Air Circuit Breaker

An air circuit breaker (ACB) is a low-voltage power circuit breaker whose contacts part in air and whose arc is extinguished in a chamber of steel splitter plates. It is built for rated currents from 630 to 6300 A and for short-circuit levels from 42 to 200 kA in one catalog family, and it is the device a switchboard designer places where a whole installation can be isolated or lost at once: the main incomer below the transformer, the bus-coupler between two sections, and the largest outgoing feeders. Each pole carries main contacts for the continuous load and a separate arcing contact that takes the arc at every opening, and a spring-charged mechanism closes and trips all poles together.

The page is for the engineer who has to choose the breaker, set its trip unit, write the inquiry and keep the device in service for decades. The decision concentrates on a few numbers: rated current, ultimate and service breaking capacity, short-time withstand current and making capacity, each of which must exceed what the installation can impose at the point where the breaker sits. Rating ranges and accessory data are taken from the ABB catalog for one breaker family, mechanism and maintenance practice from an Eaton instruction booklet, and rating definitions from the Schneider Electric Electrical Installation Guide, with IEC, IEEE and UL product standards checked on the standards bodies' own pages.

A manufacturer's photograph of a white air circuit breaker seen from the front and right side: a front panel with an electronic trip unit and a small display, a red open button and a green close button, vent openings in the side plate, and a gloved hand turning the charging handle at the lower right.

Photo: АО Контактор, CC BY 3.0, via Wikimedia Commons

The buying decision concentrates on four ratings and one plan. The ratings are the frame current, the ultimate and service breaking capacities, the short-time withstand current and the making capacity; each has to exceed what the installation imposes at the real ambient temperature and at the service voltage. The plan is selectivity: whether the breaker holds a downstream fault for a set time so that only the faulted feeder trips, or clears on its own instantaneous element. The mounting, the accessories and the evidence asked from the maker follow from those choices.

Chapter 1 / 06

What an Air Circuit Breaker Is and How It Works

An air circuit breaker is a low-voltage switching and protective device, rated by IEC 60947-2 for circuits up to 1000 V AC or 1500 V DC. It closes a circuit to carry load, opens it on command, and opens by itself on an overload or a short circuit, the latter in a few tens of milliseconds. In a switchboard it is the main incomer below the transformer, the bus-coupler between two sections, or the feeder to a large load, and because it is suitable for isolation it is also where a section is made dead for work. That position explains its construction: it must interrupt the largest current the source can deliver without needing replacement.

Opening begins with a latch. Closed contacts are held by a linkage locked against a trip latch, and the springs that press the contacts together keep that linkage under load. A small rotation of the trip shaft frees the latch, the linkage collapses, and the contacts part under their own contact pressure, whatever the operator is doing. The mechanism is trip-free: the breaker can be tripped at any point of its closing stroke, so a held closing command cannot keep the contacts pressed onto a fault. The same trip shaft is turned by the manual trip button, by the opening release, by the undervoltage release, and by the actuator that the trip unit energizes when it detects an overcurrent.

The arc forms as soon as the tips separate, because the current cannot stop instantly. Air between the contacts breaks down into a conducting column of ionized gas and metal vapor that carries the current across the gap. Its heat is proportional to the current and its length to the voltage; the arc energy, arc voltage times current over the arcing time, is spent as heat in the interrupter and as erosion of the tips. In alternating current the arc has a natural chance to die at every current zero, which comes twice per cycle, 100 times a second at 50 Hz and 120 at 60 Hz. Extinction depends on the gap recovering dielectric strength faster than the voltage across it rises.

Interrupting in air means controlling where the arc burns. Each pole carries an arc chute fitted down over the arcing contacts so that the arc is confined inside it at every current. The chute holds a stack of vertical steel splitter plates with an inverted V notch, set between insulating spacers in an insulating jacket and vented to the atmosphere. The magnetic field of the arc current drives it upward off the tips and into the plates, which cut it into a series of short arcs. This is the de-ion principle: each partial arc adds its own voltage drop, so the total arc voltage rises and opposes the source, while the plates cool and stretch the arc until it dies at a current zero.

Two contact systems share each pole, and only one of them is meant to burn. The main contacts carry the continuous load as butt-type faces built from a row of spring-loaded fingers; their pressure rises under short-circuit current because the magnetic field pushes each finger toward the moving blade. Above them sit the arcing contacts, with tips of arc-resistant composition. They make first and break last, so the arc roots leave the main faces and burn on the arcing tips alone; their lead over the main contacts is fixed by the design. For that reason a power breaker is repaired by renewing its tips, where a molded-case breaker is usually discarded when its contacts wear.

Closing and opening come from a spring-charged stored-energy mechanism, so contact speed never depends on the operator. A geared motor turns a ratchet wheel through an oscillating pawl, winding the closing springs until the crank arms pass over dead center and a stop on the close cam holds them; one family quotes 7 to 8 s for the charge. A closing command energizes a release that frees the cam, and the springs drive the contacts closed, then stand discharged until the breaker opens. A hand lever charges the springs when the auxiliary supply is missing. An anti-pumping circuit permits one close operation per close command, so a held command cannot reclose the breaker onto a fault.

Chapter 2 / 06

Air Circuit Breaker Types and Structural Variants

The two mounting versions are fixed and drawout. A fixed breaker is bolted to the busbars through its terminals, needs the least space, and suits feeders where compactness matters more than rapid replacement. A drawout breaker has a moving part that runs on rails into a cradle, with isolating contacts that separate as it is withdrawn. It has four positions: remove; disconnect, where main and auxiliary contacts are both open; test, where the main contacts are open but the auxiliary plugs are made, so the breaker can be operated and its trip unit checked; and connect. Shutters close over the live isolating contacts as it leaves the connect position, and interlocks stop it being racked while closed or closed between positions.

Trip units mark the generations of the product. Older breakers carried thermal-magnetic trips: a bimetal element, working like a thermal relay, against overload and an instantaneous electromagnet against short circuit, with overload settings from 0.7 to 1.0 times the rating and short-circuit thresholds at 7 to 10 times it. Present units are electronic: sensors in each pole feed a microprocessor with long-time (L), short-time (S), instantaneous (I) and ground-fault (G) functions, and respond to true rms current, so the distorted current of a variable frequency drive is measured correctly. The unit is powered by the load current. Basic units are set on dip-switch blocks; measuring units add readings, communication and a data logger of waveforms around a trip.

A standard air circuit breaker lets the fault current rise to its peak and interrupts at a current zero, which lets it hold its short-time rating. The smallest frames also come in a current-limiting category A version that opens before the peak and trips without delay, and an integrally fused breaker adds a fuse in series with each pole to reach up to 200 kA in one North American line, with a blown-fuse indicator that trips all poles. A switch-disconnector keeps the contacts, arc chute and mechanism but drops the trip unit; it serves as a load switch with a defined isolating distance when open. Breakers have three or four poles, usually with the neutral at the full phase rating; versions for 1000 V AC and higher, and for DC, trade breaking capacity for insulation level.

Internal accessories are common to a whole family and are fitted from the front without opening the mechanism. The motor operator reloads the closing springs whenever they are discharged and power is present. An opening release, the shunt trip, and a closing release give remote control; they respond to a pulse of at least 100 ms and work within 70 to 110 percent and 85 to 110 percent of their rated voltage. An undervoltage release trips when its coil voltage collapses and permits closing only while energized; a time-delay version rides through voltage dips. Auxiliary contacts report open and closed position, a trip-signalling contact reports a protection trip, and key locks, padlocks and an operation counter complete the list.

The boundary against neighboring products follows from that construction. The generic circuit breaker page covers the whole class and the molded-case and miniature families; this page treats the air type alone, which stands above the molded-case breaker in current rating and in its declared short-time withstand. An isolating switch or a switch-disconnector makes and breaks current but clears no fault. Vacuum, oil and sulfur hexafluoride breakers interrupt in other media, at medium and high voltage. In the distribution chain it sits between a dry-type transformer or a power transformer upstream and, downstream, a distribution cabinet, a motor control center built as an MCC cabinet with a contactor and a motor protection relay in each motor circuit, or an uninterruptible power supply.

Chapter 3 / 06

Air Circuit Breaker Key Specifications and Standards

Ratings fall into two groups: those set by continuous service and those set by the short circuit. Rated operational voltage Ue is the voltage at which the breaker is designed to operate, 690 V on a standard IEC breaker and 600 V nominal on North American lines. Rated insulation voltage Ui, 1000 V on the same frames, is the value to which dielectric tests and creepage distances refer, and Ue must never exceed it. Rated impulse withstand voltage Uimp is the peak the insulation takes from a surge, 12 kV in the catalog quoted here. Rated current, written In or Iu, is the maximum a breaker carries indefinitely at the reference ambient of 40 degrees Celsius (104 F); the frame rating is the largest sensor that fits.

The short-circuit ratings decide whether the breaker survives a fault. Rated ultimate breaking capacity Icu is the highest prospective current it can interrupt once without damage. Rated service breaking capacity Ics is the current it can interrupt and still return to service, a percentage of Icu of 25, 50, 75 or 100 percent, with 100 percent common on air breakers. Rated short-time withstand current Icw is the current it carries, usually for 1 s, while a downstream device clears the fault, and rated making capacity Icm is the peak it can close onto, Icu times a factor k of 1.7 to 2.2 set by the power factor of the fault loop. Utilization category B marks a breaker with a short-time rating and a deliberate delay; category A covers all others.

Standards come from the product and from the assembly around it. IEC 60947-2 covers circuit-breakers for circuits up to 1000 V AC or 1500 V DC, and its current edition dropped the classification by interrupting medium. IEEE C37.13 and UL 1066 cover enclosed low-voltage power circuit breakers in North America, and UL 1066 excludes molded-case breakers. IEC 61439-2 covers the power switchgear assembly that holds the breaker, including forms of internal separation: form 1 has none, form 2 separates busbars from functional units, form 3 also separates functional units from each other, and form 4 also separates the terminals from each other. IEC TS 61641 gives methods of verifying that an assembly limits injury and damage from an internal arc fault.

ParameterTypical rating or rangeWhat it decides
Rated current, frame and sensor630 to 6300 A at 40 degrees Celsius (104 F)Continuous load before derating
Rated operational voltage Ue690 V AC; up to 1000 V AC or 1500 V DCSystems it may be used on
Insulation and impulse voltage, Ui and Uimp1000 V and 12 kVDielectric test level, creepage, surge withstand
Ultimate breaking capacity Icu42 to 200 kA at 400 to 415 VHighest fault current the breaker interrupts
Service breaking capacity Ics25 to 100 percent of Icu, commonly 100 percentCondition after a fault near the rating
Short-time withstand current Icw42 to 120 kA for 1 sFault current held while a downstream device trips
Making capacity Icm88 to 440 kA peakPeak current the breaker may close onto
Poles3 or 4, neutral at 100 percent of the phase ratingNeutral switching and protection
Trip thresholdsL 0.4 to 1 x In, S 0.6 to 10 x In, I 1.5 to 15 x In, G 0.1 to 1 x InCoordination with load and downstream devices
Breaking time40 ms below Icw, 25 ms aboveArc energy and contact wear per operation
Ambient temperaturefrom -25 degrees Celsius (-13 F) to 70 degrees Celsius (158 F)Derating inside the cubicle
Altitude2000 m (6562 ft) without deratingInsulation strength and cooling at the site
Chapter 4 / 06

Air Circuit Breaker Selection and Duty Calculations

Selecting an air circuit breaker is a sequence of checks between what the installation imposes and what the breaker declares: load current against rated current, fault current against breaking and withstand ratings, and the tripping plan against the settings the trip unit offers. The table after them lists the decisions that recur on every inquiry.

Start with the load. The long-time setting Ir must lie above the design current IB and below Iz, the current the cables and busbars allow. The frame is chosen so that the sensor rating sits at or just above the design current; Ir then adjusts from 0.4 to 1 times the sensor rating, so one frame covers a range of loads. Ratings are stated at the reference ambient of 40 degrees Celsius (104 F), and a breaker inside a cubicle runs warmer, so its current must be reduced. A 125 A breaker carries 117 A at 50 degrees Celsius (122 F) and 109 A at 60 degrees Celsius (140 F), and one large family keeps 87 percent of a 2000 A rating at 70 degrees Celsius (158 F).

Altitude and atmosphere add corrections. One family keeps its rated performance up to 2000 m (6562 ft); above that the thinner air weakens dielectric strength and cooling, so at 3000 m (9843 ft) the same breaker is rated 607 V in place of 690 V and 98 percent of its current, and at 5000 m (16404 ft) 470 V and 90 percent. The service range is from -25 degrees Celsius (-13 F) to 70 degrees Celsius (158 F) at pollution degree 3; qualified versions cover corrosive or seismic sites. The arc chutes vent to atmosphere, so dust in the cubicle reaches the interrupters, and a dirty site needs a shorter inspection interval. Before installation it is stored clean, dry and ventilated, with heat against condensation if needed.

The fault level is checked at the service voltage against three ratings. The prospective short-circuit current at the breaker terminals must not exceed Icu at that voltage; the peak must stay within Icm; and for a breaker that delays its trip, the current must stay within Icw for the set delay. The power factor of the fault loop falls as the current rises, and the standard test values are 0.5 between 6 and 10 kA, 0.3 between 10 and 20 kA, 0.25 between 20 and 50 kA and 0.2 above 50 kA, with the making factor rising from 1.7 to 2.2 over the same steps. A breaker with an Icu of 100 kA therefore has a making capacity of 220 kA peak.

Selectivity is the plan that decides which breaker trips. With time selectivity the upstream breaker has its instantaneous element off and its short-time element on, so it holds the fault while the feeder breaker clears it; the limit of selectivity is then the upstream Icw. Zone selectivity shortens the delay: each breaker that sees a fault signals the one above it, which holds its delay only while it receives that signal from below and otherwise trips at once. Current selectivity keeps the upstream instantaneous threshold above any fault current a downstream device has to clear. Cascading, or back-up protection, is the opposite choice: a current-limiting breaker upstream lets weaker breakers be used downstream, but it sacrifices selectivity and continuity and holds only for pairs the maker has tested.

Trip settings follow the load. The long-time curve protects cables and transformers, and thermal memory keeps count of heat from earlier overloads. Short-time and instantaneous thresholds are set above the inrush of large motors, whether started direct on line or through a soft starter, and above transformer inrush, or a start-up function raises the S, I and G thresholds for a set time after closing. Ground-fault protection is derived from the sum of the phase and neutral currents or from an external toroid, with its own delay. Generator incomers need reverse-power, voltage and frequency functions, and a bus-coupler between a utility supply and a diesel generator needs synchrocheck before closing.

DecisionWhat to checkTypical choice
Frame and sensorDesign current at cubicle temperature; Ir above it and below cable ampacitySmallest sensor that keeps Ir above the design current
Breaking capacityProspective fault current at the breaker, at its service voltageIcu above the prospective current, with margin for supply growth
Withstand and delayIcw against the delay the downstream devices needCategory B with the instantaneous element off for a main or bus-coupler
SelectivityUltimate selectivity limit of each pair of breakers in seriesTime or zone selectivity; cascading only from the maker's tables
MountingNeed to replace the breaker without touching busbarsDrawout for incomers and couplers; fixed where space is tight
EnvironmentCubicle temperature, altitude, corrosive or seismic siteDerated current, a higher-voltage version or a qualified version
DutyTransformer, generator or large motor load on the feederStart-up function; generator or measuring trip unit; synchrocheck on a coupler
Neutral and earth faultWhether the neutral is distributed and switched3 or 4 poles; neutral protection at 50 to 200 percent; G or external toroid
Accessories and supplySources of trip and close commands; auxiliary voltage availableOpening and closing releases, undervoltage release, auxiliary contacts, motor operator
Chapter 5 / 06

Air Circuit Breaker Installation, Maintenance, and Failure Modes

An air circuit breaker is a high-energy mechanism bolted to busbars that can deliver the full short-circuit current of the source, and most service problems begin at a joint, a latch or a trip coil. The steps below put a drawout breaker into service; the paragraphs that follow cover connections, commissioning, maintenance and the failures each check catches.

  1. Inspect the breaker for transit damage, remove the shipping braces, and confirm that every arc chute and interphase barrier is in place.
  2. Set the compartment rails, lift the breaker with its lifting adapter, and push it to the remove position.
  3. Lever it to the test position, charge the springs, and close and trip it several times by hand and electrically, watching the indicators.
  4. Set the trip unit to the coordination study and test each protection function through its test port, in the test position and never in connect.
  5. Lever the breaker to connect until the stop is felt, remove the crank, and check that the shutters and auxiliary plugs have made up.

Installation is a matter of heat, force and insulation. The breaker stands upright in its compartment and can be fed from either the upper or the lower terminals, although a measuring module needs its voltage taps on the supply side to read while open. Busbars bolt to silver-plated copper terminals at the maker's torque, 40 Nm (29.5 lbf ft) on the small frame and 70 Nm (51.6 lbf ft) on the larger frames of one family, with anchorage plates close to the terminals because the electromagnetic force of a short circuit bends unsupported bars. Above about 440 V, fixed breakers need phase separators to hold the insulation distance. Every frame is bonded to the switchboard protective circuit.

The heat the breaker loses has to leave the cubicle. At rated current one family dissipates 31 W at 630 A and 201 W at 1600 A fixed, and about twice that withdrawable, where the isolating contacts add resistance, up to 767 W and 1550 W at 6300 A. That heat, added to busbar and cable losses, sets the cubicle temperature and therefore the derating. Terminals take copper busbars at the rear, front or in spread formation, aluminum through tinned aluminum, or cables directly on small frames. Auxiliary circuits leave through a terminal block and run as control cable to the door devices and the plant control cabinet; the supply arrives by busway or as power cable on a cable tray.

Commissioning checks fall into three groups. Insulation is proved before energization with an insulation resistance tester, and any dielectric test on the main busbars is carried out with the trip unit's measuring module disconnected, because the module is wired internally to the breaker terminals. The trip unit is then tested function by function through its test port, and its current readings are checked against a clamp meter on each phase. Mechanically, the breaker is opened and closed several times, a stored breaker at least 5 times, and each interlock is tried: no racking while closed, no closing between positions, shutters and position indicator correct. A torque mark on every joint and a signed test sheet complete the record.

Maintenance is driven by operations, by faults and by dirt. One instruction book calls for inspection and lubrication after 250 operations on its largest frames and 1,750 on the smallest, or at the end of the first 6 months, then at least yearly; a breaker that has cleared a fault near its rating is inspected withdrawn, with barriers and chutes removed. The work is mostly cleaning with a dry cloth or compressed air, looking for loose hardware, and applying a little lubricant to the latch and trip shaft surfaces, never to a contact. The trip unit is solid state and is tested, not serviced. Work is done by trained staff with the contacts open and the springs discharged, using insulated tools.

Failure modes map onto the parts. Eroded arcing tips and worn arc-chute plates raise contact resistance and arc energy; a loose busbar joint overheats and discolors, which a thermal imager finds before it fails. In the mechanism a chipped charging pawl or a worn trip latch shows as slow charging, a failure to stay closed or repeated trip-free closing. An open trip coil, rating plug or sensor removes protection silently, so modern trip units check their own continuity and raise an alarm, or call on the breaker upstream to open. The worst case is an internal arc, fed by a missing chute or a defeated interlock; separation above form 1 and the barrier in front of the breaker reduce its chance of starting and shield the operator.

CheckInterval or triggerLimit or action
Contact tips, main and arcingYearly; after any fault near the ratingReplace if burned or worn more than 0.030 inch (0.76 mm)
Arc chute splitter platesYearly; after any fault near the ratingReplace the chute if more than 0.25 inch (6.4 mm) is eroded at the top of the V slots
Cleaning and lubricationAfter 250 to 1,750 operations by frame size; at least yearlyDry cloth or compressed air; lubricate latch and trip shaft, never contacts
Trip unit functionsAt commissioning, yearly and after any setting changeInjection test in the test position; replace a unit that fails
Mechanism and interlocksYearly, and after any period of storageSprings, charging pawl, actuator reset, shutters, racking lock, position indicator
Busbar jointsAfter installation and on every thermographic surveyTorque to the maker's value; investigate any hot joint
InsulationBefore energization and after an overhaulInsulation resistance test; measuring module disconnected for dielectric tests
Operation counters and recordsContinuousPlan overhaul within a mechanical life of 12,000 to 25,000 operations
Breaker taken from storageBefore placing in serviceOperate at least 5 times
Chapter 6 / 06

Industry Applications and Procurement Checks for an Air Circuit Breaker

Applications follow from the ratings. Data centers, hospitals and commercial buildings use air circuit breakers as main and coupling devices where a single feeder fault must be cleared without losing the rest of the board. Heavy industry, paper production, oil refining and water treatment use them on the main low-voltage boards of large plants, including those with reactive power compensation banks and drive lines. Marine and offshore installations use versions offered for approval by the shipping registers, and generator plants use trip units built for generator protection. Where power is metered for billing, a certified energy meter stays in circuit; the multifunction power meter built into the trip unit serves operation and diagnostics. A power quality analyzer is brought in to study harmonics and size a harmonic filter.

Integration with the plant decides the accessory list. The opening release accepts trip commands from a fire alarm control panel or an emergency shutdown circuit, and the undervoltage release drops the breaker with the supply that feeds it. Interlocks between incomers and a bus-coupler can be mechanical, by cable between two or three breakers, or logical, programmed in a programmable logic controller instead of hard wiring. The trip unit works self-powered, but an external supply module fed by a DC power supply at 24 to 48 V keeps its display, communication and low-level ground-fault protection alive at light load. Readings and trip records can be reported to a power monitoring system, and trip units, releases and spares are common across a family's frame sizes.

Cost and lead time are driven by rating and by options. Breaking capacity is the largest driver: a frame built for 150 kA or 200 kA needs heavier contacts, a larger arc chute and a stronger mechanism than one built for 42 kA. Drawout mounting costs more than fixed, trip units are priced in steps from dip-switch protection to measuring units, and each accessory, from an undervoltage release to a motor operator, adds to the bill. Lead time lengthens for versions qualified for marine or seismic duty, for service above 690 V, and for certificates with type-test reports. Spare arc chutes, poles, trip units and release coils are best ordered with the breaker; a withdrawable breaker can later be exchanged, or retrofitted into an older cubicle, without new busbars.

An inquiry for an air circuit breaker should state, as a minimum: the system voltage, frequency and grounding arrangement; the design load current and the ambient temperature inside the cubicle; the prospective short-circuit current at the breaker and its X to R ratio or peak; the required Icu, Ics and Icw with the withstand time; three or four poles and whether the neutral is switched or protected; the mounting as fixed or drawout, with the compartment dimensions and the busbar or cable connection; the trip functions, their ranges and the selectivity study they must meet; the auxiliary supply voltage for the motor and releases; every accessory, including opening and closing releases, undervoltage release, auxiliary and trip-signalling contacts, interlocks and communication protocol; the site conditions, including altitude, pollution, corrosive atmosphere and seismic requirement; and the standards and certifications the breaker must meet. The buyer should ask for the rating plate data, type-test certificates for breaking capacity and internal arc if claimed, the coordination tables, the installation and maintenance instructions, the list of recommended spares, and local service and parts.

FAQ

How does an air circuit breaker interrupt a short circuit?

The trip unit senses the overcurrent in each pole and energizes an actuator that releases the trip latch. The contacts part under spring pressure and an arc forms between the arcing tips. The magnetic field of the arc current drives it into the arc chute, a stack of steel splitter plates that cut it into short arcs; their combined voltage drop opposes the source, the plates cool the arc, and it goes out at a current zero, which comes 100 times a second on a 50 Hz system. The spring-charged mechanism fixes the opening speed, and one breaker family clears a fault in 25 to 40 ms.

What types of air circuit breaker are available?

Air circuit breakers are grouped by mounting, by trip unit and by interruption. Fixed types bolt to the busbars and save space; drawout types run into a cradle with disconnect, test and connect positions for quick replacement. Electronic trip units with long-time, short-time, instantaneous and ground-fault functions are standard; older units were thermal-magnetic. A current-limiting type opens before the fault peak and gives up short-time withstand, and an integrally fused type adds series fuses for higher interrupting ratings. Switch-disconnector versions have the same frame without a trip unit. Frames cover three and four poles and versions for higher AC voltage and for DC.

Which air circuit breaker ratings matter most?

Five ratings carry the specification. Rated current, stated at 40 degrees Celsius (104 F), must exceed the load after derating for cubicle temperature. Rated ultimate breaking capacity Icu must exceed the prospective fault current at the service voltage. Rated service breaking capacity Ics, a percentage of Icu, states what the breaker can interrupt and still return to service. Rated short-time withstand current Icw, usually for 1 s, is the fault current it can hold while a downstream device trips, and makes time selectivity possible. Rated making capacity Icm is the peak it can close onto. Utilization category B confirms that a short-time rating exists.

How do I choose the right air circuit breaker size?

Choose the smallest frame whose sensor rating sits at or just above the design current, then set the long-time pickup below the ampacity of the cables and busbars. Apply derating for the temperature inside the cubicle and for altitude above 2000 m (6562 ft). Check the fault current at the breaker against Icu, Icm and Icw at the service voltage, and allow for future growth of the supply. Decide the selectivity plan next: a main or bus-coupler breaker normally has its instantaneous element off and a short-time delay on, which requires category B. Finish with the accessories, the mounting and the trip unit version the duty needs.

What maintenance does an air circuit breaker need?

Maintenance is mostly inspection and cleaning on a schedule set by the number of operations, usually yearly and sooner in dusty rooms. Contacts and arc chutes are inspected after any fault near the breaker's rating; arcing tips are renewed when burned or worn past the maker's limit, and an arc chute when its splitter plates are eroded. Latch and trip surfaces get a little lubricant; contacts must stay free of it. The trip unit is tested through its test port rather than opened, the mechanism is exercised several times, and busbar joints are checked for tightness and heat. A breaker taken from storage is operated at least 5 times before service.

What affects the cost and lead time of an air circuit breaker?

Breaking capacity is the largest cost driver, because a 150 kA or 200 kA frame needs heavier contacts, a larger arc chute and a stronger mechanism than a 42 kA one. Drawout mounting, a measuring or communicating trip unit, four poles and accessories such as undervoltage releases and a motor operator each add to the price. Lead time grows with versions qualified for marine or seismic duty, with higher-voltage service and with type-test reports and special certificates. Ordering the recommended spares with the breaker avoids long outages later. The selectivity study and the maker's coordination tables belong in the inquiry.

Which standards apply to air circuit breakers, and are they safe to operate?

They are safe when their interlocks are left intact and the switchboard is built for the duty. Drawout breakers lock the racking device while closed, prevent closing between positions, discharge their springs when removed, and cover live isolating contacts with shutters. IEC 60947-2 is the product standard; IEEE C37.13 and UL 1066 apply in North America. IEC 61439-2 governs the assembly and its forms of separation, and IEC TS 61641 covers verification of internal arc-fault protection, which limits injury and damage if a fault arcs inside the cubicle. Work is done by trained staff with the breaker open and its springs discharged.

Sources

  1. IEC: 60947-2 Low-voltage switchgear and controlgear, Part 2 Circuit-breakers
  2. UL: 1066 Power Circuit Breakers up to 1000 V AC and 1500 V DC Used in Enclosures
  3. ABB: SACE Emax 2 low voltage air circuit-breaker technical catalogue (PDF)
  4. Eaton: instruction booklet for low voltage power circuit breakers (PDF)
  5. Schneider Electric Electrical Installation Guide: fundamental characteristics of a circuit-breaker
  6. Schneider Electric Electrical Installation Guide: other characteristics of a circuit-breaker