connector with bulk cable is cheaper when lengths are unknown until commissioning or when cords must be repaired on site.

Which standards and safety points apply to a control system cordset?

The connectors are covered by IEC 61076-2-101 for M12 and IEC 61076-2-104 for M8, which set the dimensions, the codings and the ceilings of 250 V and 4 A on M12 and 50 V AC or 60 V DC and 4 A on M8. Degrees of protection are classified by IEC 60529. IEC 60947-5-2 is the product standard for the proximity sensors these cords feed and applies to the cordset only through its connector types. On safety, a cordset is only as good as its rating: M8 stays on low voltage, the degree of protection holds only on a mated and tight connection, and a damaged cord in a washdown zone is isolated before it is touched.

Sources

  1. SICK: M8 and M12 connectivity for industrial applications (guide of 2018)
  2. IEC webstore page for the M12 connector standard
  3. IEC webstore page for the M8 connector standard
  4. IEC webstore page for the IP Code standard
  5. Helukabel: M12 connector guide, coding, pinout and selection
  6. Igus: chainflex catalogue for continuous flex cable
Ask SpecForge AI