Earth Leakage Circuit Breaker

An earth leakage circuit breaker (ELCB) is a mechanical switching device that opens its contacts when current leaking to earth reaches a set value. Two devices carry the name. The voltage-operated ELCB, now obsolete, watched the potential of the earthing conductor against a reference electrode. The current-operated device, the residual current device (RCD), compares the currents in the live conductors of a circuit with a core-balance transformer and trips when they no longer sum to zero. Installed in the distribution boards of plants and buildings, without overcurrent protection as a residual current circuit breaker (RCCB) or with it as an RCBO, it protects people from electric shock and wiring from the overheating an earth fault causes.

Specifying one is a matter of five decisions. The residual operating current decides what the device protects: 30 mA for people, 300 mA against fire. The waveform type, AC, A, F or B, decides whether it still sees the fault current the load produces. The time delay, none or Type S, decides which of two devices in series trips. The earthing system, TN or TT, decides the loop check the installation must pass. The back-up device decides whether its contacts survive a short circuit. The device bought today is the current-operated one, and it is the one these five decisions are made for; the voltage-operated type survives only as the origin of the name.

Close-up of a distribution board with a four pole residual current device with a black toggle and test button, mounted beside three miniature circuit breakers.

Photo: Kirschblut at German Wikipedia, public domain, via Wikimedia Commons

Five things decide an earth leakage circuit breaker purchase. First the residual operating current, because 30 mA protects people and 300 mA protects against fire. Second the waveform type, since a device blind to the direct current a drive leaks gives no protection. Third the time delay, which settles which device trips when two sit in series. Fourth the earthing system and the earth fault loop, because the rating multiplied by the loop impedance must stay below 50 V. Fifth the back-up protection, since a device without overcurrent elements needs a fuse or breaker ahead of it. Get these right and the board stays quiet.

Chapter 1 / 06

What an Earth Leakage Circuit Breaker Is and How It Works

The device the market still calls an earth leakage circuit breaker is defined in its product standards as a mechanical switching device that makes, carries and breaks current under normal service conditions and causes its contacts to open when the residual current attains a given value. Residual current is what is left when the currents in the outgoing and the returning conductors of one circuit are added. A fault to earth, damaged insulation, or a person touching a live part takes current out of the circuit along a path that bypasses the returning conductor, and that imbalance is the signal. The device answers within tens of milliseconds, fast enough to keep the current through a human body below the level that can start ventricular fibrillation.

The sensor is a summation current transformer, in practice a ring-shaped core of permalloy or of a newer nanocrystalline material, with every live conductor of the protected circuit passing once through its window. In a healthy circuit the instantaneous currents sum to zero, their magnetic fluxes cancel in the core, and the output winding delivers nothing. Once part of the current returns by earth, the ampere-turns no longer balance, flux appears in the core, and the secondary winding delivers a current proportional to the missing current. Two things follow. The core material sets the smallest current the device can see, and in a separate transformer the live conductors must pass symmetric through the window, because asymmetry adds to unwanted tripping by surge short-circuit currents.

The secondary signal goes to the trip element. A voltage-independent design, the common form in Europe, releases a polarized relay whose armature a permanent magnet holds against a spring; the secondary current weakens the holding flux and the spring releases the mechanism, on a tripping input of roughly 50 to 120 microVA. A voltage-dependent design passes the signal through an electronic amplifier that drives a trip solenoid with about 0.1 to 1 W, a simpler mechanism that needs the supply alive. In both, the trip releases a mechanism that opens every pole. In normal switching the neutral pole closes before the line poles and opens after them, and the handle cannot hold the contacts closed against a trip. The device stays off until it is reset by hand.

Two limits follow from the principle. The device sees only current that leaves the circuit. A short circuit or an overload between two live conductors, or a person touching line and neutral together, sends no current outside the conductors and is invisible to it, which is why an overcurrent device must sit ahead of it or inside it. A direct component in the residual current can also lower the sensitivity of a simple device or block its tripping altogether. Speed is set by the delay. A voltage-independent unit trips in 20 to 120 ms at its rated current. A delayed unit waits first for 10 ms or 40 ms, so that a switching surge does not trip it and a downstream device can clear a fault first.

Because the mechanism may stand for years without a fault, every device carries its own test circuit: a button in series with a resistor that drives a current around the outside of the transformer, so that the sensor sees a residual current higher than its rating. Pressing it exercises core, relay, mechanism and contacts together, and the device must trip. The resistor is chosen for the voltage, and the circuit has to work down to 0.8 of the rated voltage. The button proves only that the device trips: it measures neither the trip time nor the trip current and does not test the earthing conductor. It should also be pressed briefly: held for seconds on a miswired circuit, it burns its own resistor.

The voltage-operated ELCB that gave the product its name worked on a different quantity. A second terminal connected it to a remote reference earth electrode, and it tripped when the potential of the bonded metalwork of the installation rose above a set limit relative to that electrode. It protected only metalwork wired to it, and it could not see current leaving a live conductor to ground by another path, a person standing on the soil included. A broken earth wire, or a second connection to earth anywhere on the system, could disable it, and potential gradients from a nearby lightning strike or a neighboring earth electrode could trip it. The current-operated device needs no reference electrode and no third wire, senses every earth fault downstream of it and every direct contact, and replaced it.

Chapter 2 / 06

Earth Leakage Circuit Breaker Types and Structural Variants

The family is divided first by how the breaking is arranged. The residual current circuit breaker (RCCB) has no overcurrent elements and is the form met most often; its product standard covers rated currents up to 125 A at voltages up to 440 V AC. The RCBO adds a miniature circuit breaker in the same case and protects against overload and short circuit as well as earth fault, with rated short-circuit capacities up to 25,000 A within the same limits. For larger feeds a power circuit breaker takes an integral residual current release and becomes a CBR, and a modular residual current device is a transformer with a separate relay that trips a circuit breaker, a switch or a contactor. Both belong to the industrial circuit-breaker standard and are set and operated by skilled persons.

The second division is by the waveform of residual current the device still recognises, the choice that most often goes wrong. A Type AC device is built for sinusoidal alternating residual current only; a pulsating direct component can lower its sensitivity or block tripping. Type A adds pulsating direct current and a small smooth direct component of up to 6 mA. Type F, a variant of Type A, also answers the composite currents that arise when a frequency inverter sits between phase and neutral or between phase and the earthed middle conductor. Type B answers alternating residual current up to 1,000 Hz, pulsating direct and smooth direct current, and is the type for drives, photovoltaic plants and other equipment with power semiconductor elements.

The third division is by time. A general use device trips without intended delay and must open within 300 ms at its rated residual current. A selective device, marked with an S in a square frame, holds for at least 40 ms before it trips, so that the device nearer the fault clears first; the delay comes from a capacitor charged from the secondary winding that releases its energy to the trip winding only when the residual current persists. Between the two sit short-delayed devices, marked G by some makers, with a non-operation time of at least 10 ms that rides through switching surges; the IEC product standards do not define this middle class. Selectivity between two devices in series needs more than delay: the upstream S device must also carry a rating at least 3 times that of the downstream device.

The mechanical variants follow from the circuit. A single-phase circuit takes a 2-pole device that opens and closes line and neutral; a three-phase circuit takes a 4-pole device, which may serve a circuit that has no neutral conductor, provided the conductors land on the terminals that keep the test circuit working. Most devices are built for 230/400 V systems, with 110 V versions for the North American market. The standard operating condition is an ambient temperature from -5 to +40 degrees Celsius; versions marked for -25 degrees Celsius serve outdoor distribution boxes and building sites. A device that depends on a separate auxiliary supply is admitted only where qualified personnel operate the installation.

The boundaries against neighboring products are short. An earth leakage circuit breaker is not an overcurrent device. A circuit breaker clears the short circuit, and an air circuit breaker of the large frames, up to 6,300 A, can take an earth fault release as well; this device clears earth faults only unless it is the RCBO or CBR form. It is not a test instrument: an earth ground tester measures the earth electrode, an insulation resistance tester finds the damaged circuit, and a clamp meter around all live conductors reads the standing leakage. It is not a surge protector, which limits the overvoltage a lightning stroke induces, although the two must be chosen together. It sits in a distribution cabinet between the overcurrent devices and the final circuits.

Chapter 3 / 06

Key Specification Parameters and Standards

Six parameters describe an earth leakage circuit breaker on a datasheet. The rated residual operating current, 10, 30, 100, 300 or 500 mA, or 1 A, is the value at which it must trip and the one that sets what it protects, called the rating below. The break times state how fast it must open at 1, 2 and 5 times that current. The waveform type, AC, A, F or B, and the delay class, general use or S, complete the residual current behavior. The rated current is the load current its contacts carry, 16 to 100 A in the usual catalog and up to 125 A within the product standard. The poles and the rated voltage fix the circuit, and the rated breaking capacity fixes the back-up fuse or breaker the device needs.

Three lines need care. The breaking capacity of a device without overcurrent elements is small, about 500 A up to 40 A of rated current and 1,000 A at 100 A, so a datasheet that prints 10 kA is quoting a conditional short-circuit rating valid only with the upstream fuse named beside it. A rating of 30 mA says nothing about the waveform: on a circuit feeding a variable frequency drive the same 30 mA device in Type AC may hold closed on a fault that Type B clears. And the rated current is not the setting of the breaker ahead of it. A miniature circuit breaker to IEC 60898-1 is allowed to carry 1.13 times its nominal current without tripping, so the fuse or breaker that protects the contacts is chosen one step below the device rating, or the RCBO is used instead.

The standards divide by device. IEC 61008-1 covers residual current operated circuit-breakers without integral overcurrent protection for household and similar uses, rated up to 440 V AC and 125 A. IEC 61009-1 covers the RCBO within the same limits and with short-circuit capacities up to 25,000 A. IEC 62423 adds the requirements for Type F and Type B devices and is used only together with the two. IEC 60898-1 covers the overcurrent circuit-breaker for household and similar installations on which the RCBO builds. Industrial circuit-breakers with an integral residual current release, and modular devices without their own contacts, fall under IEC 60947-2. Installation rules then state where the device is required, the type test it must pass and the earth fault loop it must satisfy.

ParameterTypical valueWhat it decides
Rated residual operating current10, 30, 100, 300, 500 mA, 1 AProtection level: 30 mA for people, 300 mA against fire
Trip band on residual currentTrips between 50 and 100 percent of the ratingBudget for the standing leakage of the circuit
Break time, general useup to 300 ms at 1x, 150 ms at 2x, 40 ms at 5xSpeed of disconnection
Break time, Type S130 to 500 ms at 1x, 60 to 200 ms at 2x, 50 to 150 ms at 5xDiscrimination with the downstream devices
Rated current16 to 100 A usual, 125 A limitLoad current the contacts carry
Rated voltage230/400 V, 110 V versions, 440 V AC limitSupply system; 2-pole or 4-pole frame
Breaking capacity, RCCB500 A to 1,000 ABack-up fuse or breaker required ahead of it
Conditional short-circuit rating10 kA with the named fuseWithstand at the fault level of the board
Surge current withstand, 8/20 microsecond wave250 A general use, 3 kA delayed, 5 kA Type SRide-through beside a surge protector
Waveform typeAC, A, F, BLoads with electronic power conversion
Non-operation time10 ms type G, 40 ms Type SSelectivity and surge immunity
Selectivity ratio3 x minimumOnly the downstream device trips
Ambient temperature range-25 to +40 degrees CelsiusOutdoor and building-site boards
Chapter 4 / 06

Selection and Duty Calculations

Selection names the protection the circuit needs, checks that the earth fault loop lets the chosen rating work, and then matches the device to its load and to the devices around it. The numbers below are the checks an engineer runs before the board is ordered.

The first step is to name the protection. Three levels are in use. Additional protection of people is given by a rating of 30 mA or lower. Protection by automatic disconnection in case of a fault takes a rating set by the conditions at the place of installation, and a TT system with a high earth resistance pushes it upward. Protection against fire from leakage current asks for 300 mA or lower. Wiring rules fix the first and the third in many cases: socket outlet circuits take a device of 30 mA or lower, and a cable that supplies temporary structures takes 300 mA or lower at its origin, with a delay so that it does not trip together with the devices of the final circuits.

The second step is the earth fault loop check. The wiring rule is that the rated residual operating current in amperes multiplied by the earth fault loop impedance in ohms must not exceed 50 V, the touch voltage a fault may leave on exposed metalwork until the device opens. The arithmetic decides the rating. A 30 mA device allows about 1,670 ohms, a 300 mA device about 167 ohms and a 500 mA device about 100 ohms. On a TT system the earth electrode is the largest part of the loop. An electrode of 200 ohms, measured with an earth ground tester, gives 60 V at 300 mA and fails, and gives 20 V at 100 mA and passes.

The third step is the earthing system. In a TN system the neutral point of the supply is earthed and the exposed metalwork is bonded to it, so a fault produces a large current that an overcurrent device may clear; the loop condition for the residual device becomes the supply voltage divided by the rating, about 7,670 ohms at 230 V and 30 mA, which is met with a wide margin. In a TT system the metalwork has its own earth electrode, a fault can leave 150 to 200 V on it, and the earth leakage circuit breaker is the device that clears the fault. Because the whole protection then rests on one mechanism, two are placed in series: a main device and a 30 mA device on the final circuits.

None of this works on a TN-C supply. There the neutral and the protective conductor are one shared PEN conductor, so the fault current returns inside the conductor the device monitors and no residual current appears. The use of the device in a TN-C network is prohibited: it cannot trip. The PEN conductor must be split into separate neutral and protective conductors upstream of the device, at the main board, which converts the network to TN-C-S, and the two conductors must never be rejoined downstream of it. The earthing arrangement also depends on the source. A plant fed by its own dry-type transformer, by busway trunking or by a standby diesel generator on changeover needs the neutral-to-earth connection of each source confirmed, because the conditions for automatic disconnection follow from the earthing arrangement of whichever source is feeding the board.

The fourth step matches the device to its load and to its neighbors. Every load leaks a little: a computer with its switching power supply 1 to 2 mA, and many such loads on one device push the standing residual current toward 15 mA, the level at which a 30 mA device may trip. Circuits are therefore split, with each neutral on its own device, rather than raised to a less sensitive rating. The waveform type follows the power electronics on the circuit, a servo drive and a variable frequency drive being the usual sources of direct residual current. The back-up follows the form: an RCCB needs a fuse or miniature circuit breaker ahead of it, sized one step below its rated current so that the device withstands a fault on its load side, while an RCBO carries that protection inside.

DecisionCondition in the installationChoice
People protectionSocket outlets, portable and handheld equipment30 mA, general use
Fire protectionOrigin of the installation; cable feeding temporary structures300 mA or lower, Type S
TT system with a 200 ohm electrodeRating x loop impedance above 50 V at 300 mA100 mA or lower
TN-C supplyNeutral and protective conductor not yet splitSplit the PEN conductor upstream of the device
Drive or inverter on the circuitSmooth or composite residual current expectedType F or Type B
Two devices in seriesOnly the device near the fault may tripType S upstream, rating at least 3 x the downstream rating
Surge protector on the same boardSwitching surges and lightning impulsesShort delay or Type S, 3 kA or 5 kA withstand
Outdoor or building-site boardAmbient below -5 degrees CelsiusVersion marked -25 degrees Celsius
Chapter 5 / 06

Installation, Maintenance, and Typical Failure Modes

Most unwanted trips, and most devices that fail to trip when tested, trace back to the wiring around the transformer or to a test that was never done. The rules are few. They are checked before the board is energised and at set intervals afterwards.

Installation begins with what passes through the transformer. Every live conductor of the protected circuit, the line conductors and the neutral, passes once through the window in the same direction. The protective conductor, PE or PEN, never does, because the fault current has to find its way back outside the device. Downstream of the device the neutral and the protective conductor stay separate, each circuit keeps its own neutral on its own device, and no conductor protected by one device is shared with another: a socket wired from the wrong circuit or a neutral borrowed from the next trips both. In a crowded distribution cabinet the neutral bar sits close to the line terminals of the devices, so every conductor is identified before the board is energised.

Testing happens twice: at commissioning with an instrument, and afterwards with the button. The commissioning test uses a residual current device tester connected on the load side, between the phase conductor of the protected circuit and its circuit protective conductor, with the load disconnected, so that the instrument draws a known current to earth and measures the time the device takes to open. A general purpose device must open in less than 300 ms at 100 percent of its rated current; a Type S device must open between 130 ms and 500 ms. The supply has to be on and at its rated voltage for this test and for the button, so the voltage at the input is checked first with a digital multimeter.

  1. Confirm that every live conductor passes through the device and that the protective conductor does not.
  2. With the device off, check with an insulation resistance tester that neutral and protective conductor downstream are separate.
  3. Press the test button at the rated voltage; the device must trip, then reset it.
  4. Connect the tester on the load side with the load off, and read the trip time at 100 percent of the rating.
  5. Repeat at 5 times the rating and confirm that the device holds at 50 percent.

Routine testing follows the intervals the maker prints. The common instruction is once a month with the button; types of enhanced reliability extend this to 6 months or a year. One schedule used in the industry is 6 months for boards in dry and dust-free rooms, 1 month for outdoor circuits and manufacturing premises, 6 months for delayed types and 1 year for digital types, with a test immediately after installation and after any modification. The climate test behind these intervals runs 28 days at 55 degrees Celsius and 95 percent humidity, after which the device must still trip at 1.25 times its rating. The interval is short because the mechanism is delicate: a voltage-independent trip works on roughly 50 to 120 microVA, and the button is the only warning that it still moves.

Nuisance tripping has a few causes and one method. Supply side: mains-borne disturbance, site machinery and lightning. Load side: a device of the wrong type or without selectivity, a crossed neutral on a split-load board, a neutral to earth fault, and standing leakage from surge protective devices, from too many items with filter circuits, from long mineral-insulated power cable, and from damp or from heating elements. The method is elimination. Unplug or switch off every appliance and reset. Switch the circuit breakers on one at a time until the device trips. Reconnect the appliances of that circuit one at a time. A trip that follows a thunderstorm points to a non-delayed device of 250 A surge withstand beside a surge protector, and a delayed type ends it.

SymptomMost likely causeAction
Trips as soon as one appliance startsNeutral and protective conductor joined downstream; the test resistor may be burntSeparate the conductors; replace the device if the button no longer trips
Trips when a circuit on another device is usedNeutral of that circuit returned to the wrong deviceRewire the neutral to its own device
Trips at switch-on of drives or filtersNon-delayed device reacting to the charging currentFit a short-delayed or Type S device
Trips with no fault in any applianceStanding leakage above half the ratingSplit the circuit over more devices
Trips during storms or switchingSurge withstand of 250 A exceededDelayed type with 3 kA or 5 kA withstand; check the surge protector
Does not trip at any test currentFailed mechanism, or a smooth direct residual current blinding a Type AC deviceReplace; use Type B where power electronics are present
Upstream device trips together with the downstream oneNo selectivity: no delay, or too small a ratio between the ratingsType S upstream with at least 3 times the rating
Contacts welded, device will not resetOvercurrent without back-up protectionCheck the back-up fuse or breaker; replace
Chapter 6 / 06

Industry Applications and Procurement Checks

The places that ask for the device are those where an earth fault current is too small to operate an overcurrent device in time, or where people can touch equipment that may become live. Wiring rules call for it on socket outlet circuits and on installations supplied from overhead lines, and a rating of 300 mA or lower protects against fire on agricultural and horticultural premises. In industry it appears in the distribution cabinet of a workshop, in the MCC cabinet that feeds motor drives, on the supply to machine tools, in the building-site power distribution box and in the cable distribution cabinet that feeds temporary structures. Boards that stand outside are specified with devices marked for -25 degrees Celsius, and the IP enclosure rating of their box is a separate line of the order.

Within a plant the device is one layer of a chain. Supply enters through an isolating switch or a load switch and the main overcurrent device and divides into final circuits; there the earth leakage device sits after the breakers and fuses for a group of circuits, or each circuit takes an RCBO. On a feed with power electronics the group device is Type B or F, and a variable frequency drive, an immersion heater or a piece of site machinery is given its own smaller device so that its leakage does not trip the others. Where a standby diesel generator can feed the board, the earthing arrangement is confirmed for both sources. A switch-disconnector ahead of the devices isolates the whole group for maintenance.

What separates one device from another of the same rating is the engineering inside the case, not the frame. A Type B device carries an extra evaluation circuit and a core that answers direct current; a delayed type adds the capacitor circuit that holds the trip back; a voltage-independent design needs a polarized relay held by a permanent magnet, while a voltage-dependent design uses an electronic amplifier and a trip solenoid. Surge withstand of 3 kA or 5 kA, a 4-pole frame and the 125 A frame are further lines that narrow the choice of models. A version marked -25 degrees Celsius, a special voltage or a type test certificate to IEC 61008-1 or IEC 61009-1 is therefore asked for when the board is ordered, and the device schedule is checked against the board schedule before either order is placed.

The purchase order for an earth leakage circuit breaker should state the form, RCCB without overcurrent protection or RCBO with it, the number of poles, the rated current, the rated voltage and the rated residual operating current, the waveform type, AC, A, F or B, and the delay class, general use or Type S. It should name the standard the device is type tested to, IEC 61008-1 or IEC 61009-1. It should name the back-up fuse or breaker and the conditional short-circuit rating valid with it, and the surge current withstand, 3 kA or 5 kA. The buyer should also ask for the ambient range, -25 degrees Celsius for outdoor boards, the trip times at 1 and 5 times the rating, and a completed test schedule. Two questions matter most: how much standing leakage the device carries without tripping, and which delay makes it selective with the devices already installed.

FAQ

How does an earth leakage circuit breaker work?

All live conductors of the protected circuit pass through a ring-shaped transformer core. In a healthy circuit their currents sum to zero and the core carries no flux. When current leaves to earth, the core is magnetised and a secondary winding delivers a signal. That signal releases a polarized relay, or is amplified to drive a trip solenoid, and the released spring opens every pole. A general use device opens within 300 ms at its rated current and within 40 ms at 5 times that current. It cannot see a fault between two live conductors, so it needs an overcurrent device ahead of it or inside it.

What is the difference between an ELCB, an RCD, an RCCB and an RCBO?

The four names describe two devices and two packages. The ELCB was first the voltage-operated breaker that watched the potential of the earthing conductor against a reference electrode; it is obsolete. The RCD, residual current device, is the current-operated successor and the general term for it. An RCCB is an RCD without overcurrent protection, the common board device that needs a fuse or breaker ahead of it. An RCBO is an RCD with a miniature circuit breaker in the same case, giving overload, short-circuit and earth fault protection from one unit.

Which residual current rating should I choose?

The rating is chosen by what the device must protect and by the earth fault loop. A rating of 30 mA or lower gives additional protection to people. A rating of 300 mA or lower protects wiring against fire from leakage current and is common at the origin of an installation. The loop check is that the rating in amperes multiplied by the earth fault loop impedance in ohms must not exceed 50 V: 30 mA allows about 1,670 ohms and 300 mA about 167 ohms. The standing leakage of the load must also stay below half the rating.

What are RCD types AC, A, F and B, and which one do I need?

The letters state which residual current waveforms the device still detects. Type AC answers sinusoidal alternating current only; a pulsating direct component can blind it. Type A also answers pulsating direct current and a small smooth direct current up to 6 mA. Type F, a variant of Type A, answers the composite currents produced by single-phase frequency inverters. Type B answers alternating current up to 1,000 Hz, pulsating direct and smooth direct current. Choose by the load: resistive, capacitive and inductive loads without electronic parts on Type AC, single-phase electronic equipment on Type A, and circuits with variable frequency drives or photovoltaic installations on Type F or Type B.

Why does my earth leakage circuit breaker keep tripping for no reason?

Trips without a fault have a few causes. The most frequent is a neutral and protective conductor joined downstream of the device. A neutral returned to the wrong device does the same. Standing leakage from many items with filter circuits or from long mineral-insulated cable can reach half the rating. A non-delayed device trips on switching surges and lightning unless it has a 3 kA or 5 kA surge withstand. Two devices in series trip together when the upstream one is not Type S or has less than 3 times the downstream rating. The method is elimination: disconnect everything and reset, then restore circuits and appliances one at a time.

How do I test an earth leakage circuit breaker, and how often?

Two tests are needed. The test button drives a current around the transformer through a built-in resistor and proves that the sensor, the relay and the mechanism still trip together; press it once a month, or every 6 months to a year for types of enhanced reliability, and always after installation and after any modification. A residual current device tester, connected on the load side between phase and the circuit protective conductor with the load disconnected, measures the actual trip time: less than 300 ms at the rated current for a general purpose device, and 130 ms to 500 ms for a Type S device.

Which standards apply to an earth leakage circuit breaker?

IEC 61008-1 covers residual current operated circuit-breakers without integral overcurrent protection, the RCCBs, and IEC 61009-1 covers those with it, the RCBOs; both are written for ratings up to 440 V AC and 125 A. IEC 62423 adds the requirements for Type F and Type B devices, and IEC 60947-2 covers industrial circuit-breakers with a residual current release. National wiring rules state where the device is required and the earth fault loop it must satisfy. A GFCI, ground fault circuit interrupter, is the North American name for the same current-operated principle; devices for that market come in 110 V versions.

Sources

  1. IEC: IEC 61008-1, residual current operated circuit-breakers without integral overcurrent protection (RCCBs), publication page
  2. IEC: IEC 61009-1, residual current operated circuit-breakers with integral overcurrent protection (RCBOs), publication page
  3. Eaton: Residual Current Devices, application guide BR019003EN (PDF)
  4. EMSD Hong Kong: Code of Practice for the Electricity (Wiring) Regulations, 2025 Edition (PDF)
  5. BEAMA: RCD Handbook, guide to the selection and application of residual current devices (PDF)
  6. IEC: IEC 62423, type F and type B residual current operated circuit-breakers, publication page